V1.00/EN/00698632 - 70710100T90Z001K000
17
DIP-switch configuration
The devices can be configured via DIP-switches. The DIP-switches are located on the side of the device and can be adjusted
with a small screwdriver or other implement.
Default configurations
(Power must be cycled after DIP-switch positions are changed).
JUMO dTRANS T08 02 and
JUMO dTRANS T08 12
Pt100
JUMO dTRANS T08 01 and
JUMO dTRANS T08 11
TC J & K
*JUMO dTRANS T08 01 -
only int CJC
JUMO dTRANS T08 31
Pt100 & TC J/K
JUMO dTRANS T08 13 and
JUMO dTRANS T08 37
Pt100 & TC J/K + HART
JUMO dTRANS T08 33
Pt100
JUMO dTRANS T08 02,
JUMO dTRANS T08 12,
JUMO dTRANS T08 31,
JUMO dTRANS T08 33
JUMO dTRANS T08 01,
JUMO dTRANS T08 11
JUMO dTRANS T08 13,
JUMO dTRANS T08 37
Sensor type
Pt100, 3 wire
TC K (int. CJC)
Pt100, 3 wire
Output range
4...20 mA
4...20 mA
4...20 mA
Error detection
Short circuit detection
Broken circuit detection
Short circuit detection
Short circuit detection
Broken circuit detection
Error output current
3.5 mA
3.5 mA
3.5 mA
Noise suppression
50 Hz
50 Hz
50 Hz
Input lower limit
0°C
0°C
0°C
Input upper limit
150°C
600°C
150°C
Response time
< 30 ms
< 30 ms
< 60 ms
Configuration mode
-
-
DIP switch configuration