4 Setup program

4.3

Connection layout for calibration

The following connection layout applies to transmitters with basic
type extension 880 or 990.

NOTE!

For the communication between transmitter and setup pro-
gram, the transmitter has to be supplied with the appropri-
ate voltage.

USB/SPI

+

-

+

-

-

+

Supply voltage

7.5 — 30V

/ 25mA

DC

Indicator

4 — 20mA

Precision
decade resistor

Supply voltage

15 — 30V DC

Indicator

0 — 10V

Precision
decade resistor

dTRANS T03 BU

dTRANS T03 B

USB

USB/SPI converter

Adapter

Содержание dTRANS T03 B

Страница 1: ...digitaler Einstellung Analog transmitter with digital adjustment Betriebsanleitung Operating Manual 70703000T90Z000K000 V2 01 DE EN 00392647 dTRANS T03 J 707030 dTRANS T03 B 707031 dTRANS T03 BU 70703...

Страница 2: ......

Страница 3: ...S T03 BU Typ 707033 14 3 5 Anschluss dTRANS T03 TU Typ 707034 15 3 6 Abmessungen 16 3 7 Anschlussbeispiel Stromausgang mit Netzger t 19 3 8 Anschlussbeispiel Stromausgang mit Speisetrenner 19 3 9 Ansc...

Страница 4: ...Nummer editieren 33 4 7 5 Datentransfer zum Ger t 34 4 7 6 Datentransfer vom Ger t 34 4 7 7 Feinabgleich 35 4 8 Messbereich abgleichen 36 4 9 Messbereichsspanne 39 5 Technische Daten Zweidraht Messumf...

Страница 5: ...en bei der Inbetriebnahme Schwierigkeiten auftreten bitten wir Sie keine Manipulationen vorzunehmen die Ihren Gew hrlei stungsanspruch gef hrden k nnen Warnende Zeichen VORSICHT Dieses Zeichen in Verb...

Страница 6: ...loge Dauermessung statt digitaler Messrate Hieraus resultiert ein rauscharmes und st rfestes Ausgangssignal H chste Pr zision selbst bei kleinen Messbereichen wird durch die messbereichs spezifische V...

Страница 7: ...ew nschte Messbereich ohne Sensorsimulation und Messung konfiguriert 1 3 Funktions bersicht dTRANS T03 J Typ 707030 dTRANS T03 B Typ 707031 dTRANS T03 T Typ 707032 dTRANS T03 BU Typ 707033 dTRANS T03...

Страница 8: ...TN Die Teilenummer kennzeichnet einen Artikel im Katalog eindeutig Sie dient der Kommunikation zwischen Kunden und Verkauf F Nr Der Fabrikationsnummer kann das Produktionsdatum Jahr Woche entnommen we...

Страница 9: ...loger Dreidraht Messumformer zur Montage auf Tragschiene 2 Grundtyperg nzung x x x x x 880 abgleichbara a werksseitig eingestellt F hlerbruch positiv Leitungswiderstand 0 x x x x x 881 konfigurierbara...

Страница 10: ...ontage von Typ 707031 und Typ 707033 auf Tragschiene Teile Nr 00352463 Netzger te 1 und 4 fach Typenblatt 707500 HINWEIS abgleichbare Messumformer Abgleichbare Messumformer Grundtyperg nzung 880 oder...

Страница 11: ...ung DC 7 5 bis 30 V bzw Stromausgang 4 bis 20 mA 1 2 RB B rdenwiderstand Ub Spannungs versorgung Analoge Eing nge Widerstands thermometer in Zweileiter schaltung 3 4 serienm ig RL 0 RL Leitungswider s...

Страница 12: ...orgung Analoge Eing nge Widerstands thermometer in Zweileiter schaltung 3 5 6 serienm ig RL 0 RL Leitungswider stand je Leiter Widerstands thermometer in Dreileiter schaltung 3 5 6 RL 11 RL Leitungswi...

Страница 13: ...30 V bzw Stromausgang 4 bis 20 mA 81 82 RB B rdenwiderstand Ub Spannungs versorgung Analoge Eing nge Widerstands thermometer in Zweileiter schaltung 11 12 13 serienm ig RL 0 RL Leitungswider stand je...

Страница 14: ...g nge Widerstands thermometer in Zweileiter schaltung 4 5 6 serienm ig RL 0 RL Leitungswider stand je Leiter Widerstands thermometer in Dreileiter schaltung 4 5 6 RL 11 RL Leitungswider stand je Leite...

Страница 15: ...sorgung DC 15 bis 30 V Spannungs ausgang 0 bis 10 V 81 82 82 83 Last 10 k Analoge Eing nge Widerstands thermometer in Zweileiter schaltung 11 12 13 serienm ig RL 0 RL Leitungswider stand je Leiter Wid...

Страница 16: ...16 3 Installation 3 6 Abmessungen dTRANS T03 J Typ 707030 dTRANS T03 B Typ 707031 dTRANS T03 BU Typ 707033 Setup 44 1 0 21 1 0 7 5 Setup...

Страница 17: ...17 3 Installation dTRANS T03 T Typ 707032 dTRANS T03 TU Typ 707034 Tragschiene Hutschiene 35 mm 7 5 mm EN 60715 Tragschiene Hutschiene 15 mm EN 60715 Tragschiene G Schiene EN 60715 Setup...

Страница 18: ...18 3 Installation Aufbaugeh use HINWEIS Beim Typenzusatz 243 ist der Messumformer im Aufbau geh use montiert 55 44 16 5 1 5 80 128 42 52 14 4 2...

Страница 19: ...tallation 3 7 Anschlussbeispiel Stromausgang mit Netzger t Zweidraht Messumformer Typ 707030 707031 707032 3 8 Anschlussbeispiel Stromausgang mit Speisetrenner Zweidraht Messumformer Typ 707030 707031...

Страница 20: ...20 3 Installation 3 9 Anschlussbeispiel Spannungsausgang Dreidraht Messumformer Typ 707033 707034 Netzger t DC 15 30 V L1 N 0 10 V 0 10 V Registrier ger t Anzeige ger t Regler Dreidraht Messumformer...

Страница 21: ...Hauptspeicher 50 MB freier Festplattenspeicher 1 freie USB Schnittstelle Windows 7 Windows 8 und Windows 10 jeweils 32 Bit und 64 Bit Version 4 2 abgleichbare konfigurierbare Parameter TAG Nummer 8 Z...

Страница 22: ...munikation zwischen Messumformer und Setup Programm ist es erforderlich dass der Messumfor mer mit der entsprechenden Spannung versorgt wird USB SPI Spannungsversorgung DC 7 5 30V 25mA Anzeigeger t 4...

Страница 23: ...Grundtyperg nzung 881 oder 991 HINWEIS F r die Kommunikation zwischen Messumformer und Setup Programm ist es erforderlich dass der Messumfor mer mit der entsprechenden Spannung versorgt wird USB SPI S...

Страница 24: ...p Programm 4 5 Programmstart Nach dem Start des Setup Programms erscheint zun chst der Ge r te Assistent Durch ihn wird entschieden wie die Setup Software gestartet wird h Online oder Offline Betrieb...

Страница 25: ...e bessere L sung d h dem Offline Betrieb vorzuziehen Fehleinstellungen k nnen hiermit vermieden werden 4 5 2 Offline Betrieb Im Offline Betrieb muss der Anwender entscheiden welchen Ger tetyp er mit d...

Страница 26: ...tup Programms gestartet Symbolleiste Die Symbolleiste enth lt ausgew hlte Funktionen Sie k nnen durch Bet tigen der linken Maustaste gestartet werden Bleiben Sie mit dem Mauszeiger ber einem der Symbo...

Страница 27: ...Einstellungen einer Konfigurationsdatei Mit einem Doppelklick linke Maustaste auf einen Eintrag im Ar beitsbereich starten Sie die entsprechende Funktion analog zum Funktionsaufruf ber die Men leiste...

Страница 28: ...ie Symbolleiste stehen die Funktionen Datentransfer zum Ger t und Datentransfer vom Ger t zur Verf gung ber das Men Extras oder die Symbolleiste steht die Funktion Feinabgleich zur Verf gung 4 7 1 Set...

Страница 29: ...etupdaten Info gehen hier jedoch nicht verloren 4 7 3 Eingang editieren Mit der Funktion Editieren Eingang editieren wird die Einstellung des Messumformers vorgenommen Mit der Men funktion Datentransf...

