background image

TFP223

Page 4 of 6

Care and 

Maintenance

The Series EC-8 Sprinklers must be 

maintained and serviced in accordance 

with this section.
Before closing a fire protection system 

main control valve for maintenance 

work on the fire protection system that 

it controls, permission to shut down the 

affected fire protection systems must 

be obtained from the proper authorities 

and all personnel who may be affected 

by this action must be notified.
Sprinklers that are found to be leaking 

or exhibiting visible signs of corrosion 

must be replaced.
Automatic sprinklers must never be 

painted, plated, coated, or other-

wise altered after leaving the factory. 

Modified sprinklers must be replaced. 

Sprinklers that have been exposed to 

corrosive products of combustion, but 

have not operated, should be replaced 

if they cannot be completely cleaned 

by wiping the sprinkler with a cloth or 

by brushing it with a soft bristle brush.
Care must be exercised to avoid 

damage to the sprinklers before, 

during, and after installation. Sprin-

klers damaged by dropping, striking, 

wrench twist/slippage, or the like, must 

be replaced. Also, replace any sprin-

kler that has a cracked bulb or that has 

lost liquid from its bulb. (Ref. Installa-

tion Section.)
Frequent visual inspections are rec-

ommended to be initially performed 

for corrosion resistant coated sprin-

klers, after the installation has been 

completed, to verify the integrity of the 

corrosion resistant coating. Thereafter, 

annual inspections per NFPA 25 should 

suffice; however, instead of inspecting 

from the floor level, a random sampling 

of close-up visual inspections should 

be made, so as to better determine the 

exact sprinkler condition and the long 

term integrity of the corrosion resistant 

coating, as it may be affected by the 

corrosive conditions present.
The owner is responsible for the 

inspection, testing, and maintenance of 

their fire protection system and devices 

in compliance with this document, as 

well as with the applicable standards 

of the NATIONAL FIRE PROTECTION 

ASSOCIATION (e.g., NFPA 25), in 

addition to the standards of any other 

authorities having jurisdiction. The 

installing contractor or sprinkler man-

ufacturer should be contacted relative 

to any questions.
It is recommended that automatic 

sprinkler systems be inspected, tested, 

and maintained by a qualified Inspec-

tion Service in accordance with local 

requirements and/or national codes.

1/4" (6,4 mm)

3/4" (19,1 mm)

9/16±1/4"

(14,3±6,4 mm)

CLOSURE

1-5/16" (33,3 mm)

13/16" (20,6 mm)

MOUNTING

SURFACE

FACE OF

SPRINKLER

FITTING

2-1/4" DIA.

(57,2 mm)

2-7/8" DIA.

(73,0 mm)

MOUNTING

PLATE

1/8"

(3,2 mm)

1/4" (6,4 mm)

1/2" (12,7 mm)

MOUNTING

SURFACE

FACE OF

SPRINKLER

FITTING

7/16±1/8"

(11,1±3,2 mm)

2-1/4" DIA.

(57,2 mm)

2-7/8" DIA.

(73,0 mm)

CLOSURE

1-5/16" (33,3 mm)
1-1/16" (27,0 mm)

MOUNTING

PLATE

1/8"

(3,2 mm)

"FITTING SIDE"

TOWARDS SPRINKLER

FITTING

WRENCH

RECESS

(END "A")

WRENCH

RECESS

FIGURE 2 

SERIES EC-8 RECESSED PENDENT SPRINKLER ASSEMBLY 

WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT 

STYLE 30 RECESSED ESCUTCHEON

FIGURE 3 

SERIES EC-8 RECESSED PENDENT SPRINKLER ASSEMBLY 

WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT 

STYLE 40 RECESSED ESCUTCHEON

FIGURE 4 

W-TYPE 3  

SPRINKLER WRENCH

FIGURE 5 

W-TYPE 23 RECESSED 

SPRINKLER WRENCH

Содержание tyco EC-8 Series

Страница 1: ...ush pendent position whereas the Style 40 provides 3 4 in 19 1 mm of verti cal adjustment from the flush pendent position The adjustment provided by the Recessed Escutcheons reduces the accuracy to which the fixed pipe drops to the sprinklers must be cut Corrosion resistant coatings where applicable are utilized to extend the life of copper alloy sprinklers beyond that which would otherwise be obt...

Страница 2: ...ded Coverage Sprinklers are to be installed in accor dance with the applicable Factory Mutual Loss Prevention Data Sheet Information provided in the FM Loss Prevention Data Sheet relate to but are not limited to hydraulic design ceiling slope and obstructions minimum and maximum allowable spacing and deflector to ceiling distance HAZARD TYPE TEMP BULB LIQUID SPRINKLER FINISH See Note 4 NATURAL BRA...

Страница 3: ...hten pendent sprin klers using only the W Type 3 End A Sprinkler Wrench Wrench tighten the recessed pendent sprinklers using only the W Type 23 Sprinkler Wrench The wrench recess of the applicable sprin kler wrench Ref Figures 4 and 5 is to be applied to the sprinkler wrench flats Ref Figure 1 Area Style 135 F 57 C 155 F 68 C 16 x 16 Pendent QR QR 16 x 16 Style 30 Recessed QR QR 16 x 16 Style 40 R...

Страница 4: ...ffice however instead of inspecting from the floor level a random sampling of close up visual inspections should be made so as to better determine the exact sprinkler condition and the long term integrity of the corrosion resistant coating as it may be affected by the corrosive conditions present The owner is responsible for the inspection testing and maintenance of their fire protection system an...

Страница 5: ...kler specify tem perature rating specify finish P N specify 135 F 57 C Natural Brass PSN 50 801 1 135 Signal White RAL9003 Polyester PSN 50 801 4 135 Chrome Plated PSN 50 801 9 135 155 F 68 C Natural Brass PSN 50 801 1 155 Signal White RAL9003 Polyester PSN 50 801 4 155 Chrome Plated PSN 50 801 9 155 Recessed Escutcheon Specify Style 30 or 40 Recessed Escutcheon with specify finish P N specify Ref...

Страница 6: ...re Protection Association TEFLON is a registered trademark of DuPont 1400 Pennbrook Parkway Lansdale PA 19446 Telephone 1 215 362 0700 2018 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision date and are subject to change without notice ...

Отзывы: