4
V1.00/EN/00698632 - 70710100T90Z001K000
Mounting
Only technicians who are familiar with the technical terms, warnings, and instructions in the manual and who are able to
follow these should connect the device.
Should there be any doubt as to the correct handling of the device, please contact your local distributor or, alternatively,
JUMO GmbH & Co. KG
www.jumo.net
Mounting and connection of the device should comply with national legislation for mounting of electric materials, i.e. wire
cross section, protective fuse, and location.
Descriptions of input / output and supply connections are shown in this installation guide and on the side label.
The device is provided with field wiring terminals and shall be supplied from a Power Supply having double / reinforced
insulation. A power switch should be easily accessible and close to the device. The power switch shall be marked as the
disconnecting unit for the device.
JUMO dTRANS T/S08 must be mounted on a DIN rail according to EN 60715.
UL installation
Use 60/75°C copper conducters only.
Wire size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . AWG 26-12
UL file number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E201387
The device is an Open Type Listed Process Control Equipment. To prevent injury resulting from accessability to live parts the
equipment must be installed in an enclosure.
The power supply unit must comply with NEC Class 2, as described by the National Electrical Code® (ANSI / NFPA 70).
IECEx, ATEX installation in Zone 2
IECEx DEK 18.0006 X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Ex nA IIC T4 Gc
DEKRA 18ATEX0007 X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . II 3G Ex nA IIC T4 Gc
For safe installation the following must be observed. The device shall only be installed by qualified personnel who are familiar
with the national and international laws, directives and standards that apply to this area.
Year of manufacture can be taken from the first two digits in the serial number.
The devices shall be installed in a suitable enclosure providing a degree of protection of at least IP54 according to EN60529,
taking into account the environmental conditions under which the equipment will be used.