VA-8122 Proportional Valve Actuator Product/Technical Bulletin

 

S

pecifications 

Product 

VA-8122 Proportional Valve Actuator 

Power Requirements 

24 VAC at 50/60 Hz, 5.0 VA supply minimum, Class 2 

Input Signal 

Jumper Selectable:  0 (2) to 10 VDC, 0 (4) to 20 VDC, 6 (12) to 9 (18) VDC, 0 (4) to 20 mA 
Factory Setting: 

0 to 10 VDC, Drive Down (DD) action on signal increase 

Input Impedance 

Voltage Input: 

0 to 10 VDC, 150,000 ohms and 0 to 20 VDC, 450,000 ohms 

Current Input: 

0 to 20 mA, 500 ohms 

5/16 in. Stroke Time 

50 Hz: Approximately 108 seconds nominal 
60 Hz: Approximately 90 seconds nominal 

Force 

Shutoff and Breakaway: 

22 lb (98 N) minimum 

Cycles 

60,000 full cycles; 1,500,000 repositions 

Enclosure 

NEMA 1, IP20 

Audible Noise Rating 

35 dBA maximum at 3.28 ft (1 m) 

Ambient Operating 

Conditions 

35 to 135°F (2 to 57°C);  
85°F (30°C) maximum dew point at 90% RH, non-condensing 

Ambient Storage 

Conditions 

-40 to 150°F (-40 to 65°C);  
85°F (30°C) maximum dew point at 90% RH, non-condensing 

Valve Media Temperature 

Water:  195°F (90°C) maximum 
Steam:  Actuator is not rated for this application. 

Dimensions (H x W x D) 

4.5 x 5.0 x 2.5 in. (114 x 127 x 64 mm) 

Shipping Weight 

1.6 lb (0.74 kg) 

Agency Compliance 

UL 873 Recognized, File E27734, Guide XAPX2 
CSA C22.2 No. 139 Certified, File LR85083, Class 3221 02 

The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these 
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication 
or misuse of its products. 

 

European Single Point of Contact: 

NA/SA Single Point of Contact: 

APAC Single Point of Contact: 

JOHNSON CONTROLS 
WESTENDHOF 3 
45143 ESSEN 
GERMANY 

JOHNSON CONTROLS 
507 E MICHIGAN ST 
MILWAUKEE WI 53202 
USA 

JOHNSON CONTROLS 
C/O CONTROLS PRODUCT MANAGEMENT 
NO. 22 BLOCK D NEW DISTRICT 
WUXI JIANGSU PROVINCE 214142 
CHINA 

 

Building Efficiency

 

507 E. Michigan Street, Milwaukee, WI  53202 

 

 

Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.  

All other marks herein are the marks of their respective owners. © 2016 Johnson Controls, Inc.

 

Содержание VA-8122

Страница 1: ...r retrofits of VT Series Terminal Unit Valves with slotted stems and VB 5x39 Series Flare Valves Refer to the appropriate valve literature for more information Figure 1 VA 8122 1 Valve Actuator Features and Benefits q AUTOCAL Pushbutton Allows the actuator to define the control input range proportionally over the stroke q Simplified Setup and Adjustment Procedures Reduces installation costs q Sele...

Страница 2: ...late Drive Screw Jumpers W1 W5 AUTOCAL Pushbutton Spade Terminals 3 LED Circuit Board 24 COM VDC mA Stem Retainer Position Indicator Manual Adjustment Knob Figure 2 VA 8122 Components IMPORTANT There are no internal mechanical stops in the actuator Never drive the actuator unless it is installed on the proper valve body or the actuator may be damaged Dimensions See Figure 3 for actuator dimensions...

Страница 3: ...t adaptor nut making sure the yoke is flush with the surface of the nut Note If the valve stem is touching the coupler and preventing a flush contact use the manual adjustment knob shown in Figure 4 to reposition the coupler 5 Secure the actuator to the valve bonnet by tightening the hex head machine screw provided 6 Place the stem retainer and coupling clip over the valve stem so the lower shorte...

Страница 4: ...he input signal is determined by the position of Jumpers W3 W4 and W5 See Table 1 and Table 2 Table 1 Jumper Settings W5 W4 W3 W2 W1 Shown in Factory Default Settings DD Drive Down Drive Up DU 6 9 VDC Current Input mA VDC Voltage Input The 6 9 VDC position of Jumper W5 overrides Jumper W3 0 10 VDC 0 20 mA 2 10 VDC 4 20 mA 0 10 VDC 0 20 VDC Table 2 Available Input Control Signal vs Input Jumpers Co...

Страница 5: ...llation of the actuator This mode allows the actuator to define the control input range proportionally over the valve stroke stored in nonvolatile memory retains data when power is lost or removed Note Once calibrated it is not necessary to recalibrate if a jumper is changed To activate the AUTOCAL mode depress the AUTOCAL pushbutton for approximately 3 seconds until the LED turns off The actuator...

Страница 6: ...osition Terminal Block Controller Input Signal 24 VAC Supply VDC mA 24 VAC COM Common Figure 8 VA 8122 Wiring IMPORTANT Install all the quick connect terminals in the same direction to each other to prevent the terminals from shorting See Figure 9 Figure 9 Orientation of Terminals Input lines to the actuator must be wired correctly for the valve to move in the proper direction Refer to the specifi...

Страница 7: ...00 Series bronze valves The VA 8122 is also available for retrofitting VG7000 Series bronze valves VT Series Terminal Unit Valves with slotted stems and VB 5x39 Series Flare Valves Refer to the AV 8122 Series Proportional Control Actuated Valve Product Technical Bulletin FAN 977 or 1628 3 and the VG7000 Series Bronze Valves ANSI Class 250 PN16 Body Size 1 2 through 2 inch DN15 to DN50 Product Tech...

Страница 8: ... Valve Media Temperature Water 195 F 90 C maximum Steam Actuator is not rated for this application Dimensions H x W x D 4 5 x 5 0 x 2 5 in 114 x 127 x 64 mm Shipping Weight 1 6 lb 0 74 kg Agency Compliance UL 873 Recognized File E27734 Guide XAPX2 CSA C22 2 No 139 Certified File LR85083 Class 3221 02 The performance specifications are nominal and conform to acceptable industry standards For applic...

Отзывы: