background image

TM-21x1 Series Room Temperature Module Installation Instructions

2

Dimensions

TM-2141 Modules 

TM-2151 Modules  

TM-2161 Modules

  

Figure 1: TM-2141 Dimensions, in. (mm)

3.15 (80)

1.26 (32)

4.72

(120)

F

IG

:2

1

4

1

_

d

im

Figure 2: TM-2151 Dimensions, in. (mm)

F

IG

:2

1

5

1

_

d

im

Mode

LED

Occupancy

Button

3.15 (80)

1.26 (32)

4.72

(120)

Figure 3: TM-2161-0002 and TM-2161-0007 

Dimensions, in. (mm)

F

IG

:2

1

6

1

_

d

im

1.38 (35)

4.72

(120)

3.15 (80)

Mode

LED

Occupancy

Button

Fan

Speed

Dial

Setpoint

Adjustment

Dial

F

IG

:2

1

6

1

_

0

0

0

5

_

d

im

1.38 (35)

4.72

(120)

3.15 (80)

Mode

LED

Occupancy

Button

Setpoint

Adjustment

Dial

Figure 4: TM-2161-0000 and TM-2161-0005

Dimensions, in. (mm)

Содержание TM-2161

Страница 1: ...iode LED that indicates the current operating mode Installation Parts Included Two 6 32 x 7 8 in 22 mm wallbox mounting screws are included with the TM 21x1 Module Special Tools Needed For tightening and loosening the TM 11x1 Series Room Temperature Module security screw order the optional Allen head tool T 4000 119 from the nearest Johnson Controls representative IMPORTANT The TM 21x1 Series Room...

Страница 2: ...re 2 TM 2151 Dimensions in mm FIG 2151_dim Mode LED Occupancy Button 3 15 80 1 26 32 4 72 120 Figure 3 TM 2161 0002 and TM 2161 0007 Dimensions in mm FIG 2161_dim 1 38 35 4 72 120 3 15 80 Mode LED Occupancy Button Fan Speed Dial Setpoint Adjustment Dial FIG 2161_0005_dim 1 38 35 4 72 120 3 15 80 Mode LED Occupancy Button Setpoint Adjustment Dial Figure 4 TM 2161 0000 and TM 2161 0005 Dimensions in...

Страница 3: ...ing Location Considerations Mount the TM 21x1 Series Room Temperature Module on a wall in the room to be controlled where the occupant can easily read and adjust the setpoint dial or fan speed override adjustment dial Consider these additional guidelines in determining the best mounting location Avoid areas subject to excessive vibration electrical noise direct sunlight or the effects of radiant h...

Страница 4: ...turing an NTC Sensor with Temperature Setpoint Adjustment and Occupancy Override FIG 2161_0005_WIR 15 14 21 20 NTC Sensor Common Mode LED Occupancy Button 23 22 Room Temperature Module DC 5 V Temperature Setpoint Figure 9 Wiring to a Room Temperature Module Featuring an NTC Sensor with Temperature Setpoint Adjustment Occupancy Override and Three Speed Fan Override FIG 2161_0207_WIR 15 14 21 20 NTC...

Страница 5: ...Running low and high voltage wires in the same conduit or wiring troughs may damage the equipment or cause system malfunction MISE EN GARDE Risque de dégâts matériels Ne pas faire courir un câble basse tension dans les mêmes gaines ou goulottes électriques que des câbles haute tension L installation de fils basse tension et haute tension dans les mêmes gaines ou goulottes électriques risque d endo...

Страница 6: ...perature Output with Setpoint Adjustment Power Requirements 5 VDC Power Consumption N A Refer to individual component specification Inputs None Adjustments Temperature Setpoint Fan Speed Optional by Model Mode Indicator Green LED 5 V 4 mA Occupancy Button Momentary Contact Switch 5 V at 1 mA Output Temperature Sensing Element Resistance Temperature Device RTD Thermistor Negative Temperature Coeffi...

Страница 7: ...d III TM 21x1 0005 10k ohm potentiometer marked for 5F TM 21x1 0007 10k ohm potentiometer marked for 5F Fan Speed Adjustment Auto Off I II and III Accuracy 0 9 F 0 5 C Field Connection 18 to 22 AWG 1 00 to 0 65 mm diameter recommended Mounting Wallbox Mount Housing Material ABS PC Self Extinguishing HB UL94 Protection IP30 EN 60529 Ambient Operating Conditions 32 to 122 F 0 to 50 C 10 to 90 RH non...

Отзывы: