background image

Ultra Low Flow AQUAMIST Nozzle 

Type ULF AM15 

Non-Automatic (Open)

Page 1 of 2 

JANUARY 2019 

TFP2215

IMPORTANT

Refer to Technical Data Sheet 

TFP2300 for warnings pertaining to 

regulatory and health information.
Always refer to Technical Data 

Sheet TFP700 for the “INSTALLER  

WARNING” that provides cautions 

with respect to handling and instal-

lation of sprinkler systems and com-

ponents. Improper handling and 

installation can permanently damage 

a sprinkler system or its compo-

nents and cause the sprinkler to fail  

to operate in a fire situation or cause  

it to operate prematurely.

Worldwide 

Contacts

www.tyco-fire.com

General 

Description

The TYCO Ultra Low Flow AQUAMIST 

Nozzle Type ULF AM15 is an upright, 

stainless steel, open (non-automatic) 

intermediate pressure nozzle which uti-

lizes a single fluid jet impinging on a dif-

fuser to produce a spray having a range 

of water droplet sizes. It is intended for 

use in engineered, water mist deluge 

systems in marine applications under 

the Guidelines for Approval of Fixed 

Water-Based Local Application Fire –

Fighting Systems for Use in Category 

A Machinery Spaces, MSC/Circ. 913 

(4 June 1999).
It is recommended that the end user be 

consulted with respect to the suitabil-

ity of the materials of construction and 

finish for any given corrosive environ-

ment. The effects of ambient tempera-

ture, concentration of chemicals, and 

gas/chemical velocity, should be con-

sidered, at a minimum, along with the 

corrosive nature to which the nozzles 

may be exposed.

NOTICE

The Type ULF AM15 AQUAMIST 

Nozzles described herein must be 

installed and maintained in compliance 

with this document, as well as with the 

applicable standards of the NATIONAL 

FIRE PROTECTION ASSOCIATION 

(NFPA), in addition to the standards of 

any other authorities having jurisdiction. 

Failure to do so may impair the perfor-

mance of these devices.

The design of individual watermist 

systems can vary considerably, 

depending on the characteristics and 

nature of the hazard and the basic 

purpose of the watermist system. 

Because of these variations, the design 

of watermist systems for fire protec-

tion must only be performed by expe-

rienced designers who thoroughly 

understand the limitations as well as 

capabilities of such systems.

The owner is responsible for main-

taining their fire protection system 

and devices in proper operating con-

dition. Contact the installing contrac-

tor or product manufacturer with any 

questions.

Technical 

Data

Approvals

UL Certified 

Tested to IMO MSC/Circ. 913 (4 June 1999)

Minimum Working Pressure

175 psi (12 bar)

Maximum Working Pressure

250 psi (17,2 bar)

Discharge Coefficient

K = 0.33 GPM/psi

½

 (K = 4,7 LPM/bar

½

)

Thread Connection

1/2 in. NPT

Physical Characteristics

Frame   . . . . . . . . . . . . . . . . . . . . . Stainless Steel

Strainer . . . . . . . . . . . . . . . . . . . .  Stainless Steel

Orifice Insert . . . . . . . . . . . . . . . .  Stainless Steel

Diffuser . . . . . . . . . . . . . . . . . . . .  Stainless Steel

Shield   . . . . . . . . . . . . . . . . . . . . . Stainless Steel

The smallest waterway (orifice) diameter 

of the Orifice Insert is nominally 0.106 in. 

(2,69 mm), and the diameter of the Inlet 

Strainer perforations are nominally 0.060 in. 

(1,52 mm).

Design 

Criteria

Obtain guidance for the design of 

a watermist system that utilizes the 

TYCO Type ULF AM15 AQUAMIST 

Nozzles from the Technical Services 

Department.

Installation

The TYCO Type ULF AM15 AQUAMIST 

Nozzles must be installed in accor-

dance with this section:

General Instructions

A leak tight 1/2 in. NPT nozzle joint 

should be obtained with a torque of 

7 to 14 lb-ft (9,5 to 19,0 N

·

m). Higher 

levels of torque may distort the nozzle 

inlet and cause leakage or impairment 

of the nozzle.
Nozzles must be installed using 0.1 m 

minimum length pipe extensions as 

illustrated in Figure 3.

Step 1.

 With pipe thread sealant 

applied to the pipe threads, hand 

tighten the nozzle into the nozzle fitting.

Step 2.

 Tighten the nozzle into the 

nozzle fitting using only the W-Type 11 

Sprinkler Wrench (Ref. Figure 2). With 

reference to Figure 1, the W-Type 11 

Sprinkler Wrench is to be applied to 

the wrenching area.