background image

21

7 Electrical connection

7.2

Connecting the device

1. Insert the connecting cable into 

the M12 plug connection.

2. Manually screw the union nut of 

the connecting cable onto the 
M12 plug connection on the de-
vice.
If you are using the connecting 
cable provided by the manufac-
turer, tighten the union nut using 
an open-end wrench AF 13. 
Maximum tightening torque: 
0.4 Nm.

3. Connect the connecting cable to the device that is processing the signals and to the voltage supply. 

Route the cable so that it is protected against mechanical strain.

The device is ready for use. The device status LED indicates the current status of the device 

"Display 

and control elements", Page 22.

Содержание 406050

Страница 1: ...40605000T90Z001K000 V1 00 EN 00729317 2022 01 17 JUMO flowTRANS US W01 Ultrasonic flowmeter for liquids Operating Manual...

Страница 2: ...Further information and downloads qr 406050 en jumo info...

Страница 3: ...ut 10 4 1 1 Measuring range and accuracy 10 4 1 2 Reference conditions 10 4 2 Output 11 4 2 1 Analog output 11 4 2 2 Digital output 11 4 3 Electrical data 12 4 4 Mechanical features 12 4 4 1 Materials...

Страница 4: ...Connecting the device 21 8 Operation 22 8 1 Display and control elements 22 8 2 Troubleshooting 22 9 Maintenance and cleaning 23 9 1 Cleaning device housing 23 9 2 Cleaning parts that come into conta...

Страница 5: ...rget group This documentation is intended to be used by trained electrical mechanical and plant engineering per sonnel across all phases of the product lifecycle 1 3 Definition of terms 1 4 Symbols Us...

Страница 6: ...The vol ume flows can be output in analogue as a current signal 4 to 20 mA and digitally as a pulse signal 0 to 10 kHz During operation the admissible data and operating conditions specified in the le...

Страница 7: ...ing into consideration the safety data sheet for the hazardous substances concerned for mounting operation maintenance cleaning and disposal Comparison and systematic checking of the durability of the...

Страница 8: ...and provide interfaces for dis playing measured values Function principle Front view Rear view 1 Meter run 4 Device status LED 2 Transducer ultrasonic converter 5 O ring seal for the process connecti...

Страница 9: ...de 12 EU conformity label 6 Nominal width 13 UK conformity label 7 Nominal pressure level 14 Observe device documentation 8 Medium temperature 36039 Fulda Germany 2 3 6 7 12 13 8 4 5 11 10 1 9 14 READ...

Страница 10: ...easured value Measuring deviationa Pulse output 2 0 of measured value 0 1 of flowmax Current output Like pulse output additionally 0 1 of 20 mA Voltage output Like pulse output additionally 0 1 of 10...

Страница 11: ...f the current flow rate output of a signal for error messages display via device status LED Signal range DC 0 to 10 V Signal limits DC 0 to 10 3 V Error message DC 0 or 11 V default settings 0 V Tempe...

Страница 12: ...tage Electrical safety The device must be equipped with an electrical circuit that meets the require ments of DIN EN 61010 1 with regard to Limited energy circuits Housing PA66 GF25 Components in cont...

Страница 13: ...class 3K6 Temperature range 20 to 55 C Relative humidity 100 Condensation on device outer shell Protection type DIN EN 60529 EN 50102 IP65 IP67 Electromagnetic compatibility EMC DIN EN 61326 1 DIN EN...

Страница 14: ...e in a dry and dust free environment Observe the device storage temperature range 5 4 Packaging and transport If the device is not protected properly against external influences it may become damaged...

Страница 15: ...outlet sections Installation position To calm the flow in the pipeline the specified inlet and outlet sec tions are required at the very least For increased accuracy the inlet and outlet sections can...

Страница 16: ...nd two union nuts 2 Select the correct set for the nominal width and pipe material in question For the table of dimensions for the mounting sets please see Data sheet Nominal width Insertion length L...

Страница 17: ...nnections 2 Install the device between the two union ends of the mounting set Ensure that the O rings 2 be tween the process connections 1 and union ends 3 are cor rectly positioned 3 Manually screw u...

Страница 18: ...a cable that has a temperature resistance suitable for the process Do not lay the cable near high voltage or high frequency cables if you cannot avoid doing so main tain a minimum gap of 30 cm 7 1 1 P...

Страница 19: ...1 3 Connection of digital output Requirements Connect an unused current output 2 to GND 3 Leave an unused optional voltage output 2 open Pulse output push pull example 1 Device Connecting cable Devic...

Страница 20: ...push pull example 2 Pulse output NPN optionally Pulse output PNP optionally Device Connecting cable Device Connecting cable Device Connecting cable 24 V GND 200 mA 10 kHz 1 2 4 3 24 V GND 200 mA 10 kH...

Страница 21: ...connecting cable provided by the manufac turer tighten the union nut using an open end wrench AF 13 Maximum tightening torque 0 4 Nm 3 Connect the connecting cable to the device that is processing th...

Страница 22: ...nc tion Possible cause Troubleshooting 0 All No errors 2 Input for vol ume flow Volume flow MRE Reduce the plant s volumetric flow Use larger device nominal width Partial filling empty conduit Fill pi...

Страница 23: ...all the device Installing the device Page 17 9 3 Decontaminating the device Requirements Uninstall the device Uninstalling the device Page 24 Wear suitable protective equipment Have a suitable cleanin...

Страница 24: ...age 23 Clean the parts that come into contact with the medium Cleaning parts that come into contact with the medium and replacing O rings Page 23 Decontaminate the device Decontaminating the device Pa...

Страница 25: ...926 Mounting set PP butt welding DN 15 00750878 Mounting set PP butt welding DN 20 00750881 Mounting set PP butt welding DN 25 00750884 Mounting set PP butt welding DN 32 00750887 Mounting set stainle...

Страница 26: ...SJ T 11364 GB T 26572 Indicate the hazardous substances in all homogeneous materials for the part are below the limit of the GB T 26572 GB T 26572 Indicate the hazardous substances in at least one ho...

Страница 27: ......

Страница 28: ...ers Road East Syracuse NY 13057 USA Delivery address Mackenrodtstra e 14 36039 Fulda Germany Phone Fax Email Internet 44 1279 63 55 33 44 1279 62 50 29 sales jumo co uk www jumo co uk Phone Fax Email...

Отзывы: