4 The GSDML file
16
Configurable modules
The configurable modules are intended exclusively for transferring cyclical IO data. The assignment of
the modules can be compiled and printed via the JUMO PC setup program of the AQUIS touch P. The
printed list will help you maintain an overview of the configured modules of the JUMO IO device during
the project planning and programming of the IO controller (PLC, host PC or similar).
chapter 4.2.2 "Modules", page 11
The JUMO AQUIS touch P supports up to 10 slots in total (9 configurable slots + DeviceStatusBlock) in
the device and 10 slots in the IO controller project. The possible types of configurable modules are listed
in the table below.
DeviceStatusBlock start-up parameter
Parameter
Type
Values
Explanation
Byte sequence for cycli-
cal data
Bit
0 (Big Endian)
1 (Little Endian)
Selection of byte sequence for transferred cyclical
data
The byte sequence to be set is specified by the IO
controller.
Byte sequence for non-
cyclical data
Bit
0 (Big Endian)
1 (Little Endian)
Selection of byte sequence for transferred noncycli-
cal data
The byte sequence to be set is specified by the IO
controller.
IOPS handling
Bit
0 (OFF)
1 (ON)
Handling of the IOPS status via the IO device
0 (OFF):
The IOPS status of the respective IO device
slot communicates to the controller the validity status
of the input values following successful system boot.
If the IOPS status is valid, all values of the slot are
valid. If at least 1 invalid input value occurs in the slot
concerned, the IOPS status is likewise set to invalid.
1 (ON):
The IOPS status of the relevant IO device
slot is valid following successful system boot and no
longer depends on the validity of the input data. The
validity check of the input values must be implement-
ed in the IO controller if necessary.
In case of invalid float values (REAL type), JUMO
field devices map an error code in the transferred in-
put values, i.e. the error number rather than the input
value is contained.
chapter 7.1 "Error messages for invalid values",
page 47
Module types
IO items
Data type
Data direction
IO controller
Analog input values
Analog values 1 to 16,
Real
read
Digital input values
Digital values 1 to 32
Bool
read
Analog output values
Analog values 1 to 8
Real
write
Digital output values
Digital values 1 to 3
Bool
write
Содержание AQUIS touch P
Страница 2: ......
Страница 4: ...Contents...
Страница 6: ...1 Safety information 6...
Страница 8: ...2 Compatibility and system requirements 8...
Страница 10: ...3 Electrical connection 10...
Страница 46: ...6 Project planning 46...
Страница 48: ...7 Error messages 48...
Страница 49: ...49 8 Annex 8 Annex 8 1 PROFINET certificate...
Страница 50: ...8 Annex 50...
Страница 51: ......