![Johnson Controls YVAHP036B21S Скачать руководство пользователя страница 76](http://html.mh-extra.com/html/johnson-controls/yvahp036b21s/yvahp036b21s_engineering-manual_2023242076.webp)
OPTIONAL PARTS
3-10
TC-16001-rev.5
54-5/16 (1380)
46-3/4 (1
187)
Securing Screw
(Accessory)
11-13/16
(300)
14-9/16
(370)
15-3/4
(400)
10-13/16
(274)
9-1/4
(235)
Toppling Prevention Tool
(other optional parts)
Rear Air Inlet
Hood
Securing Screw
(Accessory)
Foundation
(Field-Supplied)
Air Outlet Hood
Air Outlet Grille
Left Air Inlet
Hood
Outdoor Unit
9-13/16
(250)
37-3/8 (950)
Securing Screw
Securing Screw
inch (mm)
47-1/4 (1200)
NOTE:
When securing parts (marked ), the securing screws for upper cover and front cover for air outlet hood should be utilized.
Securing screws (accessory) should be utilized to secure others.
< Installation >
Specifications
Part Name
Air Outlet Hood
Rear Air Inlet Hood
Left Air Inlet Hood
Model
Item
ASG-SP11FCS2
ASG-SP11BAS2
ASG-SP11LAS2
Applicable Outdoor Unit Model
036 to 060
Quantity (per outdoor unit)
1
Material
Stainless
(SUS304)
Stainless
(SUS304)
Stainless
(SUS304)
Weight
lbs (kg)
28.7 (13.0)
28.7 (13.0)
17.6 (8.0)
Configuration
Assembly on site
Accessory
Hood
1 (for Upper)
1 (for Lower)
1
1
Securing Screw
[Spare]
M5 (SUS) x
L=1/2 inch (12mm) x
4 [2]
M5 (SUS) x
L=1/2 inch (12mm) x
7 [2]
M5 (SUS) x
L=1/2 inch (12mm) x
10 [2]
Assembling Screw
[Spare]
M5 (SUS) x
L=9/16 inch (14mm) x
35 [2]
M5 (SUS) x
L=9/16 inch (14mm) x
16 [2]
M5 (SUS) x
L=9/16 inch (14mm) x
14 [2]
Installation Manual
Installation Restriction
1. It can not be used with the Wind Guard and the Airflow Guide.
2. The installation height of outdoor unit should be considered with snow
accumulation. Heighten the foundation or install the frame (higher than snow
accumulation). Install the outdoor unit on it and secure using anchor bolts.
The service space should be secured with consideration of snow accumulation
and snow removal.
3. When multiple outdoor units are installed serially and horizontally, secure a
distance of more than 4 in (100mm) between the outdoor units. Do not put
any obstacles in the airflow direction. If there are obstacles, a short-circuit will
occur or the airflow volume will decrease.
Cautions
1. Paint touch-up or caulk at screw parts for corrosion prevention (field-supplied).
2. If the outdoor unit is installed in an area where snow blows up from the
ground, install a partition (field-supplied).
3. The outdoor unit does not have strength to maintain the Snow Protection
Hood from strong winds or earthquake. Attach the stay or Toppling Prevention
Tool to protect the Snow Protection Hood from falling.
NOTES:
1. This Snow Protection Hood is to prevent snow from entering the outdoor unit.
2. It is assembled onsite. (Securely tighten the screws to assemble. If not, the screws may become loose
and cause a vibration.)
3. The operation noise is slightly increased by attaching a Snow Protection Hood.