6 Safety-related applications
22
6.5
Operating mode
Operating mode according to IEC/EN 61508: "low-demand mode" or "high-demand mode".
6.6
Failure behavior and required reaction
•
The safe state is adopted when a line fault is detected or if the voltage supply fails.
•
The safe state is achieved by disconnecting the connection terminals.
6.7
Safety/integrity requirements
Safety characteristics
•
Type A device (according to IEC/EN 61508-1 and 61508-2)
•
Safety integrity level (SIL) 2
•
Systematic capability (SC) 2
•
HFT 0
•
Low-demand mode or high-demand mode
•
MTTR = 24 h
•
1-channel: 1001 structure
•
Ambient temperature 40 °C
•
Mission time 10 years
•
Proof test coverage (PTC) 99 %
List of configurations considered
Configuration Operation
Relay contact
Relay load
C1
Not inverted
Normally closed
contact
Load field IV, up to AC 250 V, 2 A or DC 30 V,
2 A resistive or weakly inductive load
(cos
ɸ
> 0.95)
C2
Not inverted
Normally closed
contact
Load field II, up to AC 120 V, 2 A resistive or
weakly inductive load (cos
ɸ
> 0.95)
C3
Inverted
Normally closed
contact
Load field IV, up to AC 250 V, 2 A or DC 30 V,
2 A resistive or weakly inductive load
(cos
ɸ
> 0.95)
C4
Inverted
Normally closed
contact
Load field II, up to AC 120 V, 0.2 A resistive or
weakly inductive load (cos
ɸ
> 0.95)
C5
Not inverted
Normally open con-
tact
Load field IV, up to AC 250 V, 2 A or DC 30 V,
2 A resistive or weakly inductive load
(cos
ɸ
> 0.95)
C6
Not inverted
Normally open con-
tact
Load field II, up to AC 120 V, 0.2 A resistive or
weakly inductive load (cos
ɸ
> 0.95)
C7
Inverted
Normally open con-
tact
Load field IV, up to AC 250 V, 2 A or DC 30 V,
2 A resistive or weakly inductive load
(cos
ɸ
> 0.95)
C8
Inverted
Normally open con-
tact
Load field II, up to AC 120 V, 0.2 A resistive or
weakly inductive load (cos
ɸ
> 0.95)
Содержание Ex-i
Страница 1: ...70754000T99Z001K000 V1 00 EN 00751108 2021 03 17 JUMO Ex i Isolating Switch Amplifier Safety Manual...
Страница 2: ......
Страница 10: ...2 Safety requirements and installation instructions 10...
Страница 18: ...4 Configuration 18...
Страница 20: ...5 Comparison of the safety data 20...
Страница 30: ...6 Safety related applications 30...
Страница 31: ......