background image

15

USA/Canada

Secondary air

 allows combustion of volatile gas and other 

by-products of primary combustion that would otherwise 

enter the atmosphere  unburned. This unregulated air 

is preheated as it passes over the back of the stove and 

through a stainless steel manifold at the top of the firebox. 

This additional hot oxygen allows any unburned gasses 

to be burned inside the stove. The action of secondary 

combustion can be readily seen through the viewing glass 

a slow, rolling flames suspended over the main fuel bed 

and smaller jets of flame extending from the secondary 

manifold ports.  At the same time, no smoke will be 

observed exiting the chimney. This is evidence that the 

stove is operating at the so-called ”sweet-spot” wherein 

optimum efficiency is realized.

Start-Up Air Control

The start-up air control lever is located below the glass in 

the center of the front door.  This control is for “start - up” 

air only and should not be used to freshen an existing fire 

or during refueling.  Never leave the stove unattended 

while this control is open,  overfiring could result, which 

can damage the appliance. See 

figure 15

.-B.

Fig. 15

A

B

Use a Stove-top Thermometer

Determining the primary air setting for the best overall 

performance for your particular needs and installation 

will be established over time through trial and error. Each 

installation has unique characteristics  that will affect 

stove performance.  Use a stove-top thermometer to 

monitor the status of the fire.  Place the thermometer 

on the stove top,  centered two one side or the other. See 

fig. 16. Generally speaking, once the stove temperature 

has reached 400°F - 600°F, the air control may be set in a 

mid-range position to allow adequate oxygen to support 

efficient combustion throughout the burn cycle.

Fig. 16

Stove top thermometer

5.5 Break-In Procedure

The Jøtul F 

CB is constructed of cast iron and stove 

furnace cement.  Cast iron, while very durable, expands 

and contracts as it is heated and cooled. This type of 

construction requires the stove to be “broken-in” gradually 

so that thermal expansion does not occur too quickly. The 

following steps describe the proper break-in procedure for 

the Jøtul F 3

 

CB:

1.   Light a small fire of newspaper and kindling. Only al-

low the stove to reach a maximum surface tempera-

ture of 200°F (93° C). Burn for approximately 1 hour.

2.  Allow the stove to cool to room temperature.
3.  Light a second fire, allowing the stove to reach a 

maximum temperature of 300°F (149°C) for 1 hour.

4.  Cool the stove to room temperature.
5.  Light a third fire and gradually allow the stove to 

reach a surface temperature of 400°F (204°C).

6.  Cool stove to room temperature. This completes the 

“break-in” procedure.

Note

: Keep the stove under 400°F (204°C) surface 

temperature during any “break-in fire”, with the exception 

of the last “break-in” fire.  If the temperature exceeds 400°F, 

move the primary air control lever all the way to the left 

to shut off the air supply completely. It is normal that the 

stove top temperature will continue to climb until the fuel 

burns down somewhat. Once the fire is out and the stove 

has cooled to room temperature, continue the break-in 

procedure. 

Never attempt to reduce the temperature by 

removing burning logs from the fire.

 

NOTE:

 

It is normal

 for a new painted stove to emit an odor 

and smoke during its first several fires. This is caused by 

the seasoning of the high temperature paint and will 

diminish with each fire. Opening a window or door to 

provide additional ventilation will alleviate this condition.

f i r e - p a r t s . c o m

Содержание F 3 C

Страница 1: ...J tul F 3 CB Installation and Operating Instructions for the USA and Canada 2 Exploded view 20 Kindly save these instructions for future reference J tul F 3 CB Manual Version R14 fire parts com...

Страница 2: ...tion Combustion Efficiency 14 Wood Fuel and Performance 14 Air Flow and Controls 15 Break in Procedure 15 Starting and Maintaining a Fire 16 6 0 Maintenance Ash Removal 17 Glass Care 17 7 0 General Ma...

Страница 3: ...Default values per previous Federal Register 40 CFR Part 60 Subpart AAA EPA validated efficiency and CO values were unavailable at the time of this printing These values will be made available in the...

Страница 4: ...WOOD FUEL ONLY DO NOT BURN ANY OTHER FUEL DO NOT USE CHEMICALS OR FLUIDS TO START A FIRE DO NOT BURN GARBAGE OR FLAMABLE FUELS DO NOT USE A GRATE OR ELEVATE THE FIRE BUILD THE FIRE DIRECTLY ON THE HEA...

Страница 5: ...r Fig 3C Secure thefirst sectionofstovepipe to thefluecollarusing two sheet metal screws USA Canada Fig 2 Spacer Nuts Heatshield with listing label should be installed on the outside Fig 3 Stove pipe...

Страница 6: ...conform to all of the following guidelines The chimney flue size should not be less than the cross sectional area of the stove flue collar The cross sectional area of the flue of a chimney with no wal...

Страница 7: ...onsult with your local building officials to discuss any local code requirements Common method When passing through a combustible wall to a masonry chimney this method requires the removal of all USA...

Страница 8: ...round the chimney connector s proposed location With a 6 round liner the minimum area required would be 43 x 43 square It is important to remember to locate the pass through at least 25 from the ceili...

Страница 9: ...the proper clearances to surrounding trim and mantels addressed in clearance section of this manual In addition fireplace installations must also adhere to the floor protection guidelines specified in...

Страница 10: ...in when installing the J tul F 3 near combustible surfaces A combustible surface is anything that can burn i e Sheet rock wall paper wood fabrics etc These surfaces are not limited to those that are v...

Страница 11: ...mm past the ash lip of the stove Must be 1 off the wall and 1 off the floor With standard legs the shield must be 40 high With optional short legs the shield must be 38 high Both shields must extend a...

Страница 12: ...17 6 6 6 Double wall pipe or shields 460mm 355mm 430mm 150mm 150mm 150mm Connector Unprotected Surface Protected Surface Clearances per NFPA 211 or CAN CSA B365 M Singlewall pipe vertical installatio...

Страница 13: ...015mm Height above the top of the stove 68 1730mm Top vent vertical assumes the connector pipe is exiting off the top of the stove and traveling vertically If top vented to any horizontal runs the sto...

Страница 14: ...l burn too quickly to take advantage of the stove s low end efficiency strength A seasoned log will have check marks on the ends and be lighter than an unseasoned log which will show little or no chec...

Страница 15: ...mid range position to allow adequate oxygen to support efficient combustion throughout the burn cycle Fig 16 Stove top thermometer 5 5 Break In Procedure The J tul F 3 CB is constructed of cast iron a...

Страница 16: ...ESULT IN PERMANENT DAMAGE TO THE HEATER Creosote and Soot Formation and the Need for Removal When wood is burned slowly it produces tar and other organic vapors which combine with expelled moisture to...

Страница 17: ...l F 3 Do not use substitutes Replacement glass panels can be ordered through your J tul dealer Glass removal Always operate the doors slowly and cautiously to avoid cracking or breaking the glass Neve...

Страница 18: ...e a utility light to inspect the stove inside and out for cracks or leaks Replace all cracked parts and repair any cement leaks with furnace cement Fig 17 Door Gasket Glass Glass clips Gaskets Door an...

Страница 19: ...or protection with a minimum insulating R value of 1 1 Alcove installation require a minimum R value of 1 1 If a UL ULC 8 0 Accessories Firescreen 350168 TheJ tulF3hasbeenapprovedforuseasanopenfirepla...

Страница 20: ...8 4 7 6 5 12 9 8 16 15 4 42 39 41 40 38 37 35 33 34 31 32 30 26 28 29 27 5 23 24 18 17 5 22 65 70 72 71 4 64 81 60 5 7 10 5 13 19 14 20 11 50 4 48 79 79 84 313 0 87 88 89 66 69 4 90 91 92 93 94 95 2c...

Страница 21: ...lip 52 Leg 53 Skrew M6x20 ST 8 8 ubeh 54 Washer 18x0 6 4x1 55 Bottom plate 57 Inner bottom plate 58 Screw sink head M6x25 sortkrom poz black poz 59 Burn plate left 60 Insulation Firemaster blanket af...

Страница 22: ...le and is extended only to and is solely for the benefit of the original retail purchaser of the J tul or Scan Stove or Fireplace Insert This paragraph sets forth the sole remedy available under this...

Страница 23: ...reach of this warranty shall be limited exclusively to the cost of furnishing a replacement component J TUL may at its discretion discharge all obligations by refunding the wholesale price of any defe...

Страница 24: ...result of J tul s vast experience dating back to when the company first started in 1853 We appreciate your trust in welcoming our product into your home and invite your comment and appraisal of our e...

Отзывы: