background image

ZFR1811 Wireless Field Bus Router Installation Instructions 

7

Setup and Adjustments       

Set the PAN Offset value of the ZFR1811 Router using 
the DIP switches (located on the back of the cover) to 
configure the ZFR1811 Router to communicate on the 
wireless mesh network. See Figure 1 and Figure 8.

The value equals the sum of the numbers set to ON. 
For example, if the DIP switches labelled 1, 4, and 8   
are set to ON, the PAN Offset value is 13 
(1 + 4 + 8 = 13). 

When selecting a PAN Offset value for a wireless 
system:

Use a unique PAN Offset value for each wireless 
mesh network at a job site.

Use the same PAN Offset value for each wireless 
device in a wireless mesh network - the 
ZFR1810 Coordinator and each associated 
ZFR1811 Router and WRZ Sensor.

Note:

On some date code labels, the switch position 

numbers on the bottom of the dip switch are reversed. 
In either case, the switch positions are always read 
right to left.

IMPORTANT:

Ensure that the PAN OFFSET 

switches are set to the same value for each 
ZFR1810 Coordinator, ZFR1811 Router, and 
WRZ Sensor in a mesh network.

IMPORTANT: Do not

 connect the ZFR1811 Router 

to the power supply before setting the PAN OFFSET 
switches.

IMPORTANT:

On the MS/TP Address switch block 

of the associated FEC/IOM/VMA16 Field Controller, 
set switch 128 to ON for use with a ZFR1811 Router.

Figure 8: Sample DIP Switch Settings

Содержание ZFR1811

Страница 1: ... for control of the target zone A ZFR1811 Router is powered directly from the connected field controller s 15 VDC output The Router can also be powered by the power supply in the Repeater Accessory Kit to serve as a stand alone repeater extending the range of the communications within the wireless mesh network Refer to the ZFR1800 Series Wireless Field Bus System Technical Bulletin LIT 12011295 or...

Страница 2: ...d including interference that may cause undesired operation Warning Part 15 21 Changes or modifications not expressly approved by the party responsible for compliance could void the user s authority to operate the equipment Industry Canada Statement The term IC before the certification registration number only signifies that the Industry Canada technical specifications were met Le terme IC précéda...

Страница 3: ...hs if its position changes relative to another wireless device or if its environment changes If a ZFR1811 Router shows poor signal strength you may be able to improve the signal strength by rotating the ZFR1811 Router Locate the ZFR1811 Router in line of sight with as many ZFR1811 Routers and WRZ Sensors as possible Do not mount the ZFR1811 Router in recessed areas metal enclosures or shelving uni...

Страница 4: ... network ensure that the DIP switch for Address 128 is set to the ON position Table 1 Indoor Line of Sight Transmission Ranges Range Type Transmission Distance ZFR1810 Coordinator ZFR1811 Router WRZ Series Sensor Recommended 15 2 m 50 ft 15 2 m 50 ft Maximum 76 2 m 250 ft 30 m 98 ft IMPORTANT Do not connect supply power to the ZFR1811 Router before finishing wiring and checking all wiring connecti...

Страница 5: ... which are really the SA Bus terminals on a VMA1610 1620 in wireless mode as indicated in Figure 6 and Figure 7 Note The VMA1615 1630 controller have RJ 12 connectors on the FC bus and SA bus These controllers do not require port swapping when in wireless mode Table 2 Connecting the ZFR1811 Router to a Field Controller Field Controller Model Plug the ZFR1811 Router Connector Cable into the Followi...

Страница 6: ...J 12 Jack FIG ZFRCBL Figure 5 Pin Number Assignments for RJ 12 Jack Power 15 VDC SA or FC Bus SA or FC Bus Bus and Power Common Power 15 VDC Sensor SA Bus or FC Bus Port RJ 12 Modular Jack Bus and Power Common FIG RJ_pinout 2 3 4 5 6 1 Figure 6 Connecting an IOM to a Wireless Enabled VMA1610 1620 Field Controller Figure 7 Wiring a Discharge Air Netsensor Zone Netsensor with Terminal Block or IOM t...

Страница 7: ...ob site Use the same PAN Offset value for each wireless device in a wireless mesh network the ZFR1810 Coordinator and each associated ZFR1811 Router and WRZ Sensor Note On some date code labels the switch position numbers on the bottom of the dip switch are reversed In either case the switch positions are always read right to left IMPORTANT Ensure that the PAN OFFSET switches are set to the same v...

Страница 8: ... Refer to the WRZ Series Wireless Room Temperature Sensors Installation Instructions Part No 24 10332 2 for more information Approximately once every 10 seconds the Signal Strength LED flashes to indicate the strength of the signal received from neighboring devices See Table 3 Note The Signal Strength LEDs on all the ZFR1811 routers in a network extinguish after approximately 2 hours of normal ope...

Страница 9: ...shes Excellent 2 Flashes Good 1 Flash Weak OFF for 3 seconds None Network Reform Operation during network reform Rapid Flashes for 5 minutes rapid flashes occur for up to 5 minutes when the Reform Network option is initiated to the network the ZFR1811 Router disconnects itself from the network when the PAN OFFSET is changed on the ZFR1811 Router when the PAN OFFSET is changed on the ZFR1811 Router...

Страница 10: ...BTCVT 1 Wireless Commissioning Converter or DIS1710 Local Controller Display ZFR USBHA 0 USB Dongle with ZFR Driver provides a wireless connection through the CCT to allow wireless commissioning of the wireless enabled FAC FEC IOM and VMA16 controllers The USB ZFR Dongle is also used with the ZFR Checkout Tool used to troubleshoot and validate ZFR wireless meshes using a laptop computer ZFR1811 Wi...

Страница 11: ...t to Canadian ICES 003 Class B Limits Industry Canada IC RSS 210 Transmitter Identification ZFR1810 0 5969A MATRIXLP Transmitter Identification ZFR1810 1 279A WRZRADIO Australia and New Zealand RCM Mark Australia NZ Emissions Compliant Europe CE Mark Johnson Controls Inc declares that this product is in compliance with the essential requirements and other relevant provisions of the EMC Directive T...

Отзывы: