Johnson Controls ZFR1811 Скачать руководство пользователя страница 2

ZFR1811 Wireless Field Bus Router Installation Instructions

2

North American Emissions Compliance

United States

Canada

Installation

Follow these guidelines when installing a 
ZFR1811 Router:

Transport the ZFR1811 Router in the original 
container to minimize vibration and shock damage.

Verify that one 1/2 in.

 

trade size Electrical 

Mechanical Tubing (EMT) connector is shipped 
with the ZFR1811 Router.

Do not drop the ZFR1811 Router or subject it to 
physical shock.

Dimensions

See Figure 1 for physical features and dimensions of 
the ZFR1811 Router.  

Compliance Statement (Part 15.19)

This device complies with Part 15 of the FCC Rules. 
Operation is subject to the following two conditions:

1.

This device may not cause harmful interference, 
and

2.

This device must accept any interference 
received, including interference that may cause 
undesired operation.

Warning (Part 15.21)

Changes or modifications not expressly approved by 
the party responsible for compliance could void the 
user’s authority to operate the equipment.

Industry Canada Statement

The term 

IC

 before the certification/registration 

number only signifies that the Industry Canada 
technical specifications were met.

Le terme « IC » précédant le numéro d'accréditation/
inscription signifie simplement que le produit est 
conforme aux spécifications techniques d'Industry 
Canada.

IMPORTANT:

Before installing the ZFR1811 

Router in plenum applications, verify acceptance of 
exposed plastic materials in plenum areas with the 
local building authority. Building codes for plenum 
requirements vary by location.

Some local building authorities accept compliance to 
UL 1995, Heating and Cooling Equipment, whereas 
others use different acceptance criteria.

Figure 1: ZFR1811 Wireless Field Bus Router, 

Physical Features and Dimensions, mm (in.)

Содержание ZFR1811

Страница 1: ... for control of the target zone A ZFR1811 Router is powered directly from the connected field controller s 15 VDC output The Router can also be powered by the power supply in the Repeater Accessory Kit to serve as a stand alone repeater extending the range of the communications within the wireless mesh network Refer to the ZFR1800 Series Wireless Field Bus System Technical Bulletin LIT 12011295 or...

Страница 2: ...d including interference that may cause undesired operation Warning Part 15 21 Changes or modifications not expressly approved by the party responsible for compliance could void the user s authority to operate the equipment Industry Canada Statement The term IC before the certification registration number only signifies that the Industry Canada technical specifications were met Le terme IC précéda...

Страница 3: ...hs if its position changes relative to another wireless device or if its environment changes If a ZFR1811 Router shows poor signal strength you may be able to improve the signal strength by rotating the ZFR1811 Router Locate the ZFR1811 Router in line of sight with as many ZFR1811 Routers and WRZ Sensors as possible Do not mount the ZFR1811 Router in recessed areas metal enclosures or shelving uni...

Страница 4: ... network ensure that the DIP switch for Address 128 is set to the ON position Table 1 Indoor Line of Sight Transmission Ranges Range Type Transmission Distance ZFR1810 Coordinator ZFR1811 Router WRZ Series Sensor Recommended 15 2 m 50 ft 15 2 m 50 ft Maximum 76 2 m 250 ft 30 m 98 ft IMPORTANT Do not connect supply power to the ZFR1811 Router before finishing wiring and checking all wiring connecti...

Страница 5: ... which are really the SA Bus terminals on a VMA1610 1620 in wireless mode as indicated in Figure 6 and Figure 7 Note The VMA1615 1630 controller have RJ 12 connectors on the FC bus and SA bus These controllers do not require port swapping when in wireless mode Table 2 Connecting the ZFR1811 Router to a Field Controller Field Controller Model Plug the ZFR1811 Router Connector Cable into the Followi...

Страница 6: ...J 12 Jack FIG ZFRCBL Figure 5 Pin Number Assignments for RJ 12 Jack Power 15 VDC SA or FC Bus SA or FC Bus Bus and Power Common Power 15 VDC Sensor SA Bus or FC Bus Port RJ 12 Modular Jack Bus and Power Common FIG RJ_pinout 2 3 4 5 6 1 Figure 6 Connecting an IOM to a Wireless Enabled VMA1610 1620 Field Controller Figure 7 Wiring a Discharge Air Netsensor Zone Netsensor with Terminal Block or IOM t...

Страница 7: ...ob site Use the same PAN Offset value for each wireless device in a wireless mesh network the ZFR1810 Coordinator and each associated ZFR1811 Router and WRZ Sensor Note On some date code labels the switch position numbers on the bottom of the dip switch are reversed In either case the switch positions are always read right to left IMPORTANT Ensure that the PAN OFFSET switches are set to the same v...

Страница 8: ... Refer to the WRZ Series Wireless Room Temperature Sensors Installation Instructions Part No 24 10332 2 for more information Approximately once every 10 seconds the Signal Strength LED flashes to indicate the strength of the signal received from neighboring devices See Table 3 Note The Signal Strength LEDs on all the ZFR1811 routers in a network extinguish after approximately 2 hours of normal ope...

Страница 9: ...shes Excellent 2 Flashes Good 1 Flash Weak OFF for 3 seconds None Network Reform Operation during network reform Rapid Flashes for 5 minutes rapid flashes occur for up to 5 minutes when the Reform Network option is initiated to the network the ZFR1811 Router disconnects itself from the network when the PAN OFFSET is changed on the ZFR1811 Router when the PAN OFFSET is changed on the ZFR1811 Router...

Страница 10: ...BTCVT 1 Wireless Commissioning Converter or DIS1710 Local Controller Display ZFR USBHA 0 USB Dongle with ZFR Driver provides a wireless connection through the CCT to allow wireless commissioning of the wireless enabled FAC FEC IOM and VMA16 controllers The USB ZFR Dongle is also used with the ZFR Checkout Tool used to troubleshoot and validate ZFR wireless meshes using a laptop computer ZFR1811 Wi...

Страница 11: ...t to Canadian ICES 003 Class B Limits Industry Canada IC RSS 210 Transmitter Identification ZFR1810 0 5969A MATRIXLP Transmitter Identification ZFR1810 1 279A WRZRADIO Australia and New Zealand RCM Mark Australia NZ Emissions Compliant Europe CE Mark Johnson Controls Inc declares that this product is in compliance with the essential requirements and other relevant provisions of the EMC Directive T...

Отзывы: