background image

3170฀Wasson฀Road฀฀•฀฀Cincinnati,฀OH฀฀45209฀฀USA

Phone฀513-533-5600฀฀•฀฀Fax฀513-871-0105

[email protected]฀฀•฀฀www.steriflowvalve.com

Bulletin฀IM-CSDT-0409฀

Maintenance

Warning! 
Hot discharge from the trap may cause severe 
burns. Shut off steam supply and make sure that the 
trap is cool to touch before repairing or inspecting.

The trap can be maintained without disturbing the 

1. 

piping connections. Ensure that the trap is isolated 

- upstream and downstream - before attempting to 

dismantle it. ALLOW THE TRAP TO COOL BE-

FORE DISMANTLING.

The Steriflow disc trap can be cleaned or repaired 

2. 

by removing the disc and leaving the body in the 

pipe line.

Before loosening the cap, the trap must be isolated 

3. 

from both, live steam lines and condensate return 

lines. Open the blowdown valve to relieve trapped 

pressure and allow time for the trap to cool.

Remove the cap and disc.

4. 

Dirt and deposits can cause erratic operation. Disc 

5. 

can be removed from inspection and sealing sur-

faces can be wiped with a cleaning solvent. Periodic 

cleaning of the disc and seat will facilitate trouble-

free performance. DO NOT USE ABRASIVES / 

CORROSIVE MEDIA FOR CLEANING.

If surface is scratched or worn, replace with a new 

6. 

factory-lapped disc. Only the disc and seat are 

subject to wear. A worn disc can be replaced and 

slight seat wear can be corrected by resurfacing a 

lap plate.

Lubricate the cap threads sparingly with anti-seize 

7. 

compound, taking care not to apply to disc or seat 

surfaces.

Tighten cap until firmly seated, approximately 80 - 

8. 

85 ft-lbs. DO NOT OVER-TIGHTEN.

CSDT Series Disc Trap

Отзывы: