5742640-TIM-A-0419
46
Johnson Controls Ducted Systems
ZDT04 (4 Ton Belt Drive) Bottom Duct
`Air Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes gas heat exchangers and 1” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
0.2
0.4
0.6
0.8
1
1.2
1.4
1.6
1.8
2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Supplied Drive
Standard Drive Option
High Static Drive Option
1000
688
0.34
779
0.42
866
0.50
949
0.59
1029
0.67
1107
0.77
1181
0.85
1253
0.95
1322
1.05
1388
1.15
1200
722
0.40
812
0.48
899
0.56
983
0.64
1063
0.73
1140
0.82
1215
0.90
1286
1.01
1355
1.11
1422
1.20
1400
761
0.48
852
0.56
939
0.64
1022
0.73
1103
0.81
1180
0.89
1254
0.99
1326
1.08
1395
1.19
1462
1.29
1600
807
0.61
897
0.68
984
0.76
1068
0.84
1148
0.93
1225
1.02
1300
1.12
1371
1.21
1440
1.31
1507
1.40
1800
856
0.77
947
0.84
1034
0.93
1118
1.00
1198
1.10
1275
1.18
1349
1.28
1421
1.37
1490
1.47
1557
1.57
2000
910
0.97
1001
1.04
1088
1.13
1172
1.21
1252
1.30
1329
1.39
1403
1.48
1475
1.57
1544
1.68
1611
1.77
FS4
ZDT05 (5 Ton Belt Drive) Bottom Duct
Air Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes gas heat exchangers and 1” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
0.2
0.4
0.6
0.8
1
1.2
1.4
1.6
1.8
2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Supplied Drive
Standard Drive Option
High Static Drive Option
1200
722
0.40
812
0.48
899
0.56
983
0.64
1063
0.73
1140
0.82
1215
0.90
1286
1.01
1355
1.11
1422
1.20
1400
761
0.48
852
0.56
939
0.64
1022
0.73
1103
0.81
1180
0.89
1254
0.99
1326
1.08
1395
1.19
1462
1.29
1600
807
0.61
897
0.68
984
0.76
1068
0.84
1148
0.93
1225
1.02
1300
1.12
1371
1.21
1440
1.31
1507
1.40
1800
856
0.77
947
0.84
1034
0.93
1118
1.00
1198
1.10
1275
1.18
1349
1.28
1421
1.37
1490
1.47
1557
1.57
2000
910
0.97
1001
1.04
1088
1.13
1172
1.21
1252
1.30
1329
1.39
1403
1.48
1475
1.57
1544
1.68
1611
1.77
2200
968
1.22
1059
1.30
1146
1.37
1229
1.46
1309
1.54
1387
1.64
1461
1.73
1533
1.83
1602
1.92
1668
2.03
2400
1029
1.51
1119
1.58
1206
1.67
1290
1.74
1370
1.84
1448
1.92
1522
2.02
1593
2.11
1663
2.21
1729
2.31
2600
1093
1.84
1183
1.91
1270
1.98
1354
2.07
1434
2.15
1511
2.25
1586
2.34
-
-
-
-
-
-
FS4
ZDTA6 (6 Ton Belt Drive) Bottom Duct
Air Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes gas heat exchangers and 1” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. 1kW = BHP x 0.862.
0.2
0.4
0.6
0.8
1
1.2
1.4
1.6
1.8
2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Supplied Drive
Standard Static Drive Option
High Static Drive Option
1600
829
0.46
914
0.52
988
0.61
1055
0.71
1115
0.83
1170
0.95
1222
1.09
1273
1.23
1324
1.36
1377
1.50
1800
858
0.63
943
0.70
1017
0.78
1084
0.89
1144
1.00
1199
1.13
1251
1.26
1302
1.40
1353
1.54
1406
1.67
2000
898
0.84
983
0.90
1057
0.99
1124
1.09
1184
1.21
1239
1.34
1291
1.47
1342
1.61
1393
1.75
1446
1.88
2200
945
1.08
1030
1.15
1104
1.23
1171
1.34
1231
1.45
1286
1.58
1338
1.72
1389
1.85
1440
1.99
1493
2.13
2400
997
1.37
1081
1.44
1156
1.52
1222
1.62
1282
1.74
1338
1.87
1390
2.00
1441
2.14
1491
2.28
1544
2.41
2600
1052
1.70
1136
1.77
1211
1.85
1277
1.96
1337
2.07
1392
2.20
1445
2.33
1495
2.47
1546
2.61
1599
2.74
2800
1108
2.08
1192
2.14
1267
2.23
1334
2.33
1394
2.45
1449
2.58
1501
2.71
1552
2.85
1603
2.99
1656
3.12
3000
1166
2.50
1250
2.57
1325
2.65
1391
2.75
1451
2.87
1506
3.00
1558
3.13
1609
3.27
----
----
----
----