background image

TFP322

Page 3 of 4

Installation

TYCO Model ESFR-17 Early Suppres-

sion, Fast Response 16.8K Pendent 

Sprinklers must be installed in accor-

dance with this section.

General Instructions

Do not install any bulb type sprinklers 

if the bulb is cracked or there is a loss 

of liquid from the bulb. With the sprin-

kler held horizontally, a small air bubble 

should be present. The diameter of the 

air bubble is approximately 1/16 inch 

(1,6 mm) for both 155°F (68°C) and 

200°F (93°C) temperature ratings.
A leak-tight 3/4 inch NPT sprinkler joint 

should be obtained by applying a min-

imum-to-maximum torque of 10 to 20 

ft.-lbs. (13,4 to 26,8 Nm), or by hand-

tightening and applying an additional 

1-1/4 to 1-1/2 revolutions of the wrench. 

Higher levels of torque can distort the 

sprinkler inlet with consequent leakage 

or impairment of the sprinkler.

WARNING

Orange protector must NOT be 

removed until sprinkler is to be placed 

in service. The W-Type 35 sprinkler 

wrench MUST be used for proper 

installation of the sprinkler. Failure to 

do so may result in equipment damage 

or failure.

Note:

 Install the Model ESFR-17 

Pendent Sprinkler only in the pendent 

position (See Figure 2).

Step 1.

 With pipe-thread sealant 

applied, hand-tighten the sprinkler into 

the sprinkler fitting. Do not apply pres-

sure to the bulb assembly, and handle 

the Model ESFR-17 Sprinkler only by 

the Frame arms.

Step 2.

 Wrench-tighten the Model 

ESFR-17 Sprinkler using only the 

W-Type 35 Sprinkler Wrench (See 

Figure 2), and by fully engaging 

(seating) the wrench on the sprinkler 

wrench flats (See Figure 1).

Step 3.

 After installation, inspect the 

bulb of each Model ESFR-17 Sprinkler 

for damage. In particular, verify that the 

bulb is not cracked. Replace damaged 

sprinklers.

Storage Type

NFPA

FM Global

Open Frame (i.e., no solid shelves) 

Single, Double, Multiple-Row, or Portable Rack Storage of 

Class I-IV and Group A or B Plastics

Refer to NFPA 13 

Chapters 16 and 17

Refer to FM 2-0 and 8-9

Solid Pile or Palletized Storage of 

Class I-IV and Group A or B Plastics

Refer to NFPA 13 

Chapters 14 and 15

Refer to FM 2-0 and 8-9

Idle Pallet Storage

Refer to NFPA 13 

Chapter 12

Refer to FM 2-0, 8-9, and 8-24

Rubber Tire Storage

Refer to NFPA 13 

Chapter 18

Refer to FM 2-0 and 8-3

Roll Paper Storage 

(Refer to the Standard)

Refer to NFPA 13 

Chapter 19

Refer to FM 8-21

Flammable/Ignitable Liquid Storage 

(Refer to the Standard)

Refer to NFPA 30

Refer to FM 7-29

Aerosol Storage 

(Refer to the Standard)

Refer to NFPA 30B

Refer to FM 7-31

Automotive Components in Portable Racks 

(Control mode only; refer to the Standard)

N/A

N/A

N/A – Not Applicable

WRENCH

RECESS

"FITTING SIDE"

TOWARD

SPRINKLER

FITTING

FIGURE 2 

W-TYPE 35 

SPRINKLER WRENCH

TABLE A 

MODEL ESFR-17 PENDENT SPRINKLER 

COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW

Отзывы: