background image

Series ELO-231 – 11.2 K-factor 

Upright and Pendent Sprinklers 

Standard Response, Standard Coverage

Page 1 of 6 

AUGUST 2018 

TFP340

Worldwide 

Contacts

www.tyco-fire.com

IMPORTANT

Refer to Technical Data Sheet 

TFP2300 for warnings pertaining to 

regulatory and health information.
Always refer to Technical Data 

Sheet TFP700 for the “INSTALLER  

WARNING” that provides cautions 

with respect to handling and instal-

lation of sprinkler systems and com-

ponents. Improper handling and 

installation can permanently damage 

a sprinkler system or its compo-

nents and cause the sprinkler to fail  

to operate in a fire situation or cause  

it to operate prematurely.

General 

Description

TYCO Series ELO-231 11.2K Stan-

dard Response, Standard Coverage 

Upright and Pendent Sprinklers (Ref. 

Figure 1) are automatic sprinklers of 

the fusible solder type. They are stan-

dard response, spray sprinklers that 

produce a hemispherical water distri-

bution pattern below the deflector.
The 11.2 K-factor, ELO-231 Sprinklers 

were subjected to full scale, high-piled 

storage, fire tests to qualify their use 

in lieu of 5.6 or 8.0 K-factor standard 

spray sprinklers for the protection of 

high-piled storage.
Higher flow rates can be achieved at 

much lower pressures with the 11.2 

K-factor, ELO-231 Sprinklers, making 

their use highly advantageous in high 

density applications, such as the pro-

tection of high-piled storage.
Wax or lead coatings can be used 

to extend the life of the copper alloy 

components used in Series ELO-231 

sprinklers beyond that which would 

otherwise be obtained when exposed 

to corrosive atmospheres. Although 

wax and lead coated sprinklers have 

passed the standard corrosion tests of 

the applicable approval agencies, the 

testing is not representative of all pos-

sible corrosive atmospheres. Conse-

quently, it is recommended that the end 

user be consulted with respect to the 

suitability of these corrosion resistant 

coatings for any given corrosive envi-

ronment. The effects of ambient tem-

perature, concentration of chemicals, 

and gas/chemical velocity, should be 

considered, as a minimum, along with 

the corrosive nature of the chemical to 

which the sprinklers will be exposed.
An upright intermediate level version 

of the Series ELO-231 Sprinklers for 

in-rack applications can be obtained 

by utilizing the Series ELO-231 Upright 

Sprinkler with the WSG-2 Guard & 

Shield, and a pendent intermediate 

level version of the Series ELO-231 

Sprinklers can be obtained by utilizing 

the Series ELO-231 Pendent Sprinkler 

with the WS-2 Shield. If there is a pos-

sibility of the pendent intermediate level 

version being exposed to mechanical 

damage, a G-2 Guard can be added.

NOTICE

The 11.2 K-factor, Series ELO-231 

Upright and Pendent Sprinklers 

described herein must be installed 

and maintained in compliance with this 

document, as well as with the applica-

ble standards of the National Fire Pro-

tection Association (NFPA), in addition 

to the standards of any other authori-

ties having jurisdiction. Failure to do so 

may impair the performance of these 

devices.
The owner is responsible for main-

taining their fire protection system 

and devices in proper operating con-

dition. Contact the installing contrac-

tor or product manufacturer with any 

questions.
Installation of Series ELO-231 Pendent 

Sprinklers in recessed escutcheons will 

void all sprinkler warranties, as well as 

possibly void the sprinkler’s Approvals 

and/or Listings.

Sprinkler 

Identification 

Numbers (SINs)

Refer to Table A for sprinkler identifica-

tion numbers.

Technical 

Data

Approvals

UL and C-UL Listed 

FM Approved 

NYC Approved

Refer to Table C for specific details 

on laboratory listings and approvals, 

including corrosion-resistant status. 

The approvals apply to the service con-

ditions indicated in the Design Criteria 

section.

Finishes

Refer to Table C

Physical Characteristics

Frame  . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze 

Seal Disc . . . . . . . . . . . . . . . . . . . . . . . . .  Copper 

Cap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze 

Strut Assembly  . .Solder, Bronze Stainless Steel 

Compression Screw . . . . . . . . . . . . . . . . .Bronze 

Deflector . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze 

Helper Spring . . . . . . . . . . . . . . .  Stainless Steel 

Ejector Spring . . . . . . . . . . . . . . . . . . . . . .  Nickel 

Strut Clip . . . . . . . . . . . . . . . . . . .  Stainless Steel

Additional Technical Data

Refer to Table A for additional techni-

cal data.

Отзывы: