10 Configuration level 1
48
Setpoint limits
setpoint start
setpoint end
➔
WLIMITS
➔
STARTVAL
➔
ENDVALUE
0.
400.
-1999—
0
to +9999
-1999—
400
to +9999
Manual output
➔
Y MANUAL
101.
-100—100
101
= last output
Defines the output on over/
underrange
Manual operating
mode
➔
HANDMODE
ENABLED
INHIBTD
enabled
inhibited
Self-optimisation
➔
TUNE
ENABLED
INHIBTD
enabled
inhibited
Output 1 for
self-optimisation
➔
TUNEOUT1
RELAY
SSRELAY
ANOUTPUT
Relay
solid-state relay and logic output
analogue output
type of controller output 1 fro
self-optimisation
Output 2 for
self-optimisation
➔
TUNEOUT2
RELAY
SSRELAY
ANOUTPUT
Relay
solid-state relay and logic output
analogue output
type of controller output 2 for
self-optimisation
Deadband
➔
DEADBAND
0.
0
—999digit
serves to minimise the output
movement within the dead band;
e. g. with noisy signals.
The dead band is only effective
with controller structures with
I component.
Fuzzy control 1
➔
FC1
0.
0
—100
0 = fuzzy control off
Intensity of the fuzzy signal added
to the controller output to improve
the control quality.
Fuzzy control 2
➔
FC2
30.
0—
30
—100
Influences the controller parameters
during activated fuzzy module to
improve the control quality.
CONFIG 1
➔
CONTRL.
Parameter
Value/selection Description
Factory settings are shown
bold
.
A
The setpoint limits are
ineffective with setpoint input
via the interface.
For external setpoint with cor-
rection, the correction value is
limited.