Repair information
If the BACnet/IP to MS/TP router fails to operate within its specifications, replace the unit. For a
replacement unit, contact the nearest Johnson Controls
®
representative.
BACnet to MS/TP Router technical specifications
Table7: BACnet to MS/TP Router technical specifications
Product Code
TL-BRTRP-0
Electrical (USB)
Input Voltage: 5 VDC (nominal)
Input Current: 500 mA (maximum)
Environmental
Operating temperature: 0°C to 50°C (32°F to 122°F)
Storage temperature: -40°C to 85°C (-40°F to 185°F)
Relative humidity: 10% to 95%, noncondensing
Signaling
USB: 1.1 (2.0 compatible)
Ethernet: 10BASE-T, 100BASE-TX
MS/TP: EIA-485, (American National Standards Institute/American Society
of Heating, Refrigerating, and Air-Conditioning Engineers [ANSI/ASHRAE]
135-2004)
Cable Length Limit
USB: 5 m
Ethernet: 100 m
MS/TP: 1,200 m (for 18 AWG)
MS/TP bps
9600; 19,200; 38,400; 76,800
MS/TP Node Limit
127 devices
32 devices per segment
LEDs
MS/TP LED
Flashing green = receive activity
USB (Power)
LED Green
Ethernet LED
Green = 100 Mbps
Yellow = 10 Mbps
Flashing = Activity
Ethernet Flow Control
Half-duplex – backpressure
Full-duplex – Institute of Electrical and Electronic Engineers (IEEE) 802.3x
PAUSE
Portable BACnet/IP to MS/TP Router Installation Instructions
8
Содержание TL-BRTRP-0
Страница 10: ...www johnsoncontrols com ...