Version P531x L1x

4.2 Description of setting and configuration 
using the communicator LHPWinCom

The  communicator  LHPWinCom  consists  of  program 
LHPWinConf,  modem  HARTMod  (MH-02)  and  connection 
cables.  Before  use  is  necessary  to  connect  the  modem  to 
a PC using the connection cable, install and run the program 
LHPWinConf.  Program  finds  the  modem  on  the  respective 
communication port by itself. In case, that the program issues a 
message that the modem is not connected, enter the respective 
port on the HART driver panel.
The  program  includes  two  main  configuration  panels.  The 
panel ”Calibrator Configuration“ is used for fast setting of the 
range using a sensor simulator or using a calibrator. The panel 
“Keyboard  Configuration”  allows  setting  of  all  the  available 
transmitter  parameters  directly  on  the  keyboard  without  any 
necessity  to  use  a  calibrator.  Individual  steps  of  the  optimal 
user  procedure  are  given  on  both  panels  that  should  be 
followed. Configuration can be saved as a file or print it as a 
“Transmitter Configuration Protocol“.
On the panel “Options” you can change the program language 
and  run  the  fixed  output  mode.  This  mode  changes  the 
transmitter  into  a  simulator  of  output  current  with  the  range 
3.5 to 22 mA. In this mode the output current is determined by 
the entered value only and is not influenced by changes of the 
input  quantity.  The  fixed  output  mode  can  be  closed  by  the 
program  button  or  by  disconnecting  of  the  transmitter  power 
supply. 

Transmitters in version EI1 or EN2 (Ex version) can be 
set up using the communicator LHPWinCom only if the 

transmitter,  communicator  and  connected  wires  are  installed 
out of explosion hazard environment!

4.3 Description of setting and configuration 
using a handheld configurator LHPConf or 
HARTConf

LHPConf and HARTConf are a field handheld configurators for 
setting  of  all  parameters  of  transmitters  with  LHP 
communication. A detailed description of setting and control is 
given in the configurators instruction manual.

Transmitters in version EI1 or EN2 (Ex version) can be 
set  up  using  the  configurator  LHPConf  or  HARTConf 

only  if  the  transmitter,  configurator  and  connected  wires  are 
installed out of explosion hazard environment!

4.4 Operation and maintenance

Provided that the instrument is installed correctly, the operator
can read setting and measured values using a configurator.
Setting of the instrument may be changed only if a sudden
change of the output current cannot cause any failure of the
technological equipment or regulation (switch over the possible
regulator to manual control)! 
The instrument does not need any maintenance.

1 2

3 4

4w

3w

4w

4 wire

RTD

TC

PO T

TC

RTD

5 6

7 8

NAPÁJECÍ

ZDRO J

LHP komunikátor

mA

TEST

R

i

 

1 2

3 4

1 2

3 4

1 2

3 4

mA

R

L

250 Ohm

(pro komunikaci)

VÝSTUP

15 Ohm

~

POWER 

SUPPLY

LHP 

Communicator

(for communication)

OUTPUT

Numerals or letters may mark the terminals of the version P531x L1x:

Numerals

1

2

3

4

5

6

7

8

Letters

C

D

A

B

H

G

F

E

Содержание P5310

Страница 1: ...www jsp sk This document applies to serial numbers 10090000 and higher One type of transmitter for all common resistance and thermocouple sensors Linearized output signal 4 to 20 mA Accuracy from 0 1...

Страница 2: ...4 Installation operation and maintenance 4 1 Installation and commissioning 6 4 2 Description of setting and configuration using the communicator LHPWinCom 7 4 3 Description of setting and configurati...

Страница 3: ...e cover and provided with an identification label with a mark of the output control The product must not be exposed to direct rain vibrations and shocks during transport 1 5 Storage The products shall...

Страница 4: ...minal block temperature or by the entered constant temperature The inner sensor guarantees maximum accuracy and stability of cold junction temperature measurement If required compensation using an ext...

Страница 5: ...5 Low Cost Programmable Transmitters P5310 P5311 with LHP Communication 3 3 Dimensional drawings Version P531x H1x Version P531x L1x 3 4 Block diagram...

Страница 6: ...ctrostatic charging Such case may be a metal temperature sensor head or a suitable metal installation box if it does not contain magnesium nor titanium During installation it is also necessary to resp...

Страница 7: ...the input quantity The fixed output mode can be closed by the program button or by disconnecting of the transmitter power supply Transmitters in version EI1 or EN2 Ex version can be set up using the c...

Страница 8: ...0 to 400 C IEC 584 1 thermocouple B 100 to 1800 C IEC 584 1 thermocouple E 200 to 950 C IEC 584 1 thermocouple L 200 to 900 C DIN 43710 thermocouple C 0 to 2300 C N I S T Monograph 175 range can be se...

Страница 9: ...esponding temperature 10 C Range 0 to 4000 Ohm 0 1 SR or 0 8 Ohm or corresponding temperature 10 C Range 15 to 70 mV 0 1 SR or 0 02 mV or corresponding temperature 10 C the greatest value is valid Lon...

Страница 10: ...RTMod Miniature HART modem with galvanic isolation USB RS232C Communication interface for to USB port of the PC PT1000A Compensation resistor Pt1000 30 to 150 C for external compensation of thermocoup...

Страница 11: ...JSP Industrial Controls JSP s r o Raisova 547 506 01 Ji n Czech Republic 420 493 760 811 export jsp cz www jsp cz Your Supplier...

Отзывы: