Model ESFR-17 

16.8 K-factor Pendent Sprinkler 

Early Suppression, Fast Response

Page 1 of 4 

APRIL 2019 

TFP322

IMPORTANT

Refer to Technical Data Sheet 

TFP2300 for warnings pertaining to 

regulatory and health information.
Always refer to Technical Data 

Sheet TFP700 for the “INSTALLER  

WARNING” that provides cautions 

with respect to handling and instal-

lation of sprinkler systems and com-

ponents. Improper handling and 

installation can permanently damage 

a sprinkler system or its compo-

nents and cause the sprinkler to fail  

to operate in a fire situation or cause  

it to operate prematurely.

Worldwide 

Contacts

www.tyco-fire.com

Sprinkler 

Identification 

Number (SIN)

TY7236

Technical 

Data

Approvals

UL and C-UL Listed 

FM Approved*

* 155°F (68°C) temperature rating only.

Maximum Working Pressure

175 psi (12,1 bar)

Pipe Thread Connections

¾ in. NPT or ISO 7-R 3/4

Discharge Coefficient

K=16.8 gpm/psi

½

 (241,9 lpm/bar

½

)

Temperature Ratings

155°F (68°C)

1

 

200°F (93°C)

2

1.  UL/C-UL Listed and FM Approved.
2.  UL/C-UL Listed only.

Finish

Natural Brass

Physical Characteristics

Frame  . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass

Deflector . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze

Compression Screw . . . . . . . . . . . . . . . . . .Brass

Button  . . . . . . . . . . . . . . . . . . . Phosphor Bronze

Bulb(3mm)  . . . . . . . . . . . . . . . . . . . . . . . . . Glass

Sealing Assembly  . .Beryllium Nickel w/TEFLON

General 

Description

TYCO Model ESFR-17 Pendent Sprin-

klers are Early Suppression, Fast 

Response (ESFR) sprinklers having a 

nominal K-factor of 16.8 (See Figure 1). 

They are suppression mode sprinklers 

that are especially advantageous as a 

means of eliminating in-rack sprinklers 

when protecting high-piled storage.
The Model ESFR-17 Pendent Sprinklers 

are available in two temperature ratings 

and Listed or Approved accordingly; 

155

°

F (68

°

C) is UL and C-UL Listed 

and FM Approval; and 200

°

F (93

°

C) is 

UL and C-UL Listing only.
Model ESFR-17 Pendent Sprinklers are 

primarily used for ceiling-only sprinkler 

protection of (but not limited to) the fol-

lowing storage applications:

•  most encapsulated or non-encap-

sulated common materials including 

cartoned, unexpanded plastics

•  cartoned, expanded plastics
•  uncartoned, unexpanded plastics
•  uncartoned, expanded plastics
•  some storage arrangements of 

rubber tires, roll paper, and aerosols

For more specific criteria, refer to Table 

A in this technical data sheet as well as 

the applicable design standard.
The Model ESFR-17 Pendent Sprin-

klers provide the system designer 

with hydraulic and sprinkler place-

ment options not presently available 

to traditional ESFR Sprinklers having 

a nominal K-factor of 14.0. In particu-

lar, Model ESFR-17 Pendent Sprinklers 

are designed to operate at substan-

tially lower-end head pressures, as 

compared to ESFR Sprinklers having 

a nominal K-factor of 14.0. This feature 

offers flexibility when sizing system 

piping, as well as possibly reducing or 

eliminating the need for a system fire 

pump.
Applications for the ESFR-17 Pendent 

Sprinklers are expanding beyond cur-

rently recognized installation stan-

dards. For information on research fire 

tests (with flammable liquids and aero-

sols, for example) that may be accept-

able to an authority having jurisdiction, 

contact Technical Services.

WARNING

Orange protector must NOT be 

removed until sprinkler is to be placed 

in service. The W-Type 35 Sprinkler 

Wrench MUST be used for proper 

installation of the sprinkler. Failure to 

do so may result in equipment damage 

or failure.

NOTICE

The Model ESFR-17 Pendent Sprinklers 

described herein must be installed and 

maintained in compliance with this 

document, as well as with the appli-

cable standards of the National Fire 

Protection Association (NFPA), in addi-

tion to the standards of any authorities 

having jurisdiction, such as FM Global. 

Failure to do so may impair the perfor-

mance of these devices.
The owner is responsible for main-

taining their fire protection system 

and devices in proper operating con-

dition. Contact the installing contrac-

tor or product manufacturer with any 

questions.
In all cases, the appropriate NFPA or 

FM Global installation standard, or 

other applicable standard, must be ref-

erenced to ensure applicability and to 

obtain complete installation guidelines. 

The general guidelines in this technical 

data sheet are not intended to provide 

complete installation criteria.