Jøtul GF 3 CF 2 Скачать руководство пользователя страница 7

7

Figure 7.  Clearance to a combustible shelf.

520 mm

Flue System Installation

Flue outlet (spigot) dimensions:
Internally = 128 mm
Externally = approx. 131 mm

When installing the vent, it is important to adhere to

national and local regulations that apply. Only one appli-
ance may be connected to the vent system.

The vent system must terminate above the roof.

The vent system and the flue pipe components must

be fastened to the stove with screws.

Minimum height of the chimney is approx. 2,15 m (7')

and maximum height should not be more than approx. 10,7
m (35'). (When installation is at or above a height of
approx. 610 m (2000'), the chimney’s height must be at
least approx. 3,7 m (12'.) measured from the flue outlet. If
the chimney has to move through a horizontal distance,
make sure to use 45º or 90 º bends.

Max. number of 45º bends = 4

Max. number of 90º bends = 3

It is permitted to move the chimney a total of approx.

1,2 m (4') horizontally.

An exhaust hood (terminal, cowl or rain cap) must be

mounted at the chimney’s termination point . After fitting
of the vent system and installation of the appliance, carry
out a smoke test on the flue as described in the relevant
section.  If the appliance shuts off in operation for no
apparent reason (especially during windy or stormy
conditions) and will not relight, it is possible that the flue
system safety switch has operated. Allow the appliance to
cool down and relight. Any obstruction to the flow of
exhaust gases up the flue can cause this switch to oper-
ate thereby making the situation safe. If the appliance
cuts out repeatedly, do not continue to use the appliance
and seek flue checking and service from qualified person-
nel before re-using the appliance.

Closure Plate Installation

It is permissible to install this appliance using a closure
plate installation similar to traditional outset gas fires.
See diagrams (1 E-F) on page 28. The British Standards
detailing this type of installation are BS5871 pt1 and
BS5440 pt 1. The appliance and flue must be sound and if
used with solid fuel or oil appliances it must be swept
prior to installation. There must be no other openings
other than the exit from the top of the flue and the
opening into which the appliance is being installed. All
cracks, holes, underfloor air vents etc must be removed
and sealed fully before installation continues. A propri-
etary metal flue box complying with BS715 is a suitable
appliance opening.

Figure 8.   Vent height requirements.

550 mm

(21 5/8”)

CL

635 mm

(25”)

 Draft Hood

Vent Height off

Draft Hood:

Min. 2.15 m (7’)

Max. 3.7 m (35’)

Figure 9.   Closure plate requirements.

Min.

50 mm

Min.

250 mm

Closure Plate

Содержание GF 3 CF 2

Страница 1: ...flammable vapors and liquids in the vicinity of this or any other appliance WHATTO DO IF YOU SMELL GAS Donottrytolightanyappliance Do not touch any electrical switch do not use any phone in your buil...

Страница 2: ...ompany Date Service details Annual service year 5 Sign Company Date Service details Annual service year 6 Sign Company Date Service details Annual service year 7 Sign Company Date Service details Annu...

Страница 3: ...Installer Information 6 5 User Information 12 6 Troubleshooting 14 THIS OWNER S MANUAL PROVIDES INFORMATIONTOENSURESAFEINSTALLATION AND EFFICIENT DEPENDABLE OPERATION OF YOUR STOVE PLEASE READTHESE IN...

Страница 4: ...Appliance Category II2H3P Gas Types NG LPG G20 1 G31 2 State of Adjustment I2H I3P Supply Pressure mbar 20 37 NominalHeatInput Nett kW 6 3 6 8 Maximum Gas Consumption at Full Rate m3 h at 15 C 1013 25...

Страница 5: ...intended for use on a gas installation with a governed gas supply SafetyPrecautions This appliance must be installed in accordance with the rules in force Consult instructions before installation and...

Страница 6: ...staller When the TTB is exchanged only original manufacturer s parts shall be used Installation Guide for Qualified Personnel Important The appliance is factory pre set for Natural Gas G20 If Propane...

Страница 7: ...arent reason especially during windy or stormy conditions and will not relight it is possible that the flue system safety switch has operated Allow the appliance to cool down and relight Any obstructi...

Страница 8: ...pliance will not work correctly and may cut out repeatedly if the sealing of the appliance and flue is not correct Remember if the closure plate extends beyond the sides or top of the stove a non comb...

Страница 9: ...tically simulate glowing coals when the burner is operating These should be spread evenly over the burner plate and around the logs 1 Engage the holes in the underside 0f the rear log with the two peg...

Страница 10: ...raught diverter hood on the rear of the appli ance accessible through a cutout in the rear heatshield The smoke should be drawn into the flue and no smoke should spill into the room If the smoke does...

Страница 11: ...call for service Annual Service Annual service of the appliance includes the following check points Lighting the pilot flame Cleaning the glass The gasket around the glass must be inspected annually...

Страница 12: ...778 to provide extra protection Operating Instructions Lighting Note Odors when using the stove When used for the first time the appliance may emit an irritating gas that may smell a little The gas is...

Страница 13: ...off of paint and lubrication used in the production process See section Odors when using the stove for the first time Adjusting the Heat Setting Heat and flame size can be adjusted by turning the reg...

Страница 14: ...when the valve is being replaced Troubleshooting When No Spark is Generated at the Pilot Head It is uncommon for the Piezo spark ignitor fig 23 A to fail unless it has mechanical damage If the spark...

Страница 15: ...valve even if the pressure is OK at outlet E You should therefore always check for leakage Thermocouple Fig 24 and Thermopile Fig 25 A thermocouple is in principle a thermal generator and consists of...

Страница 16: ...at the back of the appliance It should be set to the ON position 2 Make sure the wire from the valve to the ON OFF STAT switch is connected correctly This is the trouble shooting procedure for the the...

Страница 17: ...17 Figure 26 Check main burner orifice for debris blockage Burner pan is removed Burner Orifice...

Страница 18: ...44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 4 7 61 62 63 5 64 65 1 66 67 68 69 70 71 72 73 74 75 76 77 78 79 6 81 82 83 84 85 86 30 89 88 80 90 35 34 24 87 91 92 93 94 ONLY USE REPLACEMENT PART...

Страница 19: ...117917 68 Nut M6 Flange 2 117968 69 Exhaust Baffle 220763 70 Inner Draft Hood 220914 71 Screw 8 x 1 2 Blk 4 117917 72 Upper Draft Hood 222519 73 Draft Hood Cover Plate 222520 74 Starter Collar 5 dia...

Страница 20: ...rmance with local and national building regulations Before beginning the installation it is important that the these instructions be carefully read and understood J tul maintains a policy of continual...

Отзывы: