Functions and Control
24
Domestic Air Conditioner
After the compressor is started for 5 seconds, the outdoor fan is started at the medium speed at
first, after 30 seconds it begins to control the airflow speed according to the temperature
conditions of the outdoor environment.
Remarks: Ta:The temperature of the outdoor air; Te: The temperature of the outdoor coil.
The temperature of the outdoor
air
Ta
Airflow speed
Ta
22
Low
19
Ta<22
Keeping the speed
16
Ta<22
Medium
14
Ta<16
Keeping the speed
Ta<14
High
Remarks: Ta:The temperature of the outdoor air; Te: The temperature of the outdoor coil.
5.2.3
The control of the outdoor electronic expansion valve
When starting the compressor: the opening size of the valve must be guaranteed to have entered
into the standard opening size, and then the compressor can be started.
When refrigeration is in vain (the machine is shut down or is in the state of retrograde operation),
the opening size of the expansion valve of the indoor unit is 5 steps;
When heating is in vain, the opening size of the expansion valve of the indoor unit is 55 steps;
When the outdoor unit is shut down, the valve is opened completely for 2 minutes, and then
begin initialization.
The scope of refrigerationg valve 90-----480 steps
The scope of heating valve 80-----480 steps
The valves are adjusted according to the degree of superheat
SHa
SHa.
5.2.4
Four way control
For the details of Defrost four-way valve control, see the Defrost process.
Four way working in other ways:
Under the mode of heating, open the four-way valve, when the compressor is not started or
changed to non-heating mode, make sure the compressor is stoped for 2 minutes, and then
close the four-way valve.
The temperature of the
outdoor air
Ta
The temperature of the outdoor
coil
Te
Airflow speed
Ta
30
High
26
Ta<30
Keeping the speed
24
Ta<26
Medium
23
Ta<24
Keeping the speed
5
Ta<23
Low
Ta<5
15
Te
Low
15
>Te
Stop
5.2.2.1 The outdoor fan control when refrigerating or dehumidifying
5.2.2.2 The outdoor fan control when heating
Содержание York FREE MATCH EK-Series
Страница 15: ...Connector Wiring Diagram 13 Domestic Air Conditioner PCB 2 CN1 CN5 CN6 CN7 CN10 CN11 CN8 CN9 CN2 CN3 CN4 ...
Страница 70: ...WARNING CAUTION 68 Installation ...
Страница 76: ...74 Installation ...
Страница 79: ...Pressurize for over 3 minutes at 4 2MPa After above 77 Installation ...
Страница 83: ...81 Domestic air conditioner Removal of procedure 9 ...
Страница 86: ...84 Domestic air conditioner Removal of procedure three 3 HOOKS ...
Страница 87: ...85 Domestic air conditioner Removal of procedure horizontal flap flap flap flap flap ...
Страница 89: ...87 Domestic air conditioner Removal of procedure ...
Страница 90: ...Domestic air conditioner Removal of procedure 3 88 ...
Страница 91: ...Domestic air conditioner Removal of procedure 89 ...
Страница 92: ...Domestic air conditioner Removal of procedure 90 ...
Страница 93: ...Domestic air conditioner Removal of procedure Outdoor Unit Removal of Outdoor Panel 91 ...
Страница 94: ...92 Domestic air conditioner Removal of procedure Loosen the top panel screws 1 2 Lift the top panel ...
Страница 95: ...93 Domestic air conditione Removal of procedure Loosen the csrews and pull the panel ...
Страница 97: ...95 Domestic air conditioner Removal of procedure ...
Страница 98: ...96 Domestic air conditioner Removal of procedure ...
Страница 99: ...97 Domestic air conditioner Removal of procedure 2 Loosen the fixing screws and remove the motor ...
Страница 100: ...98 Domestic air conditioner Removal of procedure ...
Страница 101: ...99 Domestic air conditioner Removal of procedure and remove the reactor Loosen the screw ...
Страница 102: ...100 Domestic air conditioner Removal of procedure Loosen the marked screws and pull out the backgurd ...
Страница 110: ...The end ...