OUTDOOR UNITS
TC-16001-rev.5
2-11
2.9 Electrical Data
Model
Outdoor Unit
INV Comp.
Hz
Voltage
Max.
Min.
MCA
MOP
Max. Fuse
RLA
LRA
[Hz]
[V]
[V]
[V]
[A]
[A]
[A]
[A]
[A]
(H,Y,C)VAHP036B21S
60
208/230
228/253
188/207
31
40
40
24
30
(H,Y,C)VAHP048B21S
60
208/230
228/253
188/207
31
40
40
24
30
(H,Y,C)VAHP060B21S
60
208/230
228/253
188/207
31
40
40
24
30
Model
Fan Motor
Wiring Size
Conduit Tube
Output
FLA
Power Supply
Wiring
Ground Wiring
Communication
Cable
for Power
Supply Wiring
[kW]
[A]
[AWG]
[AWG]
[AWG]
[in. (mm)]
(H,Y,C)VAHP036B21S
0.058+0.058
0.5+0.5
8
8
18
3/4 (19.05)
(H,Y,C)VAHP048B21S
0.058+0.058
0.5+0.5
8
8
18
3/4 (19.05)
(H,Y,C)VAHP060B21S
0.058+0.058
0.5+0.5
8
8
18
3/4 (19.05)
MCA: Minimum Circuit Ampacity (A)
MOP: Maximum Overcurrent Protective Device (A)
RLA: Rated Load Ampacity (A)
LRA: Locked Rotor Ampacity (A)
FLA: Full Load Ampacity (A)
Содержание YVAHP036B21S
Страница 2: ......
Страница 10: ......
Страница 48: ...OUTDOOR UNITS 2 30 TC 16001 rev 5 ...
Страница 50: ...OUTDOOR UNITS 2 32 TC 16001 rev 5 ...
Страница 66: ......
Страница 94: ... 2016 Johnson Controls Inc TC 16001 rev 5 Code No LIT 12012260 Revised January 2019 ...