Some dehumidification, air mover runs continuously but 

compressor only runs sporadically.

1.   Unit is in defrost cycle, DEFROST light on
2.   Defrost thermistor defective or loose
3.   Loose connection in compressor circuit
4.   Defective compressor overload
5.   Defective compressor
6.   Defective relay
7.   Upper housing is not sealed to lower housing
8.  Check dehumidistat for proper setting

No dehumidification, air mover runs but compressor does 

not.

1. Bad connection in compressor circuit
2. Safety float switch closed, check pump reservoir
3. Defective compressor capacitor
4.   Defective compressor overload
5.   Defective compressor
6.   Defective control board

Air mover does not run. Compressor runs briefly but cycles 

on and off.

1.   Loose connection in blower circuit
2.   Obstruction prevents impeller rotation
3.   Defective air mover

Unit removes some water but not as much as expected.

1.   Air temperature and/or humidity have dropped
2.   Humidity meter and/or thermometer used are out of 

calibration

3.   Unit has entered defrost cycle
4.   Air filter dirty
5.   Defective defrost thermistor
6.   Low refrigerant charge
7.   Air leak such as loose front cover
8.   Defective compressor
9.   Restrictive exhaust or inlet ducting

Unit runs but does not pump water.

1.   Hose kinked or plugged
2.   Pump motor defective
3.   Pump check valve plugged
4.   Bad connection in pump circuit
5.   Hose disconnected internally
6.   Defective control board (pump phase)

Unit pumps water automatically but not when PURGE button 

is pushed.

1. Bad connection in PURGE button circuit
2. Defective control board

Evaporator coil frosted continuously, low dehumidifying 

capacity.

1. Defrost thermistor loose or defective
2. Low refrigerant charge
3. Dirty air filter or restricted air flow
4. Upper housing is not sealed to lower housing

Compressor runs with POWER button OFF.

1. Defective relay
2. Defective control board
3. Upper housing not sealed to tower

No hour meter display when the HOURS button is pressed.

1.   Battery charge is low. Replace battery
2.   Defective control board

4.4 Air Mover Replacement

The blower has a PSC motor and internal thermal overload 

protection. If defective, the complete assembly must be 

replaced.
1.   Unplug power cord
2.   Remove the front cover
3.   Remove the four screws attaching the blower to the 

mounting support

4.   Disconnect the blower leads
5.   Reassemble the new blower using the above procedure 

in reverse

4.5 Thermistor Replacement

The defrost thermistor is attached to the refrigerant suction 

line between the accumulator and the evaporator.
To replace thermistor:
1.   Unplug the dehumidifier
2.   Remove the front cover
3.   Remove aluminum tape
4.   Remove control panel
5.   Unthread thermistor from condenser grommet
6.   Detach thermistor from control board jumper, J1
7.   Reassemble thermistor and dehumidifier using the above 

procedure in reverse

4.6 Condensate Pump Replacement

The internal condensate pump removes water that collects in 

the reservoir.
To replace the condensate pump:
1.   Unplug the unit
2.   Remove the front cover
3.   Unplug the pump wires from the wire harness

Содержание Ultimate 340

Страница 1: ...ntially drier air as well as for drying areas to much lower humidity levels than conventional dehumidifiers The Ultimate 340 LGR High Capacity Dehumidifier Improved water removal 145 pints per day AHA...

Страница 2: ...always be used in the upright position The air inlet on top the side outlet must be at least 1 foot from walls and other obstructions to air flow Read the operation and maintenance instructions caref...

Страница 3: ...before the final purge 2 8 Hour Meter The digital hour meter displays the cumulative and job time the dehumidifier has been turned on to the tenth of an hour The total and job hours measured are stor...

Страница 4: ...claim authorization and technical assistance 4 2 Technical Description The Ultimate 340 uses a refrigeration system similar to an air conditioner s to remove heat and moisture from incoming air and to...

Страница 5: ...d pump phase Unit pumps water automatically but not when PURGE button is pushed 1 Bad connection in PURGE button circuit 2 Defective control board Evaporator coil frosted continuously low dehumidifyin...

Страница 6: ...pump fails and cannot be replaced immediately the Ultimate 340 can be used by draining by gravity 1 Unplug the unit and remove the front cover 2 Push the plastic plug on the right side see Fig 4 out f...

Страница 7: ...L 7 WHT 9 WHT 7 YEL BLU GRY WHT RUN CAPACITOR COMPRESSOR BLOWER MOTOR LEVEL SWITCH RUN CAPACITOR RELAY LOW PRESSURE PUMP FLOAT SAFETY NC NO THERMISTOR PLUG R C S E5 E4 E1 E2 E3 6 0 4 1 WIRE NUT YEL YE...

Страница 8: ...3 EA 1 Front 19 PH 4026304 EA 2 12 Wheel Item Part No Qty Description 20 PH 4026311 EA 1 Axle 21 PH 1284404 EA 2 Cotter Pin 22 PH 4027273 EA 1 Skid Plate 23 PH 4023080 EA 1 Coupling Insert 38 Tube 24...

Страница 9: ...9 www jondon com Toll Free 1 800 556 6366 This page intentionally left blank...

Страница 10: ...tion etc resulting from misuse abuse lack of normal care corrosion freezing tampering modification unauthorized or improper repair or installation accident acts of nature or any other cause beyond Jon...

Отзывы: