compliance with this document, as well 

as with the applicable standards of any 

authorities having jurisdiction. Contact 

the installing contractor or product 

manufacturer with any questions.
Automatic sprinkler systems are rec-

ommended to be inspected, tested, 

and maintained by a qualified Inspec-

tion Service in accordance with local 

requirements and/or national codes.

Maintenance of the Nitrogen 

Generator

The nitrogen generator cabinet con-

tains three separate cartridge filters. 

It is recommended that each of the 

filter cartridges be replaced as part of 

an annual preventative maintenance 

program. In some environments it may 

be necessary to replace filters more 

frequently. When maintained properly 

the nitrogen separation membrane will 

provide up to 20 years of service life.

Filter Replacement Procedure

With reference to Figure 4, perform 

the following steps when replacing the 

cartridge filters located in the Filter 

Housing.

Step 1.

 Turn the power supply to the 

unit off.

Step 2.

 Close the Inlet and Outlet Ball 

Valves, and open the Bypass Ball Valve.

Step 3.

 Depressurize the nitrogen gen-

erator internal inlet piping by slowly 

opening the Depressurization Ball 

Valve in the cabinet to the left of the 

filter housing.

Step 4.

 Remove the filter housing by 

pulling down on the blue housing lock 

and turning the filter housing count-

er-clock wise.

Step 5.

 Once the filter housing has 

been removed, the filter cartridge 

inside is removed by first unscrewing 

the black retaining disc at the base of 

the cartridge and then pulling down on 

the cartridge. Discard the old filter car-

tridge and replace it with the appropri-

ately marked filter cartridge from the 

filter replacement kit by pushing up 

so that it fits snugly onto the receiving 

cylinder in the upper part of the filter 

housing. Hand tighten the black retain-

ing disc back onto the central metal 

threaded rod.

Step 6.

 Replace the filter housing by 

pushing up into position and turning the 

housing clockwise until blue housing 

lock locks into place.

Step 7.

 Repeat Step 4 through Step 6 

for each additional filter.

Note:

 Filters 2 & 3 do not have a black retain-

ing disc, filters screw directly into housing.

Step 8.

 Remove the Water Separator 

housing by pulling down on the blue 

housing lock and turning the housing 

counter-clockwise. Inspect the Water 

Separator and clean as necessary.

Step 9.

 Replace the Water Separator 

housing by pushing up into position 

and turning the housing clockwise until 

blue housing lock locks into place.

FIGURE 3C 

MODEL TNGC-1150/1500/2000/3000 AIR COMPRESSOR 

EMEA AND APAC POWER SUPPLY CONNECTIONS

Содержание tyco NG-1 1150

Страница 1: ...on on TYCO Dry Air Vent TAV D and to TFP1263 for more information on TYCO SMART Air Vent TSV D System Assembly The TYCO Nitrogen Generator unit includes the following components Steel enclosure cabinet with mem brane type nitrogen generator no nitrogen gas storage and manual bypass Power supply 120 VAC Single phase 60Hz 230 VAC Single phase 50Hz Single point nitrogen air discharge 1 2 in NPT Hour ...

Страница 2: ...4605 1150 4353 2300 8706 NG 1 1500 24 3 688 11000 41640 1440 5451 2880 10902 NG 1 2000 24 688 18500 70030 2025 7666 4050 15331 NG 1 3000 35 992 22500 85172 2900 10978 5800 21955 Notes a Capacity based on NFPA 13 30 minute fill requirement of largest single system Model Number Cabinet Without Bypass Cabinet With Bypass Weight Lbs kg Width Inches mm Height Inches mm Depth Inches mm Width Inches mm H...

Страница 3: ... N2 Purity at Discharge 98 or greater maximum of 2 0 oxygen N2 Pressure at Discharge Minimum of 15 psig 1 bar Max of feed air pressure minus 15 psig 1 bar N2 Water Dew Point Typically less than 70 F 57 C Note When connecting a TYCO Stand Alone Nitrogen Generator to an existing dry pipe preaction fire sprinkler system the existing fire sprinkler system s must be limited to a maximum leak rate of le...

Страница 4: ... The nitrogen air discharge plumb ing from the nitrogen generator is to be connected directly to the sprinkler system valve trim using a minimum of 1 2 in to 1 in black steel galva nized steel or copper piping The size of the nitrogen air supply line is to be based on the length of pipe between the nitrogen generator and the fire sprinkler systems along with the total volume of the fire sprinkler ...

Страница 5: ...GENERATOR RUNNING OUTPUT BYPASS MODE ALARM OUTPUT LEAK MONITORING OUTPUT POWER ON OFF OUTPUT NITROGEN SUPPLY LINE PRESSURE OUTPUT L1 N G PRESSURE SWITCH INCOMING POWER FUSE BOX BUILDING MANAGEMENT SYSTEM MONITORING POINTS POWER SUPPLY POWER DISTRIBUTION L1 G N N N G FIGURE 2A MODEL NG 1 1150 NG 1 1500 NG 1 2000 AND NG 1 3000 STAND ALONE NITROGEN GENERATOR AMERICAS SYSTEM SIGNAL MONITOR AND POWER S...

Страница 6: ... drain connection be plumbed to a floor drain or building exterior When plumbing to a drain is not feasible an evaporative collection chamber can be used Note Ensure that the receiver tank auto drain is connected to an un switched power source 120 VAC for Americas 230 VAC for EMEA and APAC Note The Low Oil Level Sensor on the air compressor automatically shuts down air compressor until the proper ...

Страница 7: ...rnal inlet piping by slowly opening the Depressurization Ball Valve in the cabinet to the left of the filter housing Step 4 Remove the filter housing by pulling down on the blue housing lock and turning the filter housing count er clock wise Step 5 Once the filter housing has been removed the filter cartridge inside is removed by first unscrewing the black retaining disc at the base of the cartrid...

Страница 8: ...he Bypass Ball Valve Step 13 Open the Inlet and Outlet Ball Valves Compressors Maintenance of the Compressor For compressor maintenance please refer to the manufacturer s recom mended maintenance plan in the owner s manual for the compressor Limited Warranty For warranty terms and conditions visit www tyco fire com Ordering Procedure TYCO will supply a list of required part numbers to order throug...

Отзывы: