3 Functions
18
3.2 Write one word
For the “write word” function, the data blocks for instruction and
response are identical.
Instruction
Response
Example
Write minimum ON time “t.on” = 25 = 0x0019
Modbus address = 0x009D = 157
Instruction:
Response (as instruction):
Slave
address
Function
0x06
Word
address
Word
value
Checksum
CRC16
1 byte
1 byte
2 bytes
2 bytes
2 bytes
Slave
address
Function
0x06
Word
address
Word
value
Checksum
CRC16
1 byte
1 byte
2 bytes
2 bytes
2 bytes
01
06
00
9D
00 19 D9EE
01
06
00
9D
00
19
D9EE