I & M CSDT Series

Installation & Maintenance Instructions for  

CSDT Series Clean Steam Disc Traps

3170 Wasson Road  • Cincinnati, OH  45209 USA

Phone 513-533-5600  •  Fax 513-871-0105

E-Mail: [email protected]  •  www.steriflowvalve.com

Please read these instructions carefully!

Your Steriflow product will provide you with long, trou-

ble-free service if it is correctly installed and maintained. 

Spending a few minutes now reading these instructions 

can save hours of trouble and downtime later. When 

making repairs, use only genuine Steriflow Valve parts, 

available for immediate shipment from the factory.

Ideal Installation Schematic

Installation

Check that steam supply is shut off. Ensure that 

1. 

all system pressures are off and trap is cool before 

opening.

Remove steam trap from piping by disconnecting 

2. 

the inlet and outlet Tri-Clamp

®

 and slipping the trap 

from the line.

The trap may be installed horizontally or vertically 

3. 

with discharge downward. The preferred installation 

is in the horizontal position as close as possible to 

the equipment being drained. Whenever possible, 

position the trap below the unit being drained.

Piping should be the same size as the trap connec-

4. 

tion. To avoid excessive backpressure, discharge 

piping should not be smaller on short runs. For 

longer lines, use one size larger.

A full-ported shut-off valve upstream is recommend-

5. 

ed to allow isolation for servicing. A shutoff valve 

downstream will protect against back flow from the 

return line during servicing.

A strainer should be installed with a blowdown valve 

6. 

immediately upstream of the trap to protect it from 

grit, scale and other foreign matter.

A test valve outlet and pressure gauges should be 

7. 

provided to check trap operation where condensate 

discharge is piped to a return line.

For freeze protection, the trap should be installed 

8. 

vertically with discharge downward, as shown 

above. Discharge as close to drain connection 

as practical and discharge to atmosphere directly 

through a short pipe. A vacuum breaker upstream 

may be require to provide complete drainage.

7

1

3

6

6

8

4

5

2

1

9

Shutoff Valve

1. 

Test Valve

2. 

Blowdown Valve

3. 

Strainer

4. 

Pipe Union

5. 

Pressure Gauge (with Snubber)

6. 

Pipe Eccentric Reducer (if required)

7. 

Steriflow CSDT Series Disc Trap

8. 

Check Valve

9. 

6

3

1

4

8

5

6

2

9

Shutoff Valve

1. 

Test Valve

2. 

Blowdown Valve

3. 

Strainer

4. 

Pipe Union

5. 

Pressure Gauge

 

6. 

(with Snubber)

Steriflow CSDT Series

 

7. 

Disc Trap

Check Valve

8. 