10 Technical data
68
10.5 Measuring circuit monitoring
10.6 Voltage supply
RTD temperature probes
Thermocouples
Current 4 to 20 mA
Overrange
and underrange
is detected
in the display, ">>>>" flashes for overrange and "<<<<" for underrange.
Probe/cable break
is detected
">>>>" flashes in the display; relay output controller K1 is inac-
tive
">>>>" flashes in the display;
relay output controller K1 is in-
active
Probe short circuit
is detected
"<<<<" flashes in the display;
relay output controller K1 is inac-
tive
is not detected
"<<<<" flashes in the display;
relay output controller K1 is in-
active
Voltage supply
AC/DC 20 to 30 V, 48 to 63 Hz
AC 110 to 240 V, +10/-15 %, 48 to 63 Hz
Power consumption
12 VA
Power loss
< 12 W