background image

4

1.0 Installation

NOTE: 

Your local officials have final authority in 

determining if a proposed installation is acceptable.  Any 

requirement that is not specifically addressed in this 

manual defaults to NFPA 211, and local codes in the U.S. or 

in Canada, CAN/CSA-B365-M and local codes.

 

Installing the Venting

The Jøtul F 

3

  can be vented from the top, the rear or from 

either the right or left side.  Follow the  instructions below 

for the desired venting location.

Top-exit Venting

When top exit venting is desired, use a 3mm allen wrench 

to remove the two set screws that secure the top casting 

to the sides of the stove and lift off the top casting.  Lay 

the top casting upside-down on a flat surface. Remove 

the 10mm bolt from the cross bar and remove the smoke 

outlet cover. See 

figure 1

.

NOTE: Ivory and Majolica stoves are built for rear-exit 

flue connection - the rear outlet is left open.  THE SMOKE 

OUTLET COVER PLATE MUST BE REINSTALLED OVER THE 

REAR OPENING BEFORE REPLACING THE TOP PLATE.

Secure the top plate to the stove body by 

tightening the set screws previously loosened.   

Rear-exit Venting

When rear exit venting is desired it will be necessary to 

“knock-out” the vent hole from the rear casting on Matte 

Black and Blue Black stoves. Ivory and Brown Majolica enamel 

stoves are built with the rear outlet open. Remove the top 

casting of the stove by removing the two 3mm set screws 

that secure the top to the sides. The set screws are located 

on the outside of the stove on the top of each side panel.   

Use a 10mm wrench to remove the double rear heatshields 

from the back of the stove. Remove the front door to avoid 

damage to the glass. 

NOTE: 

Loss of the hinge washer will 

result in improper door alignment when reinstalling the 

door.

USA/Canada

Stove pipe stop

Traverse bar securing 

smoke outlet cover to top 

casting

Stove pipe top

Fig. 1

Upside down

Top casting

Safety Notices

•  BURN SOLID, NATURAL WOOD FUEL ONLY. DO NOT  

BURN ANY OTHER FUEL.

•  DO NOT USE CHEMICALS OR FLUIDS TO START A FIRE. 

DO NOT BURN GARBAGE OR FLAMABLE FUELS.

•  DO NOT USE A GRATE OR ELEVATE THE FIRE. BUILD 

THE FIRE DIRECTLY ON THE HEARTH.

•  IF THIS ROOM HEATER IS NOT PROPERLY INSTALLED, 

A HOUSE FIRE MAY RESULT. TO REDUCE THE RISK OF 

FIRE, FOLLOW THE INSTRUCTIONS IN THIS MANUAL. 

FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RE-

SULT IN PROPERTY DAMAGE, BODILY INJURY, OR  LOSS 

OF LIFE.

•  CONTACT LOCAL BUILDING OR FIRE OFFICIALS ABOUT 

RESTRICTIONS AND INSTALLATION INSPECTION RE-

QUIREMENTS IN YOUR AREA.

•  ANY EXISTING CHIMNEY SYSTEM MUST BE INSPECTED 

BEFORE INSTALLATION OF THIS APPLIANCE.

•  DO NOT CONNECT THIS STOVE TO ANY AIR DISTRIBU-

TION DUCT OR SYSTEM.

•  EXTREMELY HOT WHILE IN OPERATION! KEEP CHIL-

DREN, CLOTHING, AND FURNITURE AWAY. CONTACT 

WILL CAUSE SKIN BURNS. USE A CHILD GUARD 

SCREEN TO PREVENT ACCIDENTAL CONTACT BY SMALL 

CHILDREN.

•  INSTALL SMOKE DETECTORS IN THE LIVING AREA AND 

BEDROOMS OF YOUR HOME. TEST THEM REGULARLY 

AND INSTALL FRESH BATTERIES TWICE ANNUALLY.

  WHEN INSTALLED IN THE SAME ROOM AS THE STOVE, 

A SMOKE OR CARBON MONOXIDE DETECTOR SHOULD 

BE LOCATED AS FAR FROM THE STOVE AS POSSIBLE 

TO PREVENT THE ALARM SOUNDING WHEN ADDING 

FUEL. 

•  Avoid creating a low pressure condition in the room 

where the stove is operating. Be aware that opera-

tion of an exhaust fan or clothes dryer can create a 

low pressure area and consequently promote flow 

reversal through the stove and chimney system. In 

some cases, the optional Outside Air Kit #154335 can 

be used to alleviate this condition. The chimney and 

building, however, always work together as a system 

- provision of outside air, directly or indirectly to an 

atmospherically vented appliance will not guarantee 

proper chimney performance. Consult your local Jøtul 

authorized dealer regarding specific installation/per-

formance issues.

•  Jøtul strongly recommends that this stove be in-

stalled by a professional solid fuel technician, or that 

you consult one if you do the work yourself. Also, 

consult your insurance company regarding any other 

specific requirements.

f i r e - p a r t s . c o m

Содержание F 3 C

Страница 1: ...J tul F 3 CB Installation and Operating Instructions for the USA and Canada 2 Exploded view 20 Kindly save these instructions for future reference J tul F 3 CB Manual Version R14 fire parts com...

Страница 2: ...tion Combustion Efficiency 14 Wood Fuel and Performance 14 Air Flow and Controls 15 Break in Procedure 15 Starting and Maintaining a Fire 16 6 0 Maintenance Ash Removal 17 Glass Care 17 7 0 General Ma...

Страница 3: ...Default values per previous Federal Register 40 CFR Part 60 Subpart AAA EPA validated efficiency and CO values were unavailable at the time of this printing These values will be made available in the...

Страница 4: ...WOOD FUEL ONLY DO NOT BURN ANY OTHER FUEL DO NOT USE CHEMICALS OR FLUIDS TO START A FIRE DO NOT BURN GARBAGE OR FLAMABLE FUELS DO NOT USE A GRATE OR ELEVATE THE FIRE BUILD THE FIRE DIRECTLY ON THE HEA...

Страница 5: ...r Fig 3C Secure thefirst sectionofstovepipe to thefluecollarusing two sheet metal screws USA Canada Fig 2 Spacer Nuts Heatshield with listing label should be installed on the outside Fig 3 Stove pipe...

Страница 6: ...conform to all of the following guidelines The chimney flue size should not be less than the cross sectional area of the stove flue collar The cross sectional area of the flue of a chimney with no wal...

Страница 7: ...onsult with your local building officials to discuss any local code requirements Common method When passing through a combustible wall to a masonry chimney this method requires the removal of all USA...

Страница 8: ...round the chimney connector s proposed location With a 6 round liner the minimum area required would be 43 x 43 square It is important to remember to locate the pass through at least 25 from the ceili...

Страница 9: ...the proper clearances to surrounding trim and mantels addressed in clearance section of this manual In addition fireplace installations must also adhere to the floor protection guidelines specified in...

Страница 10: ...in when installing the J tul F 3 near combustible surfaces A combustible surface is anything that can burn i e Sheet rock wall paper wood fabrics etc These surfaces are not limited to those that are v...

Страница 11: ...mm past the ash lip of the stove Must be 1 off the wall and 1 off the floor With standard legs the shield must be 40 high With optional short legs the shield must be 38 high Both shields must extend a...

Страница 12: ...17 6 6 6 Double wall pipe or shields 460mm 355mm 430mm 150mm 150mm 150mm Connector Unprotected Surface Protected Surface Clearances per NFPA 211 or CAN CSA B365 M Singlewall pipe vertical installatio...

Страница 13: ...015mm Height above the top of the stove 68 1730mm Top vent vertical assumes the connector pipe is exiting off the top of the stove and traveling vertically If top vented to any horizontal runs the sto...

Страница 14: ...l burn too quickly to take advantage of the stove s low end efficiency strength A seasoned log will have check marks on the ends and be lighter than an unseasoned log which will show little or no chec...

Страница 15: ...mid range position to allow adequate oxygen to support efficient combustion throughout the burn cycle Fig 16 Stove top thermometer 5 5 Break In Procedure The J tul F 3 CB is constructed of cast iron a...

Страница 16: ...ESULT IN PERMANENT DAMAGE TO THE HEATER Creosote and Soot Formation and the Need for Removal When wood is burned slowly it produces tar and other organic vapors which combine with expelled moisture to...

Страница 17: ...l F 3 Do not use substitutes Replacement glass panels can be ordered through your J tul dealer Glass removal Always operate the doors slowly and cautiously to avoid cracking or breaking the glass Neve...

Страница 18: ...e a utility light to inspect the stove inside and out for cracks or leaks Replace all cracked parts and repair any cement leaks with furnace cement Fig 17 Door Gasket Glass Glass clips Gaskets Door an...

Страница 19: ...or protection with a minimum insulating R value of 1 1 Alcove installation require a minimum R value of 1 1 If a UL ULC 8 0 Accessories Firescreen 350168 TheJ tulF3hasbeenapprovedforuseasanopenfirepla...

Страница 20: ...8 4 7 6 5 12 9 8 16 15 4 42 39 41 40 38 37 35 33 34 31 32 30 26 28 29 27 5 23 24 18 17 5 22 65 70 72 71 4 64 81 60 5 7 10 5 13 19 14 20 11 50 4 48 79 79 84 313 0 87 88 89 66 69 4 90 91 92 93 94 95 2c...

Страница 21: ...lip 52 Leg 53 Skrew M6x20 ST 8 8 ubeh 54 Washer 18x0 6 4x1 55 Bottom plate 57 Inner bottom plate 58 Screw sink head M6x25 sortkrom poz black poz 59 Burn plate left 60 Insulation Firemaster blanket af...

Страница 22: ...le and is extended only to and is solely for the benefit of the original retail purchaser of the J tul or Scan Stove or Fireplace Insert This paragraph sets forth the sole remedy available under this...

Страница 23: ...reach of this warranty shall be limited exclusively to the cost of furnishing a replacement component J TUL may at its discretion discharge all obligations by refunding the wholesale price of any defe...

Страница 24: ...result of J tul s vast experience dating back to when the company first started in 1853 We appreciate your trust in welcoming our product into your home and invite your comment and appraisal of our e...

Отзывы: