5 Address tables
22
Bit 4
R/O
Output 5 (K9)
Bit 5
R/O
Output 6 (K10)
Bit 6
R/O
Output 7 (K11)
Bit 7
R/O
Output 8 (K12)
Bit 8 —15
R/O
not used
0x100E
INT
R/O
Logic inputs 1 — 8
(switching states 0 = open / 1 = closed)
Bit 0
R/O
Logic input 1
…
…
…
Bit 7
R/O
Logic input 8
Bit 8 —15
R/O
not used
0x100F
INT
R/O
reserved
0x1010
INT
R/O
reserved
0x1011
INT
R/O
reserved
0x1012
INT
R/O
reserved
0x1013
INT
R/O
reserved
0x1014
INT
R/O
reserved
0x1015
INT
R/O
reserved
0x1016
INT
R/O
Limit comparator (switching states 0 = off / 1 = on)
Bit 0
R/O
Limit comparator 1
…
…
…
Bit 7
R/O
Limit comparator 8
Bit 8 —15
R/O
not used
0x1017
INT
R/O
Logic module
Bit 0
R/O
Logic 1
Bit 1
R/O
Logic 2
Bit 2 —15
R/O
not used
0x1018
FLOAT
R/O
Analogue input 1
0x101A
FLOAT
R/O
Analogue input 2
0x101C
FLOAT
R/O
Analogue input 3
0x101E
FLOAT
R/O
Analogue input 4
0x1020
FLOAT
R/O
Mathematics 1
0x1022
FLOAT
R/O
Mathematics 2
0x1024
FLOAT
R/O
Ramp value (W)
0x1026
FLOAT
R/O
Process value filtered
0x1028
FLOAT
R/O
Process value unfiltered
0x102A
FLOAT
Setpoint
0x102C
FLOAT
R/O
Output -100 to 100% (display value)
0x102E
FLOAT
R/O
Output heating 0 to +100%
0x1030
FLOAT
R/O
Output cooling -100 to 0%
0x1032
FLOAT
R/O
Control difference
0x1034
FLOAT
R/O
Control deviation
0x1036
INT
R/O
Switch position heating (1 = contact closed/ ON)
0x1037
INT
R/O
Switch position cooling (1 = contact closed/ ON)
0x1038
INT
R/O
Parameter set number (1 — 2)
Address
Data type/
bit number
Access
Signal designation