The following fill procedure applies ONLY to HYP0490, HYP0612, HYP0774, HYP1100 and HYP1278/

HYP1300 model drives.

WARNING: Coolants may foam up when cycled through the system or when the pumps are shut 

off and the coolants tend to rise. Do not fill reservoir to top while unit is running or it may overflow 

when pumps are shut off. If foaming is evident while filling with the inhibited solution, repeat the 

FLUSHING PROCESS (ALL HYP MODEL DRIVES)

 and repeat as needed until no foaming is 

present. Refer to previous diagrams for GHT locations on each drive size.

1. 

Confirm that the heat exchanger drain valve and both of the output inductor drain valves are closed.

2.  Remove the cap from the coolant reservoir.
3.  Fill the coolant loop at the coolant reservoir. Pour the Inhibitor or distilled water into the reservoir slowly to 

minimize the foaming that may take place when filling with Inhibitor.

4.  Apply power to the chiller.
5.  Start pumps using the OptiView panel.

a. 

Press:

 Home > VSD > VSD Details > Manual Cooling > Enable.

6.  Allow pumps to run for 15 seconds.
7.  Disable the pumps.

a. 

Press:

 Home > VSD > VSD Details > Manual Cooling > Disable.

8. 

Check the fill pipe and add more inhibitor if needed to bring the level back to the within 1 inch from the top.

9.  Start the pumps and run for 5 minutes.

10. 

Disable the pumps and check the fill pipe. Add more distilled water or inhibitor if needed to bring the level 

back to within 1 inch from the top.

11. 

Repeat steps # 5 thru # 10 as needed until there no drop in the reservoir level greater than 2” detected during 

operation of the pumps.

12.  Remove the temporary 115VAC power wiring.
13.  Remove all lockout devices.
14.  The drive is ready for operation.

Содержание YORK HYP Series

Страница 1: ...ities based on drive model Work on this equipment should only be done by properly trained personnel who are qualified to work on this type of equipment Failure to comply with this requirement could ex...

Страница 2: ...219 2 JOHNSON CONTROLS EXTERNAL PIPING COMPONENTS FOR ALL PYT MODEL DRIVES LD28554 PYT 0330 0420 with Filter LD28556 PYT 0780 with Filter LD28555 PYT 0330 0420 without Filter LD28557 PYT 0780 without...

Страница 3: ...SI0270 219 3 JOHNSON CONTROLS LD28552 PYT 1020 with Filter LD28550 PYT 1280 with Filter LD28553 PYT 1020 without Filter LD28551 PYT 1280 without Filter...

Страница 4: ...the coolant loop Please see previ ous diagrams for the Garden Hose Thread GHT locations on each drive model All fluids drained from the drive should be collected and disposed of in accordance with loc...

Страница 5: ...ution repeat the FLUSHING PROCESS ALL PYT MODEL DRIVES and repeat as needed until no foaming is present Refer to previous diagrams for GHT locations on each drive size 1 Confirm that the heat exchange...

Страница 6: ...TERNAL PIPING COMPONENTS FOR ALL HYP MODEL DRIVES LD27414 744 A VSD External Piping 774 A VSD External Piping 490 A MOD A VSD External Piping 490 A MOD B VSD External Piping 490 A MOD A VSD External P...

Страница 7: ...SI0270 219 7 JOHNSON CONTROLS LD27415 490 A Non ACM VSD Shaffner Input and Output Inductors 490 A ACM VSD CTM Input and Output Inductors 1278 1300 A VSD External Piping...

Страница 8: ...SI0270 219 8 JOHNSON CONTROLS LD27416 730A VSD Shaffner Input and Output Inductors 612 A VSD CTM Input and Output Inductors...

Страница 9: ...SI0270 219 9 JOHNSON CONTROLS LD27417 1278 1300 A CTM Output Inductor 744 A VSD Output Inductor 774 A VSD CTM Output Inductor...

Страница 10: ...led Input Inductors The following drain procedure applies ONLY to HYP0744 HYP0490 Mod A Drives and HYP0774 model drives with air cooled input inductors See page 11 for all other HYP model drives If tw...

Страница 11: ...container for disposal of the trapped liquid 5 Open the heat exchanger valve to allow coolant to drain Once coolant stops flowing close the valve 6 Attach the drain hose to the top fitting of the out...

Страница 12: ...tom fitting on the output inductor 11 Use the low volume pump to fill the coolant loop 12 Slowly fill the cooling system until coolant is within 2 inches from the top of the coolant reservoir 13 HYP07...

Страница 13: ...5 Use the low volume pump to fill the coolant loop Open the valve for the bottom fitting on the output inductor 6 Slowly fill the cooling system until coolant is within 2 inches from the top of the c...

Страница 14: ...olant loop at the coolant reservoir Pour the Inhibitor or distilled water into the reservoir slowly to minimize the foaming that may take place when filling with Inhibitor 4 Apply power to the chiller...

Отзывы: