STEP 2:  Flushing Process (All HYP Model Drives)

1.  De-energize and lockout the 3 phase power supply to the Drive using all applicable policies and the appropriate 

section of the service literature 160.78-M3 or 160.84-M3.

2.  Make the necessary electrical connections to the drive to allow operation of the coolant pumps with low volt-

age using the 115VAC procedure found in Form 160.78-M3 or Form 160.84-M3. Do not energize the drive at 

this point. 

3.  Remove coolant reservoir cap.
4.  Attach drain hose to GHT faucet valve on the bottom of the shell and tube heat exchanger.
5.  Place the other end of hose in a suitable container for disposal of the trapped liquid.
6. 

Attach drain hose to the top GHT fitting on the output inductor.

7.  Place the other end of hose in a suitable container for disposal of the trapped liquid.
8. 

Confirm that the heat exchanger drain valve and both of the output inductor drain valves are closed.

9. 

Connect a low volume pump to the bottom GHT fitting on the output inductor.

10. 

Open the valve for the bottom fitting on the output inductor.

11. 

Use the low volume pump to fill the coolant loop.

12. 

Slowly fill the cooling system until coolant is within 2 inches from the top of the coolant reservoir.

13.  HYP0744 only

a.  Insure the internal supply manifold valve(s) are open.

14. 

Close the valve for the bottom fitting on the output inductor. 

15.  Apply power to the chiller.
16.  Start pumps using the OptiView panel.

a. 

Press:

 Home > VSD > VSD Details > Manual Cooling > Enable.

17.  Allow pumps to run for only 15 seconds.
18.  Disable the pumps.

a. 

Press:

 Home > VSD > VSD Details > Manual Cooling > Disable.

19. 

Check the fill pipe and add more inhibitor if needed to bring the level back to the within 1 inch from the top.

20.  Start pumps using the OptiView panel.

a. 

Press:

 Home > VSD > VSD Details > Manual Cooling > Enable.

21.  Allow pumps to run for 5 minutes.
22.  Disable the pumps.

a. 

Press:

 Home > VSD > VSD Details > Manual Cooling > Disable.

23.  Open the heat exchanger valve to allow the distilled water to drain.
24. 

When the distilled water stops flowing close the valve.

25. 

Open the heat exchanger valve and the output inductor top fitting valve to allow the distilled water to drain.

26. 

Once the distilled water stops flowing close the valve.

27. 

Repeat steps 10 – 27 so that 3 complete flush cycles are completed.

Содержание YORK HYP Series

Страница 1: ...ities based on drive model Work on this equipment should only be done by properly trained personnel who are qualified to work on this type of equipment Failure to comply with this requirement could ex...

Страница 2: ...219 2 JOHNSON CONTROLS EXTERNAL PIPING COMPONENTS FOR ALL PYT MODEL DRIVES LD28554 PYT 0330 0420 with Filter LD28556 PYT 0780 with Filter LD28555 PYT 0330 0420 without Filter LD28557 PYT 0780 without...

Страница 3: ...SI0270 219 3 JOHNSON CONTROLS LD28552 PYT 1020 with Filter LD28550 PYT 1280 with Filter LD28553 PYT 1020 without Filter LD28551 PYT 1280 without Filter...

Страница 4: ...the coolant loop Please see previ ous diagrams for the Garden Hose Thread GHT locations on each drive model All fluids drained from the drive should be collected and disposed of in accordance with loc...

Страница 5: ...ution repeat the FLUSHING PROCESS ALL PYT MODEL DRIVES and repeat as needed until no foaming is present Refer to previous diagrams for GHT locations on each drive size 1 Confirm that the heat exchange...

Страница 6: ...TERNAL PIPING COMPONENTS FOR ALL HYP MODEL DRIVES LD27414 744 A VSD External Piping 774 A VSD External Piping 490 A MOD A VSD External Piping 490 A MOD B VSD External Piping 490 A MOD A VSD External P...

Страница 7: ...SI0270 219 7 JOHNSON CONTROLS LD27415 490 A Non ACM VSD Shaffner Input and Output Inductors 490 A ACM VSD CTM Input and Output Inductors 1278 1300 A VSD External Piping...

Страница 8: ...SI0270 219 8 JOHNSON CONTROLS LD27416 730A VSD Shaffner Input and Output Inductors 612 A VSD CTM Input and Output Inductors...

Страница 9: ...SI0270 219 9 JOHNSON CONTROLS LD27417 1278 1300 A CTM Output Inductor 744 A VSD Output Inductor 774 A VSD CTM Output Inductor...

Страница 10: ...led Input Inductors The following drain procedure applies ONLY to HYP0744 HYP0490 Mod A Drives and HYP0774 model drives with air cooled input inductors See page 11 for all other HYP model drives If tw...

Страница 11: ...container for disposal of the trapped liquid 5 Open the heat exchanger valve to allow coolant to drain Once coolant stops flowing close the valve 6 Attach the drain hose to the top fitting of the out...

Страница 12: ...tom fitting on the output inductor 11 Use the low volume pump to fill the coolant loop 12 Slowly fill the cooling system until coolant is within 2 inches from the top of the coolant reservoir 13 HYP07...

Страница 13: ...5 Use the low volume pump to fill the coolant loop Open the valve for the bottom fitting on the output inductor 6 Slowly fill the cooling system until coolant is within 2 inches from the top of the c...

Страница 14: ...olant loop at the coolant reservoir Pour the Inhibitor or distilled water into the reservoir slowly to minimize the foaming that may take place when filling with Inhibitor 4 Apply power to the chiller...

Отзывы: