Page 2 of 4

Design 

Criteria

The following general guidelines pro-

vided for the TYCO

 

Model ESFR-17 

Pendent Sprinklers can be used for a 

quick reference.
The National Fire Protection Associa-

tion (NFPA) or FM Global provide instal-

lation standards that must be used to 

properly design an automatic sprinkler 

system utilizing Early Suppression, Fast 

Response (ESFR) Sprinklers. Conse-

quently, the appropriate standard must 

be used for a given installation.
In all cases, the appropriate NFPA or 

FM Global installation standard must 

be referenced to ensure applicabil-

ity and to obtain complete installa-

tion guidelines. The following general 

guidelines are not intended to provide 

complete installation criteria.

System Type

Wet Pipe

Roof Construction

Unobstructed or obstructed construc-

tion, such as smooth ceiling, bar joists, 

beam and girder.
Where the depths of the solid structural 

members, such as beams and stem, 

exceed 12 in. (302 mm), install ESFR 

Sprinklers in each channel formed by 

the structural members.

Ceiling Slope

Maximum 2 in. rise for 12 in. run (16.7%)

Maximum Coverage Area

100 ft² (9,3 m²)
In some cases, the installation stan-

dards permit a greater coverage area.

Minimum Coverage Area

64 ft² (5,8 m²) per NFPA 13 and 

FM Global 2-0

Maximum Spacing

12 ft (3,7 m) for building heights up to 

30 ft (9,1 m)
10 ft (3,1 m) for building heights greater 

than 30 ft (9,1 m)

Minimum Spacing

8 ft (2,4 m)

Minimum Clearance to Commodity

36 in. (914 mm)

NFPA 13 

Deflector-to-Ceiling Distance

6 to 14 in. (152 to 356 mm)

Centerline of Thermal Sensing 

Element to Ceiling Distance

Refer to FM Global 2-0 for Storage 

Sprinklers

Operation

The glass bulb contains a fluid which 

expands when exposed to heat. When 

the rated temperature is reached, the 

fluid expands sufficiently to shatter the 

glass bulb, allowing the sprinkler to 

activate and water to flow.

**

*

*

*

**

2-3/8"

(60,3 mm)

WRENCH

FLATS

1/2"

(12,7 mm)

NOMINAL

MAKE-IN

Temperature rating is

indicated on Deflector.

Components:

- Sealing Assembly

6

- Compression Screw

3

Bulb

Button

-

4

-

5

Deflector

Frame

-

1
2 -

ISO 7-R 3/4 pipe thread

can be provided on

special request.

2

3

4

5

6

1

3/4" NPT

1-1/2"

(38,1 mm)

CENTERLINE

THERMAL

SENSING

ELEMENT

FIGURE 1 

MODEL ESFR-17 EARLY SUPPRESSION, FAST RESPONSE 

16.8K PENDENT SPRINKLER 

ASSEMBLY AND DIMENSIONS 