59
10 Configuration level 1
10.5 Profile controller
The profile controller/generator is configured here. In addition, the response to
a power failure, the profile run and the type of programming are defined here.
CONFIG 1
➔
PROF CTR
Parameter
Value/selection Description
Function
➔
PROGRFCT
PROFCTRL
PROFGEN
CONTRL.
profile controller
profile generator
fixed-setpoint controller
With the “fixed-setpoint controller“
setting, the instrument behaves as
for Type 703570/75.
v
Operating Instructions B70.3570
Restart after
power failure
➔
RESTART
PGMCANCL
CONTINUE
STDSTILL
CONT X%
CONT X
abort profile program
continue
standstill
continue at deviation <x%
continue at process value
(for explanation, see next page)
Profile program
start
➔
PGMSTART
PGMSTART
START X
start at beginning of profile
program (w01)
start at process value
Setpoint input
➔
W INPUT
W RAMP
W STEP
setpoint ramp
setpoint step
setpoint ramp:
setpoint step:
Time/gradient
programming
➔
TIMEGRAD
TIME
DEGC/MIN
time
gradient
Defines in which way segments are
programmed when creating new
profile programs (profile program
editor):
- Time: setpoint/segment time
- Gradient: setpoint/gradient
Factory settings are shown
bold
.