Страница 30: ...anfang Im folgenden Bild wird eine fehlerhafte Eingabe gezeigt HINWEIS abgleichbare Messumformer Abgleichbare Messumformer Grundtyperg nzung 880 oder 990 m ssen zu einer nderung des Messbereichs neu a...

Страница 31: ...iagramm anzeigen wer den Ihnen alle m glichen Messbereichsanfangswerte in Abh ngig keit der Messbereichsspanne angezeigt vKapitel 4 9 Messbereichsspanne h Bet tigen Sie die Schaltfl che Messbereichs D...

Страница 32: ...g und Messbereichsorgani sation h Wechseln Sie ins Fenster Eingang h Ver ndern Sie den Messbereichsanfang oder das Messbereichs ende Der Schnittpunkt der horizontalen und der vertikalen Linie im Fen s...

Страница 33: ...ans fer abgeglichen werden Soll nur die TAG Nummer eingegeben werden alle anderen Einstel lungen bleiben erhalten benutzten Sie die Funktion Online Editie ren h Positionieren Sie den Mauszeiger im Arb...

Страница 34: ...m ssen vor dem Datentransfer abge glichen werden vKapitel 4 8 Messbereich abgleichen 4 7 6 Datentransfer vom Ger t Mit Datentransfer Datentransfer vom Ger t wird die aktuelle Ein stellung eines Messu...

Страница 35: ...unktion erscheint das Fenster Feinabgleich h Mit Hilfe der Pfeil Schaltfl chen nehmen Sie den Feinabgleich vor und schlie en ihn durch OK ab Durch Bet tigen der Schaltfl che Abbrechen wird der Feinabg...

Страница 36: ...n Grundtyperg nzung 880 oder 990 muss vor dem Datentransfer ins Ger t durchgef hrt werden Ohne erfolgreiches Abgleichen ist ein Datentransfer in den Mess umformer nicht m glich vKapitel 4 7 5 Datentra...

Страница 37: ...n Ge nauigkeiten sind folgende Voraussetzungen zu schaffen Pr zisionswiderstandsdekade Genauigkeit 0 05 Aufl sung 0 01 V Strom Spannungs Messger t Genauigkeit 0 05 10 A 5 mV Warmlaufzeit 2 min Messumf...

Страница 38: ...Funktion Datentransfer Datentransfer zum Ge r t oder Icon in der Symbolleiste und bet tigen Sie die Schalt fl che h Folgen Sie den Anweisungen des Setup Programms Nach erfolgreichem Abgleich steht di...

Страница 39: ...39 4 Setup Programm 4 9 Messbereichsspanne Messbereichsspanne Messbereichsende Messbereichsanfang...

Страница 40: ...r Schaltfl che Abgleichen den Abgleichvorgang Folgen Sie den weiteren Anweisungen des Setup Programms HINWEIS Der Messbereichsanfang ist so zu w hlen dass er inner halb der grauen Fl che liegt HINWEIS...

Страница 41: ...g bei Messspannen 75 K feste Nullpunkteinstellung 40 C 20 C 0 C 20 C 40 C a a 30 C 10 C 0 C 10 C 30 C auf Anfrage m glich bei Messspanne 75 K 50 C bei Messspannen 75 K siehe Seite 39 Sensorleitungswid...

Страница 42: ...gen DC 24 V bei ca 22 C Abgleich Konfigurationsgenauigkeit 0 2 a b c oder 0 2 K b b Der gr ere Wert hat G ltigkeit c Bei Messbereichsendwerten 600 C betr gt die Abgleich Konfigurationsgenauigkeit 0 4...

Страница 43: ...bweichung von 22 C a a Alle Genauigkeitsangaben in beziehen sich auf den Messbereichsendwert 20 mA Klimafestigkeit rel Feuchte 95 im Jahresmittel ohne Betauung Vibrationsfestigkeit gem GL Kennlinie 2...

Страница 44: ...Durchmesser Draht 0 3 bis 1 0 mm Drehmoment max 0 15 Nm 1 75 mm Drehmoment max 0 6 Nm 2 5 mm Drehmoment max 0 6 Nm Montage im Anschlusskopf Form J im Anschlusskopf Form B DIN EN 50446 im Aufbaugeh use...

Страница 45: ...ei Messspannen 75 K feste Nullpunkteinstellung 40 C 20 C 0 C 20 C 40 C bei Messspanne 75 K 50 C bei Messspannen 75 K siehe Seite 39 Sensorleitungswiderstand bei Dreileiteranschluss 11 je Leitung Senso...

Страница 46: ...C Abgleich Konfigurationsgenauigkeit 0 2 a b c oder 0 2 K b b Der gr ere Wert hat G ltigkeit c Bei Messbereichsendwerten 600 C betr gt die Abgleich Konfigurationsgenauigkeit 0 4 Spannungsversorgung U...

Страница 47: ...g von 22 C a a Alle Genauigkeitsangaben in beziehen sich auf den Messbereichsendwert 10 V Klimafestigkeit rel Feuchte 95 im Jahresmittel ohne Betauung Vibrationsfestigkeit gem GL Kennlinie 2 EMV St ra...

Страница 48: ...Drehmoment max 0 6 Nm 2 5 mm Drehmoment max 0 6 Nm Montage im Anschlusskopf Form B DIN EN 50446 im Aufbaugeh use auf Anfrage im Schaltschrank Befestigungselement erforderlich auf Hutschiene 35 mm 7 5...

Страница 49: ...3UR HVVDQVFKOXVV 1XWV 0XWWHU 6FUHZ 6FKUDXEH d 7KLV WDEOH LV SUHSDUHG LQ DFFRUGDQFH ZLWK WKH SURYLVLRQV 6 7 7 QGLFDWH WKH KD DUGRXV VXEVWDQFHV LQ DOO KRPRJHQHRXV PDWHULDOV IRU WKH SDUW LV EHORZ WKH OL...

Страница 50: ......

Страница 51: ......

Страница 52: ...WUD H XOGD HUPDQ 3RVWDGUHVVH XOGD HUPDQ 802 0HVV XQG 5HJHOJHUlWH PE 3IDUUJDVVH LHQ XVWULD 7HFKQLVFKHU 6XSSRUW gVWHUUHLFK 7HOHIRQ 7HOHID 0DLO QWHUQHW LQIR DW MXPR QHW ZZZ MXPR DW 7HOHIRQ 7HOHID 0DLO LQ...

Страница 53: ...JUMO dTRANS T03 Analog transmitter with digital adjustment Operating Manual 70703000T90Z000K000 dTRANS T03 J 707030 dTRANS T03 B 707031 dTRANS T03 BU 707033 dTRANS T03 TU 707034 dTRANS T03 T 707032...

Страница 54: ......

Страница 55: ...RANS T03 BU Type 707033 14 3 5 Connection dTRANS T03 TU Type 707034 15 3 6 Dimensions 16 3 7 Connection example current output with supply unit 19 3 8 Connection example current output with supply iso...

Страница 56: ...ing the TAG number 33 4 7 5 Data transfer to device 34 4 7 6 Data transfer from device 34 4 7 7 Fine calibration 35 4 8 Calibrating the range 36 4 9 Range span 39 5 Technical data for 2 wire transmitt...

Страница 57: ...ll times If difficulties occur during commissioning please refrain from car rying out any manipulations that could jeopardize your warranty rights Warning symbols CAUTION This symbol in combination wi...

Страница 58: ...of digital sampling rate resulting in a low noise output signal that is insensitive to interference A very high degree of precision even with small ranges is ensured thanks to the range specific gain...

Страница 59: ...simulation and measurement 1 3 Overview of function dTRANS T03 J Type 707030 dTRANS T03 B Type 707031 dTRANS T03 T Type 707032 dTRANS T03 BU Type 707033 dTRANS T03 TU Type 707034 Input Pt100 Pt100 Pt1...

Страница 60: ...2 2 Order details Part number TN The part number uniquely idetifies an article in the catalog It is im portant for communication between the customer and the sales de partment Serial number F Nr The...

Страница 61: ...U analog 3 wire transmitter for rail mounting 2 Basic type extensions x x x x x 880 adjustablea a factory set probe break positive lead resistance 0 x x x x x 881 configurablea x x x x x 990 adjustabl...

Страница 62: ...ounting Type 707031 and Type 707033 on rail part no 00352463 Supply units 1 way and 4 way Data Sheet 707500 NOTE Adjustable transmitters Adjustable transmitters basic type extension 880 or 990 must be...

Страница 63: ...ly voltage DC 7 5 to 30V or current output 4 to 20mA 1 2 RB burden resistance Ub supply voltage Analog inputs Resistance thermometer in 2 wire circuit 3 4 RL 0 as standard RL lead resistance per condu...

Страница 64: ...g inputs Resistance thermometer in 2 wire circuit 3 5 6 RL 0 as standard RL lead resistance per conductor Resistance thermometer in 3 wire circuit 3 5 6 RL 11 RL lead resistance per conductor CAUTION...

Страница 65: ...5 to 30V or current output 4 to 20mA 81 82 RB burden resistance Ub supply voltage Analog inputs Resistance thermometer in 2 wire circuit 11 12 13 RL 0 as standard RL lead resistance per conductor Res...

Страница 66: ...e thermometer in 2 wire circuit 4 5 6 RL 0 as standard RL lead resistance per conductor Resistance thermometer in 3 wire circuit 4 5 6 RL 11 RL lead resistance per conductor CAUTION When mounting the...

Страница 67: ...Supply voltage DC 15 to 30V Voltage output 0 to 10V 81 82 82 83 load 10k Analog inputs Resistance thermometer in 2 wire circuit 11 12 13 RL 0 as standard RL lead resistance per conductor Resistance th...

Страница 68: ...16 3 Installation 3 6 Dimensions dTRANS T03 J Type 707030 dTRANS T03 B Type 707031 dTRANS T03 BU Type 707033 Setup 44 1 0 21 1 0 7 5 Setup...

Страница 69: ...17 3 Installation dTRANS T03 T Type 707032 dTRANS T03 TU Type 707034 Mounting rail DIN rail 35 mm 7 5 mm EN 60715 Mounting rail DIN rail 15 mm EN 60715 Mounting rail G rail EN 60715 Setup...

Страница 70: ...18 3 Installation Surface mounted housing NOTE Extra code 243 the transmitter is mounted in a surface mounted housing 55 44 16 5 1 5 80 128 42 52 14 4 2...

Страница 71: ...707031 707032 3 8 Connection example current output with supply isolator 2 wire transmitter Type 707030 707031 707032 2 wire transmitter Recorder Indicator Controller Supply unit 7 5 30 V DC 4 20 mA...

Страница 72: ...20 3 Installation 3 9 Connection example voltage output 3 wire transmitter Type 707033 707034 Supply unit 15 30 V DC L1 N 0 10 V 0 10 V Recorder Indicator Controller 3 wire transmitter...

Страница 73: ...patible PC 256 MB main memory 50 MB available on hard disk 1 free USB interface Windows 7 Windows 8 and Windows 10 respectively 32 bit and 64 bit version 4 2 Adjustable configurable parameters TAG num...

Страница 74: ...or 990 NOTE For the communication between transmitter and setup pro gram the transmitter has to be supplied with the appropri ate voltage USB SPI Supply voltage 7 5 30V 25mA DC Indicator 4 20mA Precis...

Страница 75: ...transmitters with basic type extension 881 or 991 NOTE For the communication between transmitter and setup pro gram the transmitter has to be supplied with the appropri ate voltage USB SPI Supply volt...

Страница 76: ...24 4 Setup program 4 5 Program start After starting the setup program the Device Assistant appears which determines how the setup software is started h Select online or off line operation...

Страница 77: ...e mode is always the better choice and preferable to off line operation Wrong settings can be avoided in this way 4 5 2 Off line mode In off line mode the user has to decide which device type he wish...

Страница 78: ...program can be started from the menu bar Toolbar The toolbar contains selected functions They can be started by pressing the left mouse button If you rest the mouse pointer on one of the symbols then...

Страница 79: ...he current settings of a configura tion file You can start the appropriate function by double clicking left mou se button on an entry in the working area just like calling up a function from the menu...

Страница 80: ...functions are available via the Data transfer menu or the toolbar Data transfer to device and Data transfer from device And via the Extras menu or the toolbar the function Fine calibration 4 7 1 Setup...

Страница 81: ...difference however that the Setup data info is not lost 4 7 3 Edit input The Edit Edit input function is available for making the setting on the transmitter By using the menu function Data transfer D...

Страница 82: ...enshot shows such an incorrect entry NOTE Adjustable transmitters Adjustable transmitters basic type extension 880 or 990 must be readjusted after a change in the measuring range Please follow the ins...

Страница 83: ...ow measurement range diagram button all the possible range start values in relation to the range span will be shown to you vChapter 4 9 Range span h Activate the Show measurement range diagram button...

Страница 84: ...ill now see both windows Input and Range organization h Change to the Input window h Alter the range start or range end The point of intersection between the horizontal and the vertical line in the Ra...

Страница 85: ...le transmitters have to be calibrated before the data transfer If you wish to enter the TAG number only all other settings are re tained use the Edit online function h Position the mouse pointer withi...

Страница 86: ...rs have to be calibrated before the data transfer vChapter 4 8 Calibrating the range 4 7 6 Data transfer from device The current setting of the transmitter is read out with Data transfer Data transfer...

Страница 87: ...voltage output After calling up the function the window Fine calibration appears h Perform fine calibration by using the arrow buttons and click OK You can discard fine calibration with Cancel NOTE Wh...

Страница 88: ...nsion 880 or 990 have to be calibrated before the data are transferred to the device If the calibration is not successful the data cannot be transferred to the transmitter vChapter 4 7 5 Data transfer...

Страница 89: ...for achieving the accura cies specified under Technical data Precision decade resistor accuracy 0 05 resolution 0 01 Ammeter voltmeter accuracy 0 05 10 A 5mV Warming up time 2min Connect transmitter a...

Страница 90: ...art the Data transfer Data transfer to device function or the icon from the toolbar and activate the button h Follow the instructions in the setup program After successfully completing the calibration...

Страница 91: ...39 4 Setup program 4 9 Range span range span range end range start...

Страница 92: ...re by activating the Calibrate button The setup program will instruct you further NOTE When selecting the range start make sure it lies within the gray area NOTE For spans that are smaller than 75 C t...

Страница 93: ...C or F Zero shift for spans 75 C fixed zero 40 C 20 C 0 C 20 C 40 C a a 30 C 10 C 0 C 10 C 30 C available upon request for span 75 C 50 C for spans 75 C see page 39 Sensor lead resistance for 3 wire c...

Страница 94: ...rox 22 C Calibration configuration accuracy 0 2 a b c or 0 2 C b b The larger value applies c If the measuring range end value 600 C then the calibration or configuration accuracy is 0 4 Supply voltag...

Страница 95: ...deviation from 22 C a a All accuracies given in refer to the range end value 20 mA Climatic conditions rel humidity 95 annual mean no condensation Vibration strength to GL Characteristic 2 to GL Char...

Страница 96: ...dmissible diameter wire 0 3 to 1 0 mm max torque 0 15 Nm 1 75 mm max torque 0 6 Nm 2 5 mm max torque 0 6 Nm Mounting inside terminal head Form J inside terminal head Form B DIN EN 50446 in surface mou...

Страница 97: ...n C or F Zero shift for spans 75 C fixed zero 40 C 20 C 0 C 20 C 40 C for span 75 C 50 C for spans 75 C see page 39 Sensor lead resistance for 3 wire connection 11 per conductor Sensor lead resistance...

Страница 98: ...tion accuracy 0 2 a b c or 0 2 C b b The larger value applies c If the measuring range end value 600 C then the calibration or configuration accuracy is 0 4 Supply voltage U b DC 15 to 30V The transmi...

Страница 99: ...tion from 22 C a a All accuracies given in refer to the range end value 10 V Climatic conditions rel humidity 95 annual mean no condensation Vibration strength to GL characteristic 2 EMC interference...

Страница 100: ...5 mm max torque 0 6 Nm 2 5 mm max torque 0 6 Nm Mounting inside terminal head Form B DIN EN 50446 in surface mounting case upon request in switchgear cabinet fixing bracket is required on DIN rail 35...

Страница 101: ...3UR HVVDQVFKOXVV 1XWV 0XWWHU 6FUHZ 6FKUDXEH d 7KLV WDEOH LV SUHSDUHG LQ DFFRUGDQFH ZLWK WKH SURYLVLRQV 6 7 7 QGLFDWH WKH KD DUGRXV VXEVWDQFHV LQ DOO KRPRJHQHRXV PDWHULDOV IRU WKH SDUW LV EHORZ WKH OL...

Страница 102: ......

Страница 103: ......

Страница 104: ...address 36035 Fulda Germany Phone 49 661 6003 0 Fax 49 661 6003 607 Email mail jumo net Internet www jumo net JUMO House Temple Bank Riverway Harlow Essex CM20 2DY UK Phone 44 1279 63 55 33 Fax 44 127...

Отзывы: