Care and
Maintenance
The TYCO Type ULF AM15 AQUAMIST
Nozzles must be maintained and ser-
viced in accordance with this section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down the
affected fire protection system must be
obtained from the proper authorities
and all personnel who may be affected
by this action must be notified.
Non-automatic nozzles must never be
painted, plated, coated or otherwise
altered after leaving the factory; oth-
erwise, the spray performance may be
impaired. Modified nozzles must be
replaced if they cannot be completely
cleaned by wiping the nozzle with a
cloth or by brushing it with a soft bristle
brush.
Care must be exercised to avoid
damage to the nozzles before, during,
and after installation. Nozzles damaged
by dropping, striking, wrench twist/slip-
page, or the like, must be replaced.
Frequent visual inspections are rec-
ommended to be initially performed
for nozzles installed in potentially cor-
rosive atmospheres to verify the integ-
rity of the materials of construction and
finish as they may be affected by the
corrosive conditions present for a given
installation. Thereafter, annual inspec-
tions per NFPA 25 are required.
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the NATIONAL FIRE PROTECTION
ASSOCIATION, for example, NFPA
25, in addition to the standards of any
authority having jurisdiction.
Contact
the installing contractor or product
manufacturer with any questions.
Water mist systems should be
inspected, tested, and maintained by
a qualified Inspection Service in accor-
dance with local requirements and/or
national codes.
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for
availability.
When placing an order, indi-
cate the full product name and Part
Number.
Type AM15 AQUAMIST Nozzle
Specify: Type ULF AM15 AQUA-
MIST Nozzle, Stainless Steel,
P/N 49-215-0-001
Sprinkler Wrench
Specify: W-Type 11 Sprinkler Wrench,
P/N 56-452-1-001
FIGURE 3
TYPE ULF AM15
AQUAMIST NOZZLE
INSTALLATION ARRANGEMENT
Components:
Diffuser
Strainer
Frame
Shield
Insert
Orifice
-
3
4 -
-
1
2 -
-
5
1/2" NPT
WRENCHING
AREA
FACE OF
NOZZLE
FITTING
1-3/4"
(44,5 mm)
13/16"
(20,6 mm)
7/16" (11,1 mm)
NOMINAL MAKE-IN
1-7/16"
(36,5 mm)
2-1/2"
(63,5 mm)
5
1
2
3
4
SUPPLY
PIPE
3/4" x 1/2"
(20 mm x 15 mm)
REDUCING
COUPLING
3/4" (20 mm)
PIPE NIPPLE
4" (0,1 m)
MINIMUM
TYPE AM15
NOZZLE
FIGURE 1
TYPE ULF AM15 AQUAMIST NOZZLE
NOMINAL DIMENSIONS
FIGURE 2
W-TYPE 11
SPRINKLER WRENCH