TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
26
Setting both BIs to the same function is supported for all except Occupancy, Fan Lock, Open Door, and Open
Window. If both BIs are set the same for those four, BI2 is ignored and only BI1 is used.
The Open Door option works in conjunction with a motion sensor, either built into the TEC or connected to another
BI configured for Motion NO/NC mode. When the door is open, motion detected by the sensor is ignored.
Note:
Opening the door does not stop an Occupied period started by the motion sensor prior to opening the door.
The polarity of the inputs are provided in Table 9.
Note:
Supply Fan Status and Fan Lock are not compatible with each other. The TEC3000 only controls one fan so
it cannot accept feedback from two fan sources. When configuring BI-1 and BI-2, choose either Supply Fan Status
or Fan Lock, but not both.
Aux Control
The TEC has an auxiliary output that can be configured to operate in a few different ways. The Aux Mode supports
seven different options:
•
Not Used—Output is always off
•
Occupied NO—Output is normally open, but closes when occupied
•
Occupied NC—Output is normally closed, but opens when occupied
•
Occupied Fan NO—Output is normally open, but is closed when occupied with the fan running
•
Occupied Fan NC—Output is normally closed, but is open when occupied with the fan running
•
On—Output is turned on (relay closed), used by a BAS to directly control the AUX output
•
Off—Output is turned off (relay open), used by a BAS to directly control the AUX output
To set the Aux Mode:
1.
Press the
Menu
icon.
2.
Press
Control Setup
.
3.
Press
General
.
4.
Press
Aux Mode
and set accordingly.
5.
Press
to save and
to return to the previous screen.
Table 9: Input Polarities
BI Configuration
Contact Open
Contact Closed
Occupancy
Unoccupied
Occupied
Temp Occ
No Trigger Active
Temporary Occupancy Trigger
1
Motion NO
No Motion Detected, Standby
Motion Detected, Occupied
1
Motion NC
Motion Detected, Occupied
1
1.
Configurations that support both BIs configured for the same feature of the action that occurs when either
of the BIs enter that state.
No Motion Detected, Standby
Dirty Filter
Dirty Filter Alarm Inactive
Dirty Filter Alarm
1
Service
Service Alarm Inactive
Service Alarm
1
Fan Lock
No Airflow
Airflow
Open Door
Door Open, Unoccupied
Door Closed, Occupied
Open Window
Window Open, Control Shut Down
Window Closed, Control Running
Supply Fan Status
Supply Fan Off
Supply Fan On