TFP2215

Page 2 of 2

NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;

1400 Pennbrook Parkway, Lansdale, PA 19446 | Tel1-215-362-0700

© 2019 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.

Care and 

Maintenance

The TYCO Type ULF AM15 AQUAMIST 

Nozzles must be maintained and ser-

viced in accordance with this section.
Before closing a fire protection system 

main control valve for maintenance 

work on the fire protection system that 

it controls, permission to shut down the 

affected fire protection system must be 

obtained from the proper authorities 

and all personnel who may be affected 

by this action must be notified.
Non-automatic nozzles must never be 

painted, plated, coated or otherwise 

altered after leaving the factory; oth-

erwise, the spray performance may be 

impaired. Modified nozzles must be 

replaced if they cannot be completely 

cleaned by wiping the nozzle with a 

cloth or by brushing it with a soft bristle 

brush.
Care must be exercised to avoid 

damage to the nozzles before, during, 

and after installation. Nozzles damaged 

by dropping, striking, wrench twist/slip-

page, or the like, must be replaced.

Frequent visual inspections are rec-

ommended to be initially performed 

for nozzles installed in potentially cor-

rosive atmospheres to verify the integ-

rity of the materials of construction and 

finish as they may be affected by the 

corrosive conditions present for a given 

installation. Thereafter, annual inspec-

tions per NFPA 25 are required.
The owner is responsible for the 

inspection, testing, and maintenance of 

their fire protection system and devices 

in compliance with this document, as 

well as with the applicable standards 

of the NATIONAL FIRE PROTECTION 

ASSOCIATION, for example, NFPA 

25, in addition to the standards of any 

authority having jurisdiction. 

Contact 

the installing contractor or product 

manufacturer with any questions.

Water mist systems should be 

inspected, tested, and maintained by 

a qualified Inspection Service in accor-

dance with local requirements and/or 

national codes.

Limited 

Warranty

For warranty terms and conditions, visit 

www.tyco-fire.com.

Ordering 

Procedure

Contact your local distributor for 

 

availability.

 

When placing an order, indi-

cate the full product name and Part 

Number.

Type AM15 AQUAMIST Nozzle

Specify: Type ULF AM15 AQUA-

MIST Nozzle, Stainless Steel, 

P/N 49-215-0-001

Sprinkler Wrench

Specify: W-Type 11 Sprinkler Wrench, 

P/N 56-452-1-001

FIGURE 3 

TYPE ULF AM15  

AQUAMIST NOZZLE 

INSTALLATION ARRANGEMENT

Components:

Diffuser

Strainer

Frame

Shield

Insert

Orifice

-

3

4 -

-

1

2 -

-

5

1/2" NPT

WRENCHING

AREA

FACE OF

NOZZLE

FITTING

1-3/4"

(44,5 mm)

13/16"

(20,6 mm)

7/16" (11,1 mm)

NOMINAL MAKE-IN

1-7/16"

(36,5 mm)

2-1/2"

(63,5 mm)

5

1

2

3

4

SUPPLY

PIPE

3/4" x 1/2"

(20 mm x 15 mm)

REDUCING
COUPLING

3/4" (20 mm)

PIPE NIPPLE

4" (0,1 m)

MINIMUM

TYPE AM15

NOZZLE

FIGURE 1 

TYPE ULF AM15 AQUAMIST NOZZLE 

NOMINAL DIMENSIONS

FIGURE 2 

W-TYPE 11 

SPRINKLER WRENCH