4 Configuration
4
Configuration
NOTICE!
Only switch the DIP switch when the device is de-energized.
By default upon delivery, all DIP switches are in the "I" position.
4.1
Effective direction
Switch DIP 1 = channel 1, DIP 3 = channel 2
The effective direction is set using the DIP switch DIP 1 (for channel 1) and DIP 3 (for channel 3).
4.2
Line fault detection
Switch DIP 2 = channel 1, DIP 4 = channel 2
The line fault detection is set using the switch DIP 2 (for channel 1) and DIP 4 (for channel 2).
If line fault detection is enabled, the relay is de-energized when there is an interruption or short-circuit of
the line to the sensor, meaning that the output is put into the safe, not-conductive state.
The red LED (LF) flashes (NAMUR NE 44).
The response range according to EN 60947-5-6 for the line fault report:
(7)
DIP switch
Channel 2
Channel 2
DIP 1
DIP 3
normal phase (I)
DIP 1
DIP 3
inverse phase (II)
Relay output
normal phase (I)
inverse phase (II)
switched if
I > 2.1 mA
I < 1.2 mA
in rest position if
I < 1.2 mA
I > 2.1 mA
I
= Line fault detection disabled.
Not admissible for safety-related applications!
II
= Line fault detection enabled.
Line break
0.05 mA < I
IN
< 0.35 mA
Short-circuit
100
Ω
< R
Sensor
< 360
Ω
Содержание Ex-i
Страница 1: ...70754000T99Z001K000 V1 00 EN 00751108 2021 03 17 JUMO Ex i Isolating Switch Amplifier Safety Manual...
Страница 2: ......
Страница 10: ...2 Safety requirements and installation instructions 10...
Страница 18: ...4 Configuration 18...
Страница 20: ...5 Comparison of the safety data 20...
Страница 30: ...6 Safety related applications 30...
Страница 31: ......