![Johnson Controls YORK YLCA 12 Скачать руководство пользователя страница 8](http://html1.mh-extra.com/html/johnson-controls/york-ylca-12/york-ylca-12_installation-instructions-manual_2024752008.webp)
8
Data and dimensions are subject to change without prior notice.
MAGNETOTHERMAL
HEATER PROTECTION
(Q1)
POWER SUPPLY
CONNECTING
BOX
HEATER POWER SUPPLY
CABLE (NOT INCLUDED
WITH THE ACCESSORY)
1 2 3 N1 N2 N3
HEATER CONNECTING
CABLE TO CONTROL
PANEL (INCLUDED WITH
THE (ACCESSORY)
WIRING OF THE
HEATER
(See wiring diagram of the unit)
1
13
3 5
2
14
4 6
A1
A2
(K2)
K 2 N2
HEATER
(AH)
MAGNETOTHERMAL HEATER
CONNECTING PROTECTION
(Q1)
230M
400T
CONNECTING BOX
HEATER
CONTACT
1
13
3 5
2
14
4 6
A1
A2
(K2)
K 2 N2
HEATER
(AH)
HEATER
CONTACT
GB
HEATER
CABLE mm
2
Cu
Q1 (A)
2 kW/230M
2.5
15
3 kW/230M
2.5
15
3 kW/400T
1.5
6
4.5 kW/400T
1.5
8
6 kW/400T
2.5
15
Содержание YORK YLCA 12