background image

TFP1253

Page 3 of 8

work in conjunction with the NG-1 1150, 

NG-1 1500, NG-1 2000, and NG-1 3000 

Nitrogen Generators in a typical dry or 

preaction fire sprinkler system. It is 

also  a plant nitrogen source for wet 

pipe fire sprinkler systems used with 

the NG-1 1500, NG-1 2000, and NG-1 

3000 Nitrogen Generators.
The NG1 Air Compressors consists of 

the following features:

TNGC-1150

•  5 hp
•  Used with Model NG-1 1150
•  Air receiver tank:

 

Americas: 60 gal (227 L); vertical

 

EMEA, APAC: 71 gal (270 L); 

horizontal

TNGC-1500/2000

•  7.5 hp 
•  Used with Model NG-1 1500 or NG-1 

2000

•  Air Receiver Tank:

 

Americas: 80 gal (303 L); with 

after cooler; vertical

 

EMEA, APAC: 71 gal (270 L); 

horizontal

TNGC-3000

•   10 hp
•  Used with Model NG-1 3000
•  Air Receiver Tank

 

Americas: 120 gal (488 L); with 

after cooler; vertical

 

EMEA, APAC: 71 gal (270 L); 

horizontal

NOTICE

The TYCO Stand-Alone Nitrogen Gen-

erators described herein must be 

installed and maintained in compli-

ance with this document, in addition to 

the standards of any other authorities 

having jurisdiction. Failure to do so may 

impair the performance of the related 

devices.
The owner is responsible for main-

taining their fire protection system 

and devices in proper operating con-

dition. Contact the installing contrac-

tor or product manufacturer with any 

questions.

Technical 

Data

NG-1 Nitrogen Generators

Approvals

FM Approved 

Compliance with CE Pressure Equipment 

UL508A Listed Industrial Control Panel

Cabinet Dimensions

See Table A

Weight

See Table A

Operating Performance

See Table B

Temperature Range

40

°

F (5

°

C) to 105

°

F (40

°

C)

Power Supply

120 VAC/Single 1 phase/60Hz (dedicated 

circuit) 

230 VAC/Single phase/50Hz (dedicated 

circuit)

Power Consumption

2 amps

Gas Connection

Air Inlet - 1/2 in. NPT Female 

Nitrogen Outlet - 1/2 in. NPT Female

Drain Connection

1/4 in. NPT Connection

Nitrogen Quality

N

2

 Purity at Discharge: 98% or greater 

(maximum of 2.0% oxygen)
N

Pressure at Discharge: Minimum of 

15 psig (1 bar); Max of feed air pressure 

minus 15 psig (1 bar)
N

Water Dew Point: Typically less than 

-70

°

F (-57

°

C)

Note

: When connecting a TYCO Stand-

Alone Nitrogen Generator to an existing 

dry pipe/preaction fire sprinkler system, 

the existing fire sprinkler system(s) must be 

limited to a maximum leak rate of less than 

6 psig (0.4 bar) within a 24 hour period, per 

system.

NG1 Compressors

Air Compressor Dimensions

See Table C

Weight

See Table C

Operating Performance

See Table B

Temperature Range

40

°

F (5

°

C) to 105

°

F (40

°

C)

Power Supply

Americas:

•  460 VAC/Three phase/60 Hz (Standard)
•  208 VAC/Three phase/60 Hz (Optional)

EMEA and APAC:

•  400 VAC/Single phase/50Hz (Standard)

Note: 

Other configurations are available. 

Contact Johnson Controls Technical Ser-

vices for more information.

Auto Drain

•  120 VAC/Single phase/60Hz
•  220 VAC/1 phase/50Hz

Note:

 The auto drain can be connected 

to the Nitrogen Generator cabinet power 

supply.

Power Consumption

Americas:

TNGC-1150 

7.6 Amps @ 460 VAC

 

 

17.5 Amps @ 208 VAC

TNGC-1500/2000 

11 Amps @ 460 VAC

 

 

25.3 Amps @ 208 VAC

TNGC-3000 

14 Amps @ 460 VAC

 

32.2 Amps @ 208 VAC

EMEA and APAC:

TNGC-1150 

13 Amps @ 400 VAC

TNGC-1500/2000 

17 Amps @ 400 VAC

TNGC-3000 

22 Amps @ 400 VAC

Air Connection

Americas:

TNGC-1150 

1/2 in. NPT Female

TNGC-1500/2000 

1/2 in. NPT Female

TNGC-3000 

1 in. Female

EMEA and APAC:

TNGC-1150 

1/2 in. BSPP Female

TNGC-1500/2000 

1/2 in. BSPP Female

TNGC-3000 

1/2 in. BSPP Female

Model 

Number

Width 

Inches (mm)

Length 

Inches (mm)

Height 

Inches (mm)

Weight 

Lbs (kg)

Americas

RoW

Americas

RoW

Americas

RoW

Americas

RoW

TNGC-1150

20 (508)

21 (533)

32 (813)

60.6 (1540)

70 (1778)

43.7 (1111)

435 (197)

374.9 (170)

TNGC-1500/2000

23.6 (599)

23.3 (592)

38.1 (968)

60.6 (1540)

70.1 (1781)

47.2 (1200)

573 (260)

416.7 (189)

TNGC-3000

43.2(1097)

23.9 (606)

30 (762)

60.6 (1540)

76.6 (1946)

47.2 (1200)

800 (362)

443.2 (201)

NOTES

•  RoW = Rest of World - the EMEA and APAC regions.

TABLE C 

MODEL NG1 COMPRESSOR DIMENSIONS AND WEIGHT -  

AMERICAS AND REST OF WORLD REGIONS

Содержание tyco NG-1 1150

Страница 1: ...on on TYCO Dry Air Vent TAV D and to TFP1263 for more information on TYCO SMART Air Vent TSV D System Assembly The TYCO Nitrogen Generator unit includes the following components Steel enclosure cabinet with mem brane type nitrogen generator no nitrogen gas storage and manual bypass Power supply 120 VAC Single phase 60Hz 230 VAC Single phase 50Hz Single point nitrogen air discharge 1 2 in NPT Hour ...

Страница 2: ...4605 1150 4353 2300 8706 NG 1 1500 24 3 688 11000 41640 1440 5451 2880 10902 NG 1 2000 24 688 18500 70030 2025 7666 4050 15331 NG 1 3000 35 992 22500 85172 2900 10978 5800 21955 Notes a Capacity based on NFPA 13 30 minute fill requirement of largest single system Model Number Cabinet Without Bypass Cabinet With Bypass Weight Lbs kg Width Inches mm Height Inches mm Depth Inches mm Width Inches mm H...

Страница 3: ... N2 Purity at Discharge 98 or greater maximum of 2 0 oxygen N2 Pressure at Discharge Minimum of 15 psig 1 bar Max of feed air pressure minus 15 psig 1 bar N2 Water Dew Point Typically less than 70 F 57 C Note When connecting a TYCO Stand Alone Nitrogen Generator to an existing dry pipe preaction fire sprinkler system the existing fire sprinkler system s must be limited to a maximum leak rate of le...

Страница 4: ... The nitrogen air discharge plumb ing from the nitrogen generator is to be connected directly to the sprinkler system valve trim using a minimum of 1 2 in to 1 in black steel galva nized steel or copper piping The size of the nitrogen air supply line is to be based on the length of pipe between the nitrogen generator and the fire sprinkler systems along with the total volume of the fire sprinkler ...

Страница 5: ...GENERATOR RUNNING OUTPUT BYPASS MODE ALARM OUTPUT LEAK MONITORING OUTPUT POWER ON OFF OUTPUT NITROGEN SUPPLY LINE PRESSURE OUTPUT L1 N G PRESSURE SWITCH INCOMING POWER FUSE BOX BUILDING MANAGEMENT SYSTEM MONITORING POINTS POWER SUPPLY POWER DISTRIBUTION L1 G N N N G FIGURE 2A MODEL NG 1 1150 NG 1 1500 NG 1 2000 AND NG 1 3000 STAND ALONE NITROGEN GENERATOR AMERICAS SYSTEM SIGNAL MONITOR AND POWER S...

Страница 6: ... drain connection be plumbed to a floor drain or building exterior When plumbing to a drain is not feasible an evaporative collection chamber can be used Note Ensure that the receiver tank auto drain is connected to an un switched power source 120 VAC for Americas 230 VAC for EMEA and APAC Note The Low Oil Level Sensor on the air compressor automatically shuts down air compressor until the proper ...

Страница 7: ...rnal inlet piping by slowly opening the Depressurization Ball Valve in the cabinet to the left of the filter housing Step 4 Remove the filter housing by pulling down on the blue housing lock and turning the filter housing count er clock wise Step 5 Once the filter housing has been removed the filter cartridge inside is removed by first unscrewing the black retaining disc at the base of the cartrid...

Страница 8: ...he Bypass Ball Valve Step 13 Open the Inlet and Outlet Ball Valves Compressors Maintenance of the Compressor For compressor maintenance please refer to the manufacturer s recom mended maintenance plan in the owner s manual for the compressor Limited Warranty For warranty terms and conditions visit www tyco fire com Ordering Procedure TYCO will supply a list of required part numbers to order throug...

Отзывы: