Section 6: Programming
System Options
[013] System Option 1
1 – NC Loop/EOL
ON: All zones are wired as normally closed circuits with returns connected to a COM terminal. The end-of-line resistor is not required.
An alarm is generated when the circuit is opened.
OFF: All zones must be wired with an end-of-line resistor configuration, determined by option 2 below.
Note:
The valid EOL value is 5600 Ohms (5.6KΩ).
2 – DEOL/SEOL
ON: All zones use Double-End-of-Line resistors, except Standard Fire, Delayed Fire, Auto-Verified Fire, Co and Supervisory zone
types. DEOL resistors enable detection of zone faults and tampers. The tamper resistor (5.6KΩ) is placed in parallel across the alarm
activating device, and the single EOL resistor (5.6KΩ) is placed between the alarm and tamper contacts.
This allows detection of zone faults (shorted zone), tampers (open zone), alarms (11.2KΩ), and restored zones (5.6KΩ).
If the zone is disarmed and placed in the tamper or fault state, trouble beeps sound on all system keypads until a key is pressed on
each partition. A zone tamper is sent to the monitoring station if programmed. If the zone is armed and a tamper is activated, the
tamper alarm and zone alarm are logged and transmitted.
OFF: All zones must have a 5.6KΩ resistor. If the zone is shorted or open, it is in the tripped state. If the zone is open and programmed
as a fire zone, it is in the trouble state. The EOL and DEOL zone attributes override this system option.
Note:
Zone Faults (Supervisories) on wireless zones do not cause an audible alarm while armed.
3 – Show All Troubles When Armed
ON: The Trouble LED illuminates when troubles are present on the system in both the armed and disarmed state.
OFF: The Trouble LED illuminates and trouble beeps activate for all troubles while disarmed, but only for Fire Troubles while armed.
4 – Tamper/Faults Do Not Show As Open
ON: The zone does not show open if the zone is in the tamper or fault states. Only the Trouble LED illuminates.
OFF: The respective zone LED shows open if the zone is in the tamper or fault states. The Trouble LED also illuminates.
5 – Auto-Arm Schedule in [*][6]
ON: The auto-arm schedules ([151] - [158]) are accessible via [*][6] as well as Installer Programming.
OFF: The auto-arm schedules ([151] - [158]) are only accessible to installers via Installer Programming.
Note:
This toggle controls access for all 32 partitions.
6 – Audible Exit Fault
ON: If a delay type zone is violated after the exit delay has expired, an entry delay warning is sounded through the keypad and siren
indicating that an improper exit was made. If the alarm system is disarmed within the entry delay period no signal is sent.
OFF: The entry delay warning is sounded only through the keypad.
7 – Event Buffer Follows Swinger Shutdown
ON: Once an event reaches its swinger shutdown limit programmed in
"[377] Communication Variables" on page 131
, it will no longer
log events to the event buffer until the swinger shutdown is reset. This avoids filling the event buffer with false events.
OFF: The event buffer continues to log events to the buffer even after the event has gone into swinger shutdown.
8 – Temporal Three Fire Signaling
ON: All fire bells sound in the temporal three pattern. Cadence is as follows: (500ms ON, 500ms OFF, 500ms ON, 500ms OFF, 500ms
ON, 1.5 sec. OFF).
OFF: All fire bells will sound with the standard 1 second on/1 second off fire bell cadence.
Note:
Must be on for UL/ULC installations.
[014] System Option 2
1 – Bell Squawk
ON: The siren emits a single squawk when armed in any manner, including Auto-arm, and a double squawk when disarmed.
When the system is disarmed, the siren emits a series of three squawk pairs to indicate alarms in memory.
OFF: The siren does not squawk when arming or disarming.
NA
Note:
For UL/ULC, must be enabled if wireless keys are used with the alarm system.
- 110 -