2/3                        TVI-TD-6007 Thermostat_1109 

 

                                                                                                                          Subject to changes without prior notice

 

 

 
 
 

INSTRUCTION 

 

1. 

Cool/heat shift:

 (TVI-TD-6007A/B/C) in 2-pipe system, the thermostat is on Cooling state when the Power 

Supply switch is at position 

“ ”; on Heating state when the Power Supply switch is at position “ ”; and, 

the thermostat is shut off when the Power Supply switch is at position 

”. In 4-pipe system, the thermostat 

can  only  output  heating  or  cooling  signal  according  to  the  position  of  Power  Supply  switch.  When  the 
power switch is turned to position 

”, the thermostat will self-check, and then make the valve run for 150 

seconds  (or  300  seconds)  continuously  towards  the  closing  position.  When  it  finishes  operation,  the 
thermostat will enter into turn off state. When the power supply switch turns 

to “ ”, the LCD will show the 

cooling state symbol 

“ ”, the action signal will output forward; when it moves to “

”, the LCD will show the 

heating state symbol“

”, the action signal will output backward. When it moves to “

”, the LCD will shut off, 

the valve will run for 150 seconds (or 300 seconds) continuously towards the closing end, then the system 
will be shut off.   

2. 

Fan:

 When the thermostat is in cooling or heating state, turn the fan switch 

-

-

, the LCD will display 

corresponding air volume symbol. The terminals will output power and provide operating power for the fan. 

If the thermostat isn

’t connected to the fan, only 

  or 

  can be shown on the LCD. The symbol 

 

can 

only be shown when the thermostat is connected to the fan correctly. 

3. 

Temperature setting:

 When user presses 

increase

” decrease

button, LCD display temperature 

setting  will  show  increase  or  decrease  accordingly.  The  increase/decrease  rate  is  0.2

o

C/0.5

  o

F.  The 

adjusting  range  is  10~30

oC

/50~86

  o

F.  When  user  stops  pressing  the  button  for  over  5  seconds,  the 

thermostat will change the setting temperature data in its memory, and then the LCD shows the ambient 
temperature. (The ex-factory setting point is 25

o

C/77

 o

F.)   

4. 

Built-in/external sensor: 

When built-in NTC thermistor is used, the jumper J3 should be put to position 

“Int”. If the external NTC sensor is used, the jumper J3 should be put to “Ext” position. 

5. 

Fixed  setting  temp.  function:

  Put  the  jumper  JP4  to  position  1,  the  setting  point  can

’t be changed by 

pressing  increase  or  decrease  buttons.  (The  default  setting  is  on  position  0.  The  setting  point  can  be 
changed by pressing increase or decrease buttons) 

 
 

 

           

WIRING DIAGRAM 

 

 

 

 

         
 
 
 
 
 
 
 
 
 
 
 
       
 
               
 
 
 

 

TVI-TD-6007A-Heat/Cool 
TVI-TD-6007B-Cool Only 

TVI-TD-6007C 

– 4 Pipes Sys.

 

TVI-TD-6007P 

– Modulating

 

TVI-TD-6007F 

– Floating

 