JUDO MAFI

9

Installation

4.4

Mounting the built-in rotary
flange

Install using the supplied built-in rotary
flange. The built-in rotary flange is used as a
connecting element with the heating circuit.

It is suitable for both horizontal and vertical
pipes.

The built-in rotary flange must be in-
stalled in the direction of flow. This is
marked by a cast in arrow (see fig. 3).

Failure to comply with this means that the
magnetite filter cannot work.

ATTENTION

(see chapter “Safety information and
dangers due to non-compliance”)

The flange surface of the built-in rotary
flange must be in a vertical position! The
built-in rotary flange must be fitted so that
mechanical stresses cannot occur! Other-
wise mechanical damage can result, the
pipe may burst or the built-in rotary flange
can break. This can result in major water
damage.

In this case, people close to the magnetite
filter are exposed to a health risk due to the
large quantities of water.

Therefore, during installation, ensure that no
large forces act on the pipe, built-in rotary
flange and magnetite filter.

4.5

Mounting the magnetite filter

The built-in rotary flange for the magnetite
filter is supplied with bayonet drill holes. The
necessary seals and screws for this magnet-
ite filter have already been mounted.

Do not unscrew the screws!

Insert the four flange screws in the bay-
onet drill holes on the built-in rotary
flange (see fig. 4 I).

Turn the magnetite filter in a clockwise
direction as far as it will go (see fig. 4 II).

Tighten the four flange screws.

The section of the profiled flange gasket
must point towards the built-in rotary flange
(see fig. 3). Failure to observe this can lead
to leaks and water escaping. This can in turn
cause water damage to the house and its in-
stallations.

Fig. 3:

Built-in rotary flange

Profiled flange gasket

Fig. 4:

Built-in rotary flange

 with bayonet fixture

Select the torque (approx. 4 Nm) so
that the gasket closes and the 

mag-

netite filter

 is not damaged or

strained!

I

II

Содержание JMFI 1

Страница 1: ...tting the unit into service These instructions must always be issued to the owner user Installation and operating instructions JUDO MAFI Magnetite filter Heating loop filtration with magnetic and cent...

Страница 2: ...purchasing this unit With this magnetite filter you have purchased a state of the art unit This multi functional unit is designed for use in heating loop systems and features a centrifugal particle r...

Страница 3: ...ly available at the place in which the magnetite filter is used This instruction manual is intended to make it easier to familiarize yourself with the mag netite filter and its possible intended uses...

Страница 4: ...erve the general dan ger symbols can result for example in the following risks Failure of important functions of the magnetite filter Danger to persons due to electrical and mechanical effects Danger...

Страница 5: ...s given in the in struction manual The magnetite filter is only to be used in a technically perfect condition for its intended use safely and aware of the dangers and with full observance of the instr...

Страница 6: ...hapter Rinsing 4 1 1 Requirements for the place of installation The room where the unit is installed must be dry and frost free Unauthorised per sons must not have access to the mag netite filter ATTE...

Страница 7: ...Heating resupply station with integrated pipe disconnector type BA order no 8060080 2 JUDO MAFI Magnetite filter 1 1 1 order no 8060083 8060084 8060085 8060086 3 JUDO QUICK AN Adaptor for dosing with...

Страница 8: ...or JUDO HEIFI SOFT filling block 12000 Fill water softening unit order no 8068012 6 JUDO PURE 7500 Full demineralisation cartridge order no 8068019 or alternatively the floor standing version JUDO PUR...

Страница 9: ...osed to a health risk due to the large quantities of water Therefore during installation ensure that no large forces act on the pipe built in rotary flange and magnetite filter 4 5 Mounting the magnet...

Страница 10: ...gers during rinsing ATTENTION see chapter Safety information and dangers due to non compliance During the rinsing operation hot water comes out of the outlet nozzle Carry out with care danger of scald...

Страница 11: ...d with the cover cap 1 on the aeration unit 2 being open one turn to ensure air can be evac uated freely see fig 5 The magnetite filter is ready for opera tion once the rinsing and aeration cycle has...

Страница 12: ...pressure loss High levels of oxygen concentration can al so be found in closed loop systems Weak points within the system e g non diffusion resistant plastic pipes or membranes mean that O2 can enter...

Страница 13: ...e filter must be closed before rinsing The black magnet holder in the front of the unit is then pulled fully open to allow the sludge retained to drop tot he unit floor see fig 7 The draw may be close...

Страница 14: ...open the shut off valve downstream of the unit once rinsing is complete Check the systems pressure after rinsing as a top up may be required A top up will then bring the unit back to the correct oper...

Страница 15: ...gnetite filter has to be removed from the flange or unscrewed the chapter In tended use must always be observed Protect the flange surfaces from dam age Damaged flange surfaces cannot close tight any...

Страница 16: ...expansion vessel is pressureless Top up required heating water Check expansion vessel A backflow preventor gravity brake or automatic shut off unit are in stalled between the magnetite filter and the...

Страница 17: ...ain up to 25 solvents or alcohol spirits These substances can chemically attack the plastic parts which can lead to brittleness or even fractures These kinds of cleaners must therefore not be used 8 W...

Страница 18: ...r a completely opened ball valve Model Order no JMFI 8060083 JMFI 1 8060084 JMFI 1 8060085 JMFI 1 8060086 Nominal pressure Model Operating pressure Nominal pressure JMFI 1 6 bar PN 6 Weight Model Weig...

Страница 19: ...0080 The JUDO HEIFI F L PLUS heating resup ply station consists of two integrated shut off valves pressure regulator manometer and pipe disconnector type BA The integrated pressure regulator ensures t...

Страница 20: ...20 JUDO MAFI Spare parts 10 Spare parts 1 3 4 5 2 6 7 8 8 8 9 10 11 11 12 13 15 16 17 18 14...

Страница 21: ...n unit 1 2 Cylinder screw M6x130 set of 4 pcs 1 2060462 6 3 Upper cover 1 2060452 VE2 4 O ring 52x3 5 1 5 Base unit 1 2060458 VE2 6 Seal 1 7 Stopper 1 2060450 6 8 Set of insulating shells 1 9 Round ma...

Страница 22: ...22 JUDO MAFI Notes...

Страница 23: ...JUDO MAFI 23 Notes...

Страница 24: ...v du Laerbeek 72 A1 B 1090 Brussel Bruxelles Tel T l 32 0 24 60 12 88 Fax 32 0 24 61 18 85 e mail info benelux judo eu judo eu JUDO France S r L 76 Rue de la Plaine des Bouchers Technosud F 67100 Stra...

Отзывы: