1 Description of PDAN/PDA/PDH/PDE Series inverter 

1.1 General description and Design philosophy 

The

 PDAN

 Series inverter is a POWER CONVERTER for variable-speed AC drives. It applies the Sensor-less Vector 

concept to control the output voltage and frequency to the motor. Use current sensor detects three phase AC current 
signals and phase angle, and using the Sensor less Vector algorithm to compensate motor speed variation. The PDAN 
series will provide more torque at low speed and automatic compensate the motor slip when under heavy loading. 
The

 PDA

 Series inverter is a POWER CONVERTER for variable-speed AC drives. It applies the Sensor-less Vector 

concept to control the output voltage and frequency to the motor. Use only one current sensor at DC bus, the advanced 
microprocessor detects the DC current and recovers the signal into three phase AC current signals.    Phase angle of the 
output current is measured in order to compensate motor speed variation using the Sensor less Vector algorithm. 
Superior than traditional V/F inverter, the PDA series will provide more torque at low speed and auto compensate the 
motor slip when under heavy loading. 

PDE 

series inverter is similar to PDA series. However, for economic reason, a simple shunt resistor replaces the Hall-

effect current sensor. Therefore, the PDE does not include all the functions involving current measurement and 
calculation.   
The 

PDAN

PDA

 and 

PDE

 inverters can generate output frequency up to 650Hz. 

PDH

 series inverter can generate output frequency up to 3,000Hz used for driving very high-speed motors. In order to 

decrease sub-harmonic when running the motor at high frequency, it employs Synchronous Symmetric Sine Pulse 
Width Modulation method for waveform generation.   

Built in standard 

UP/DOWN Counter

 Module, 

Timer/Counter

 Module and 

Flip/Flop

 Module that are 

very often used in actual application system. 

Six digital inputs

 and 

three digital outputs

 are all 

programmable to meet all kinds of applications.   

Three analog inputs

 

AI1, AI2 and AI3 

is provided for 

various control applications. Moreover, many combinations 
of these three AIx signals are provided; allow your system 
design flexible. 

Serial communication control 

software is embedded in 

the CPU; it can easily achieve computer direct control 
through RS485 serial port. It is very useful when inverter or 
many inverters would like to be dynamical controlled by 
master computer.    With repeater one serial port can 
address up to 99 inverters. (Standard RS485 driver can 
drive up to 31 inverters only.)   
*    The PDAN series inverter has built-in RS-485 interface; 
the RS-485/RS-232 option card is available for PDA/PDE 
/PDH series inverter. 
 

1.2 Control input & output configuration   

The control terminal on the CPU board can be separate into three groups. 

Terminal for Analog signals: 

 

AM  AI1

 

5V

 

AI2

 

AI3

 

ACOM 

 

*AI3 does not exist in PDA/H-4015, PDE-2007/2015. 

Terminal for Digital signals: 

 

DI1

 

DI2

 

REV

 

24V

 

DO1

 

DO2

 

DI3

 

DI4

 

RST

 

RUN

 

DCOM 

 

*RUN=DI5, REV=DI6 

Terminal for 1a contact Relay output: 

 

RY1

 

RY2

 

 

!

  CAUTION 

All the input/output control signal lines, or remote panel lines and communication lines must be laid separately from the 
high current power/motor/brake lines. 
They must not be fed through the same cable conduit/trucking. 

 

     
    0~650Hz 
  SensorLess 
      Vector 
      IGBT 
    Inverter 

PDAN/PDA/PDE/PDH Series 

Up/Down 
Counter 

TIMER 

Flip/Flop 

Auto-Run 

3 Analog 
Inputs 

* RS-232/485 

6 Digital   
Input 

3 Digital 
Output 

Содержание PDA Series

Страница 1: ...PDA N Series Sensor Less Vector PDH Series High Frequency PDE Serie Wide Application Inverter Instruction Manual Version 2 1...

Страница 2: ...l the warnings and operating procedures contained with this manual l Certain parameter settings may cause the inverter to start up automatically after power on or power recover DEFINITIONS Qualified P...

Страница 3: ...14 5 1 Parameter List 14 5 2 Parameter Protection 16 5 3 Parameter Initialization 16 5 4 Description of All Parameters 17 6 Selection of RUN STOP FWD REV control command 23 7 Selection of Set Frequenc...

Страница 4: ...harmonic when running the motor at high frequency it employs Synchronous Symmetric Sine Pulse Width Modulation method for waveform generation Built in standard UP DOWN Counter Module Timer Counter Mo...

Страница 5: ...to define the characteristic of the input terminal AI2 l If you are using 0 5V input external or internal voltage reference to AI2 select JP2 to 5V position l If you are using external 20mA current in...

Страница 6: ...elects Source PNP input l JP5 upper position selects Source PNP output l JP4 lower position selects Sink NPN input l JP5 lower position selects Sink NPN output Note The digital input terminals and dig...

Страница 7: ...e specified level when the inverter is installed in cubicle l Avoid excessive vibration and shaking of the equipment l Do not be obstruct the cooling fan that installed on the inverter it is used to b...

Страница 8: ...crews may be touched with the insulated screwdrivers when connecting the leads l Make sure to connect the power terminals tight and correctly l Make sure that the power source supplies the correct vol...

Страница 9: ...5 75 750 4110 50 1000 4150 40 1500 Discharge duty 10 Warning Never connect resistor to P N terminal If the terminals are P N must add external braking unit 2 7 A C L When power supply capacity is larg...

Страница 10: ...on and may monitor any two internal status easily Refer to Sec 13 If HZ Led is on it is under MON Mode and 7 segment shows the HZ data Or the desired parameter assigned by Pr 99 If I Led is on it is u...

Страница 11: ...n For PDA series only through Pr 67 selection the inverter can operate under the following 5 different modes Operation Mode Description Series Model 0 Standard V F I PDA PDE PDH Model 1 Standard V F I...

Страница 12: ...detail explanation of Pr 54 for monitoring the output current or power 4 4 Auto Tuning 4 4 1 Auto Tuning for PDA series For PDA series the embedded Auto Tuning program can search the internal characte...

Страница 13: ...tart auto tuning process these parameters should be assigned first Pr 01 Main Acceleration rate Pr 02 Main Deceleration rate Pr 10 Base frequency Hz of the motor Pr 11 Voltage when the inverter output...

Страница 14: ...tion example DI1 TMIC DO1 TMOC DI6 REV DCOM Start Fwd Rev AI3 DI5 RUN DI2 88 Pr 00 AI3 0V Pr 71 20Sec SW1 Panel VR Rev Set up procedure for above application l Pr 39 1 1 Determines the control command...

Страница 15: ...0 FR W PDH THERMISTOR TYPE 440 8 0 0 999 9 FR W PDAN 30 00 Hz 0 00 650 00 FR W PDA PDE Pr 14 CARRIER_TRANSFER_POINT 300 0 Hz 0 0 3000 0 FR W PDH 60 00 Hz 0 50 650 00 FR W PDAN PDA PDE Pr 15 UPPER FRE...

Страница 16: ...NCE 50 Hz 0 250 R W PDH THERMAL TRIP TIME 60 Sec 0 120 R W PDAN PDA PDH Pr 51 Reserve PDE 4 2 12 FR W PDAN Pr 52 POLE 4 2 12 R W PDA PDE PDH Pr 53 GEAR RATIO 100 0 100 R W 0 0 250 R W PDAN MONITOR SEL...

Страница 17: ...1 R W Pr 97 VERSION R Pr 98 MONITOR I 61 0 99 R W Pr 99 MONITOR HZ 57 0 99 R W Note 1 Type R W parameters are stored in EAROM memory They can be read write and store in the memory permanently Type FR...

Страница 18: ...Refer to Section 8 Defines the function for input terminal DI6 or the terminal marked with REV Pr 05 BRAKE FREQUENCY While deceleration to stop if the output frequency is lower than this parameter the...

Страница 19: ...PWM Carrier otherwise it is 2KHz Minimum Carrier y 2KHz xx Carrier Frequency KHz Pr 12 xx y Output Frequency Hz Pr 13 PDA PDE PDH series MINIMUM_CARRIER Defines the minimum carrier frequency PDAN ser...

Страница 20: ...8 83 12 This parameter determines the running frequency when SPD3 speed is required PDAN series Refer to Appendix A for PID function Pr 28 SPD3 ACC TIME Refer to 8 2 8 5 8 87 Defines the acceleration...

Страница 21: ...the function for output RELAY terminal RY1 RY2 Pr 48 Irms Idc DETECTOR THRESHOLD LEVEL Refer to Section 9 13 This parameter is used to define the threshold level for Current Over Detector module Pr 49...

Страница 22: ...al Output Terminal status Refer to Section 13 2 Monitors the DO1 DO2 RY 1 2 output terminal status Digit 2 DO1 Output Terminal Status Digit 1 DO2 Output Terminal Status Digit 0 RELAY Output Status Pr...

Страница 23: ...ameter is used to record the A D converter data when AI1 input terminal is connected to ACOM terminal JP1 select 5V Pr 90 AI1_HIGH This parameter is used to record the A D converter data when AI1 inpu...

Страница 24: ...rols the running direction If CMD_SELECT 2 The RUN terminal is equivalent to FORWARD RUN The REV terminal is equivalent to REVERSE RUN If CMD_SELECT 3 Similar to mode 1 but will check RUN terminal at...

Страница 25: ...requency 21 Frequency Set Panel Computer Set 100 Pr 70 AI2 22 Set Frequency Panel Computer Set Pr 15 Pr 70 AI1 With Minimum Pr 16 23 24 Reserve 25 AI3 used as frequency source similar to mode 2 26 AI3...

Страница 26: ...quence must be determined by control command If the input signal reaches maximum level the set frequency is equal to Pr 15 UPPER LIMIT If the desired set frequency is lower than Pr 16 LOWER LIMIT the...

Страница 27: ...come from Internal Up Down Counter with Preload from Pr 00 Note When start running the minimum running frequency shall be Pr 16 Internal U p D ow n C ounter Preload Pr 00 C ounter output 2 3 1 1 If P...

Страница 28: ...2 terminal will be used to determine the output frequency and direction of the inverter The input signal level determines the direction of the output phase sequence If the input signal is positive max...

Страница 29: ...odification quantity is Pr 15 Pr 70 and if AI1 is minimum the modification quantity is Pr 15 Pr 70 Note Minimum running frequency is Pr 16 Typical application is as follows Position Detector AI2 INV1...

Страница 30: ...6 LOWER LIMIT On the contrary if the input signal is zero the set frequency is equal to Pr 15 UPPER LIMIT Note Set jumper JP2 to match with the input signal type and range If necessary use Pr 91 and P...

Страница 31: ...91 and Pr 92 are used to define the high and low limit of AI3 Input range is 0 5V 7 2 28 Pr 40 28 Speed input is the combination of AI1 100 Pr 70 AI3 This mode is similar to mode12 but AI3 is used ins...

Страница 32: ...ction it is same as mode 18 use AI2 as input source If the motor run in REVERSE direction it is same as mode 17 use AI1 as input source 7 2 39 Pr 40 39 When start running the output frequency is deter...

Страница 33: ...OLD Output HZ to UP DOWN COUNTER 18 OFF_BB BASE BLOCK if DIx is OFF 19 U D COUNTER UP INCREASE UP DOWN COUNTER 20 U D COUNTER DOWN DECREASE UP DOWN COUNTER 21 ALARM CLEAR CLEAR ALARM WHEN ALARM OCCUR...

Страница 34: ...re other four pre settable speeds JOG Speed SPD1 SPD2 and SPD3 The following table lists the corresponding parameters PARAMETER FUNCTION COMMENT Pr 00 MAIN SPD SET Main preset speed Pr 01 MAIN ACC TIM...

Страница 35: ...function it serves as Input of the OFF DELAY timer User must assign a digital output DOx which select TMOA function to serve as the output of this timer And the timer time will be defined in Pr 71 Re...

Страница 36: ...execute Speed Search process Refer to Sec 11 the special function for Speed Search process Also Refer to Sec 8 8 for complement function 8 19 DIx_Select 19 UP If DIx 19 is ON the UP COUNTER will incr...

Страница 37: ...is used the Counter Module will advance one count when the input status of DIx changes from OFF to ON The maximum input clock rate is limited to 1 000 Transitions Second 8 29 DIx_Select 29 reserve 8...

Страница 38: ...SENSOR LESS externally If Pr 67 1 and DIx 72 ON mode will change from Non Sensor Less to Sensor Less If Pr 67 3 and DIx 72 ON mode will change from Sensor Less to Non Sensor Less 8 73 RUN function 8...

Страница 39: ...and source cc DIx 89 ON Control Command source b DIx 89 OFF Control Command source a DIx 90 ON Speed Command source dd and Control Command source b DIx 90 OFF Speed Command source cc and Control Comma...

Страница 40: ...6 SPNZ NOT ZERO SPEED 17 STALLING OUTPUT WHILE STALLING 18 19 Reserve 20 TMOB TIMER OUTPUT TYPE B 21 STEP1 AUTO RUNNING AT STEP 1 22 STEP2 AUTO RUNNING AT STEP 2 23 STEP3 AUTO RUNNING AT STEP 3 24 STE...

Страница 41: ...ATING Under Deceleration status 88 DISCHARGING Under Discharging status 89 Reserve 90 FWD FORWARD RUNNING 91 REV REVERSE RUNNING 92 TMOC TMOC ENABLE AFTER TMIC ON 93 TMOC Same as DOx 43 Note When powe...

Страница 42: ...mplement of Sec 9 8 DOx 9 DOx 8 9 10 SPA Speed Arrive function Refer to Section 9 2 The output status of DOx will ON if the output frequency is EQUAL to the Set frequency Definition of EQUAL means Dif...

Страница 43: ...seful when the inverter is controlled by a master computer or under TEST mode The master computer can control these digital outputs for other peripheral independent to the inverter operation 9 39 rese...

Страница 44: ...WARNING 9 79 OL WARNING The OL level can be monitored at Pr 61 when Pr 54 11 DOx 78 will ON if OL level 50 DOx 79 is complement function of DOx 78 Refer to Pr 54 for monitoring the OL accumulation lev...

Страница 45: ...Input from AI1 If DIx 54 ON 5V PID Boost PID Output Bias Input from AI1 If DIx 54 OFF 5V PID Boost PID Output 9 PID Output Bias Input from AI2 If DIx 54 ON 5V PID Boost PID Output Bias Input from AI2...

Страница 46: ...en the restart process begins PARAMETER FUNCTION DESCRIPTION Pr 79 RESTART TYPE SELECT RESTART TYPE Pr 80 RESTART STALL LEVEL STALL LEVEL WHILE RESTARTING Pr 81 RESTART DEC TIME DEC TIME WHILE SPEED S...

Страница 47: ...ERIOD determines time STEP3 inverter running as if SPD2 command is applied Pr 75 SPD2_PERIOD determines time STEP4 inverter running as if SPD3 command is applied Pr 76 SPD3_PERIOD determines time STEP...

Страница 48: ...D determines time STEP9 inverter running as if SPD3 command is applied Pr 76 SPD3_PERIOD determines time STEP10 inverter running as if STOP command is applied Pr 77 HALT_PERIOD determines time AFTER S...

Страница 49: ...d for AUTO STEP EQUAL application Refer to Section 9 21 9 30 EXAMPLE If user wishes to activate the DOx outputs when inverter is auto running if LET DO1 22 select STEP2 DO2 23 select STEP3 DO3 24 sele...

Страница 50: ...verter output voltage Pr 61 IRMS or other status Through Pr 54 other status can be selected for display Pr 54 0 Irms ampere Pr 54 1 Irms of inverter rating Pr 54 2 Irms of motor rating Pr 54 3 Power A...

Страница 51: ...f CPU will execute Analog to Digital conversion and put the conversion result in Pr 56 The range of the converted data is from 0 to 1023 corresponding to full range input Pr 55 Pr 56 A D DATA 0 VDC ch...

Страница 52: ...n UP UNDER VOLTAGE Note n 0 present alarm type n OL OVER LOAD n 1 alarm type before n OH OVER HEAT n 2 alarm type twice before n OC OVER CURRENT when normal run n 3 alarm type three times before n CA...

Страница 53: ...9600bps 1stopbits B 6 19200bps 1stopbits B 7 Reserve 15 1 2 PDA PDE PDH series Communication Parameter Pr 93 B ID B Baud Rate ID Unit Number 1 ID is used to assign the communication address while this...

Страница 54: ...8 Bit 3 JOG 4 Bit 2 Reverse 2 Bit 1 RUN Bit 0 Reset Control Code Function cc 00 Stop cc 01 Reset cc 02 Forward Run cc 06 Reverse Run cc 10 Forward JOG Run cc 14 Reverse JOG Run fffff Set Frequency PDA...

Страница 55: ...ch is 65536 ddddd 9 Read only store in RAM 00000 65535 999 99 10 Read only store in RAM 00000 65535 9999 9 11 Read only store in RAM 00000 65535 99999 12 Read only store in RAM 00000 00255 999 99 13 R...

Страница 56: ...B or N 3 4 4 24V 24V or DCOM 6 24V or DCOM 7 5 5 Note 1 Apply NFB before power line input to inverter 2 The analog signal wires should be shielded connected to the Earth 3 Refer to Sec 2 6 in order t...

Страница 57: ...52 PID Clear If DIx 52 ON PID Integrator Clear 53 PID Preset If DIx 53 ON PID Integrator preset to the value defined by Pr 74 54 PID Bias Enable If DIx 54 ON Bias Bias Input Enable If DIx 54 OFF Bias...

Страница 58: ...Pr 77 D Time 200ms ERROR PID Output Set Selection X Switch PID SET PID FB FB Selection Y PID Integrator Clear DIx 52 Pr 73 X Y AI 1 AI 2 AI 3 Pr 27 DI 2 Switch AI 1 AI 2 AI 3 Pr 27 DI 2 PID Preset DI...

Страница 59: ...JOINT PEER SYSTEC CORP 1R Q 6HF KRQJKH 6W QG IORRU LQVKH LVW 7DLFKXQJ LW 7DLZDQ TEL 886 2 6866 FAX 886 2 4889 http www jps com tw E mail MSV service jps com tw JPS...

Отзывы: