ZFR1812 Wall Mount Wireless Field Bus Router Installation Instructions
6
For further information on how to set up a field
controller to work with the ZFR1812 Router, refer to the
following documents:
•
FAC3611 Advanced Application Field Equipment
Controller Installation Instructions (Part No. 24-
10143-470)
•
FEC16 Field Equipment Controller Installation
Instructions (Part No. 24-10143-136)
•
FEC26 Field Equipment Controller Installation
Instructions (Part No. 24-10143-144)
•
IOM17 and IOM27 Input/Output Modules
Installation Instructions (Part No. 24-1044-76)
•
IOM37 Input/Output Module Installation
Instructions (Part No. 24-1044-84)
•
IOM47 Input/Output Module Installation
Instructions (Part No. 24-1044-92)
•
VMA16 Series Variable Air Volume Controllers
Installation Instructions (Part No. 24-10143-20)
Table 2: Connecting the ZFR1812 Router to a Field Controller
Field
Controller
Model
Plug the ZFR1812 Router
Connector Cable into the
Following Jack on the Field
Controller:
Connection Points for the
Bluetooth® CVT
Commissioning Interface
and Other SA Bus Products
1
Use This
Communications Port
between WEFC and
Wired IOMs, WRZ
Sensors, or VFDs:
FAC26
FC Bus RJ-12 Jack
SA Bus RJ-12 Jack
SA Bus Terminals
FAC36
FC Bus RJ-12 Jack
SA Bus RJ-12 Jack
SA Bus Terminals
FEC16
FC Bus RJ-12 Jack
SA Bus RJ-12 Jack
SA Bus Terminals
FEC26
FC Bus RJ-12 Jack
SA Bus RJ-12 Jack
SA Bus Terminals
IOM17
2
,
3
SA/FC Bus RJ-12 Jack
Not available in wireless mode.
Use CCT with ZFR Dongle.
N/A
IOM27
SA/FC Bus RJ-12 Jack
Not available in wireless mode.
Use CCT with ZFR Dongle.
N/A
IOM37
SA/FC Bus RJ-12 Jack
Not available in wireless mode.
Use CCT with ZFR Dongle.
N/A
IOM47
SA/FC Bus RJ-12 Jack
Not available in wireless mode.
Use CCT with ZFR Dongle.
N/A
VMA1615/30
FC Bus RJ-12 Jack
SA Bus RJ-12 Jack
SA Bus Terminals
1.
SA Bus Products include the DIS1710 Local Controller Display, the MS-BTCVT-1 Wireless
Commissioning Converter, and the NS Series (hard-wired) Network Sensors, Balancing Sensors, and
Discharge Air Temperature Sensors.
2.
IOMs cannot be used in wireless mode to extend the IO of a field controller. You must always hardwire
IOMs to their host field controller.
3.
Do not connect any device to the SA Bus/FC Bus terminal block when using the IOM with a ZFR1812.
Figure 7: Pin Number Assignments for
RJ-12 Jack
Power
(15 VDC)
SA or FC Bus +
SA or FC Bus
-
Bus and Power Common
Power
(15 VDC)
Sensor, SA Bus, or FC Bus Port
(RJ-12 Modular Jack)
Bus and Power Common
FI
G
:R
J_
p
in
o
u
t
2
3
4
5
6
1