background image

TEC3000 Series Single- or Two-Stage Economizer Thermostat 

Controllers Installation Instructions

1

 Refer to the 

QuickLIT website

 for the most up-to-date version of this document.

Applications

The TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers are stand-alone and 
field-selectable BACnet® MS/TP or N2 networked devices that provide control of the following:

unitary rooftop units (RTUs)

unitary RTUs with economizers

unitary RTUs with heat pumps

unitary RTUs with economizers and heat pumps

The networked models feature a field-selectable Building Automation System (BAS) BACnet MS/TP or N2 
communication capability that enables remote monitoring and programming for efficient space temperature control. 
All models include a USB port configuration that reduces installation time by allowing simple backup and restore 
features from a USB drive, which enables rapid cloning of configuration between like units.

Some models have occupancy sensing capability built into the device. These thermostat controllers maximize up to 
30% energy savings in high-energy usage commercial buildings, such as schools and hotels, during occupied 
times by using additional standby setpoints.

All models feature an intuitive onboard touchscreen UI with backlit display that makes setup and operation quick 
and easy. Only the single-speed fan configuration is supported for fan coil equipment types.  

IMPORTANT:

The TEC3000 Series Thermostat Controller is intended to provide an input to equipment under 

normal operating conditions. Where failure or malfunction of the thermostat controller could lead to personal 
injury or property damage to the controlled equipment or other property, additional precautions must be 
designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems 
or safety or limit controls, intended to warn of or protect against failure or malfunction of the thermostat 
controller.

IMPORTANT: 

Le TEC3000 Series Thermostat Controller est destiné à transmettre des données entrantes à un 

équipement dans des conditions normales de fonctionnement. Lorsqu'une défaillance ou un dysfonctionnement 
du thermostat controller risque de provoquer des blessures ou d'endommager l'équipement contrôlé ou un autre 
équipement, la conception du système de contrôle doit intégrer des dispositifs de protection supplémentaires. 
Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou 
d'alarme, ou des dispositifs de sécurité ou de limitation, ayant une fonction d'avertissement ou de protection en 
cas de défaillance ou de dysfonctionnement du thermostat controller.

TEC3000 Series Single- or Two-Stage Economizer 
Thermostat Controllers

Installation Instructions

TEC3330-xx-xxx, TEC3331-xx-xxx,
TEC3630-xx-xxx, TEC3631-xx-xxx

Part No. 24-10789-5, Rev. 

F

Issued July 2018

                (barcode for factory use only)

 

*24107895F*

24-10789-5, Rev. F

Содержание TEC3330 Series

Страница 1: ...ported for fan coil equipment types IMPORTANT The TEC3000 Series Thermostat Controller is intended to provide an input to equipment under normal operating conditions Where failure or malfunction of the thermostat controller could lead to personal injury or property damage to the controlled equipment or other property additional precautions must be designed into the control system Incorporate and m...

Страница 2: ...limits are designed to provide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If thi...

Страница 3: ...ectrical junction box use 2 1 2 x 4 in 63 x 101 mm square boxes with mud ring covers and avoid smaller 1 1 2 x 4 in 38 x 101 mm square or 3 x 2 in 76 x 51 mm boxes This procedure ensures that you have enough space for cabling if needed For surface mounted applications use durable mounting hardware such as wall anchors that cannot be easily pulled out of the mounting surface 4 Pull approximately 6 ...

Страница 4: ...al connections to avoid electric shock Risque de décharge électrique Débrancher l alimentation avant de réaliser tout raccordement électrique afin d éviter tout risque de décharge électrique Risk of Property Damage Do not apply power to the system before checking all wiring connections Short circuited or improperly connected wires may result in permanent damage to the equipment Risque de dégâts ma...

Страница 5: ...controller as the end of the Field Controller FC Bus and N2 Bus The default position is OFF If the thermostat controller is at the end of a daisy chain of devices on the FC Bus and N2 Bus set the EOL switch to the ON position See Figure 4 Figure 4 EOL Switch Positions Left and Installing the Thermostat Controller Cover Right 5 Reattach the thermostat controller cover to the mounting base bottom si...

Страница 6: ...and base board there is no error For example if 0B is listed as the CPU board and the base board the model is the TEC3611 Name Code Number1 TEC3310 00 TEC3610 0A TEC3311 01 TEC3611 0B TEC3312 02 TEC3612 0C TEC3313 03 TEC3613 0D TEC3320 04 TEC3620 0E TEC3321 05 TEC3621 0F TEC3322 06 TEC3622 10 TEC3323 07 TEC3623 11 TEC3330 08 TEC3630 12 TEC3331 09 TEC3631 13 IMPORTANT If the display is dirty gently...

Страница 7: ...r temperature COM2 Common G Fan BI2 Configurable binary input 2 BI1 Configurable binary input 1 SAT Supply temperature sensor R SEN Zone temperature sensor NET Not connected Field bus N2 NET Not connected Field bus N2 NET COM Not connected Isolated common for field bus 1 RH needs to be connected for W1 and W2 to energize For heating systems with an isolated power supply connect RH to the R termina...

Страница 8: ...quired for each TEC Figure 7 Staged Wiring Diagram Rooftop Unit See Table 2 for Terminal Identification Thermistor FIG Model 3 Wiring_output 24 V R SEN 24V NET COM SAT OAD COM Supply Aux Thermistor Vin Common Economizer 24 V Cool 1 Cool 2 Y1 AUX TB1 W2 SUP Y2 G AUX FIG Model 3 Wiring_input Common RH W1 OB Outdoor Air Temp Heat 1 ...

Страница 9: ...or each TEC Figure 8 Staged Wiring Diagram Heat Pump See Table 2 for Terminal Identification Thermistor FIG Model 3 Wiring_output 24 V R SEN 24V NET COM SAT OAD COM Supply Aux Thermistor Vin Common Economizer 24 V Compressor 1 Compressor 2 Y1 AUX TB1 W2 SUP Y2 G AUX FIG Model 3 Wiring_input_heatpump Common RH W1 OB Outdoor Air Temp O B ...

Страница 10: ...n control which options the occupant can access and adjust Figure 11 Thermostat Controller Home Screen This model cannot be purchased with a built in sensor The only way for the unit to display humidity is if the network override for humidity is active If this override is active the humidity level is displayed on the home screen IMPORTANT Table 10 provides a full list of TEC3000 menu settings In t...

Страница 11: ...sed on the menu and those icons are also described in Table 3 Brightness Units Time Zone Date Enable Backlight Time Time Format Date Format Fan Button Off Button Alarm Indication Date Time Space Temperature Hold Button Occupancy Status Humidity Setpoint Unit Status Table 3 Touchscreen Icons Part 1 of 2 Icon Icon Name Description Menu Displays the configuration screens where various settings may be...

Страница 12: ...rride between On Auto and Quiet for single speed fans Home Returns the display to the main home screen Back Returns to the previous screen Save Saves the current configuration and parameter settings Delete Deletes the scheduled event Clear Clears the password entry on the keypad screen Wrench Indicates that the value is editable Checkmark Indicates that an event or schedule is programmed for a spe...

Страница 13: ...31 00 000 Models to configure each device Loading the Firmware 1 Ensure that the TEC screen is on 2 Insert the USB drive into the right side of the TEC See Figure 1 for the USB port location 3 Press the Menu icon 4 Scroll down the menu and press Update 5 Press Load Firmware 6 Select the correct firmware version The correct file name has the pkg extension 7 Press Confirm if you have the correct fir...

Страница 14: ... The setting files are named based on the TEC3000 model name date and time stamp for example TEC3311 00_2015 10 08T1 The files are saved locally and on the USB drive s root directory 7 Press Confirm if you have the correct file name The settings are loaded from the USB drive 8 After the settings are loaded from the USB drive remove the USB drive from the TEC3000 Choosing the Communication Mode TEC...

Страница 15: ...Y2 Certain heat pumps do not require an O B input and instead take standard W and Y commands as heat or cool commands internally sequencing the equipment For these type of heat pump units leave the controller in Rooftop mode When in heat pump mode the TEC controls up to two stages of compressors Y1 Y2 for both heating and cooling O B is controlled through the W1 OB output and one stage of suppleme...

Страница 16: ...ing Automation System BAS which overrides the internal sensor If Outdoor Air Humidity OAH is also provided by writing to NET OAH then the single enthalpy method is used to determine if economizer cooling should be used Finally if Zone Humidity ZNH is also provided by writing to NET ZNH then the dual enthalpy method is used to determine if economizer cooling should be used All network overrides to ...

Страница 17: ... periods but is continuously running during occupied standby periods The Fan Override icon on the home screen is dependent on the fan type The following options are provided for single speed fans On Overrides the fan to be continuously on Auto Follows the behavior set as Fan Mode Quiet Follows the behavior set as Auto Mode The Quiet option has no effect on the RTU heat pump equipment as only a sin...

Страница 18: ...lowering the temperature but the building owner can still set back setpoints during standby and unoccupied periods When the setpoint is in Hold mode pressing the icon again releases the hold and immediately sets the setpoint offset back to 0 When the TEC is in Min Max mode Setpoints Occ Setpoint Select are equal to Min and Max Setpoint the TEC rejects any attempts to change the present value outsi...

Страница 19: ...ion matrix as shown in Table 6 Occ Setpoint Select Setpoint Offset and Heat Cool Setpoint Mode Common Setpoint In this mode the TEC has one setpoint Common Setpoint for heating and cooling There is also a common Setpoint Offset warmer cooler adjust that is only applied to Common Setpoint Otherwise this setting works the same as when Occ Setpoint Select Setpoint Offset and Heat Cool Setpoint Mode I...

Страница 20: ...neither BI1 Config nor BI2 Config is set to Occupancy BI Open and Closed refer to the current state of the BI when configured as Occupancy Temporary Occupancy2 3 2 True is triggered by interacting with the screen during a scheduled unoccupied period A value of True can only occur when the schedule is not Occupied 3 When triggered by a BI configured for Temp Occ the input is ignored when the schedu...

Страница 21: ...rnal BAS 5 Press to save and to return to the previous screen This option is also exposed to the BAS through the point OCC CONFIG If BAS is configured as the occupancy source map the point NET OCC in and write to that point to control the schedule remotely If the supervisor goes offline as identified by the network icon going away on the home screen of the TEC the control logic automatically falls...

Страница 22: ...e event to be set 7 Set the Occupancy to Not Set Occupied Unoccupied or Standby and press Save Figure 12 Selecting the Days Left and Selecting the Event Right Figure 13 Setting the Room Occupancy Left and Setting the Occupancy Mode Right IMPORTANT Internally the TEC 3000 uses a BACnet schedule where daily schedules are independent of the previous and next days The default occupancy of the TEC3000 ...

Страница 23: ...n Figure 15 Returning to the Main Menu 10 Press to save and to return to the previous screen Overriding the Occupancy Mode The TEC supports a manual override of all other schedule sources for example Schedule Occupancy BI and temporary occupancy To override the Occupancy Mode 1 Press the Menu icon 2 Press Schedule 3 Press Schedule Options 4 Press Manual Occupancy Mode and select Occupied Unoccupie...

Страница 24: ...ed sensor the default timeout is still 15 minutes but it only is applied when one of the two configurable binary inputs is set to be a motion sensor see Configurable Binary Inputs for information on configuring the binary inputs To disable motion sensing capabilities set the Motion Sensor Timeout to 0 minutes See Table 6 to view the available setpoints See Table 10 to view the setpoint values To a...

Страница 25: ...disables control 60 seconds after detecting an opened window Open Door Works in conjunction with the Motion NO Motion NC sensor to control occupancy Fan Lock Air Proof switch input to shut down control if no airflow is detected within 10 seconds of turning the fan on Fan Lock must be manually reset from the Faults menu Service Input from the equipment to display a service warning on the thermostat...

Страница 26: ...closes when occupied Occupied NC Output is normally closed but opens when occupied Occupied Fan NO Output is normally open but is closed when occupied with the fan running Occupied Fan NC Output is normally closed but is open when occupied with the fan running On Output is turned on relay closed used by a BAS to directly control the AUX output Off Output is turned off relay open used by a BAS to d...

Страница 27: ...en internal sensors for control and display Not all sources are available for all sensors Network commands operate on a timeout basis When a network point is written to by a supervisor the point becomes the highest priority for 15 minutes If a new update is written within 15 minutes the timer is restarted for another 15 minutes Available Fault Diagnostics Supply Fan Faults The TEC3000 supports a c...

Страница 28: ...emperature always needs to be 1 F 0 55 C above the heating temperature These values only appear when Heat Cool Setpoint Mode Individual Setpoints and Occ Setpoint Select Min and Max Setpoint Min Heating Setpoint 60 F 15 C 45 F 7 22 C to Max Heating Setpoint These values only appear when Heat Cool Setpoint Mode Individual Setpoints and Occ Setpoint Select Min and Max Setpoint Max Cooling Setpoint 8...

Страница 29: ...ur 24 hour or 12 hour Date N A Set Date Format YYYY MM DD YYYY MM DD or Day Month DD YYYY or MM DD YYYY Language English English French Spanish Show Fan Icon Yes Yes or No Show Temp Yes Yes or No Show Humidity Yes Yes or No Show Off Icon Yes Yes or No Show Hold Icon Yes Yes or No Show Setpoint Yes Yes or No Show Alarms Yes Yes or No Show Occ Status Yes Yes or No Show Unit Status Yes Yes or No Show...

Страница 30: ...ow Open Door Fan Lock Service Dirty Filter Motion NC Motion NO Temp Occ Occupancy BI2 Config Disabled Disabled Open Window Open Door Fan Lock Service Dirty Filter Motion NC Motion NO Temp Occ Occupancy Supply Temp Sensor Nickel Nickel Platinum A99B 2 25k ohm negative temperature coefficient NTC 10k ohm NTC 10k ohm NTC Type 3 Supply Temp Offset 0 5 to 5 F or C based on Units setting under Display S...

Страница 31: ...00 seconds 60 to 900 seconds Values only appear when the Temp control equals Manual PID Tuning Heat Time Constant 720 seconds 360 to 1 440 seconds Values only appear when the Temp control equals Manual PID Tuning Heat Process Dead Time 72 seconds 20 to 120 seconds Values only appear when the Temp control equals Manual PID Tuning Heat Period 60 seconds 30 to 120 seconds Values only appear when the ...

Страница 32: ...es only appear when Auto Economizer Tuning is Disabled Econ Process Dead Time 72 seconds 20 to 120 seconds Values only appear when Auto Economizer Tuning is Disabled Econ Period 60 seconds 30 to 120 seconds Values only appear when Auto Economizer Tuning is Disabled Equipment Size Normal Normal or Oversized Value only appears when Temp Control Setup is not equal to On Off Control Network Setup FC C...

Страница 33: ... True Cooling Lockout Temp 40 F 4 C 0 to 100 F 18 to 38 C Heating Lockout Temp 80 F 27 C 0 to 100 F 18 to 38 C Unoccupied Off Delay 10 minutes 0 to 10 minutes Economizer Economizer Installed False True or False Economizer Min Pos 20 0 to 100 Economizer True Closed Voltage 2 VDC 0 to 10 VDC Economizer True Open Voltage 10 VDC 0 to 10 VDC Economizer True Dry Bulb Sepoint 68 F 20 C 0 to 100 F 18 to 3...

Страница 34: ...FF ZNH 0 to 100 RH B1 Status On or Off B2 Status On or Off EFF OAT 50 to 250 F 45 56 to 121 11 C EFF SAT 50 to 250 F 45 56 to 121 11 C FANSPD S On or Off CLG1 C On or Off CLG2 C On or Off HTG1 C On or Off HTG2 C On or Off OAD O 0 to 100 Trend HTG O 0 to 100 CLG O 0 to 100 Table 10 Menus and Submenus Part 7 of 9 Level 1 Level 2 LCD Screen Name Level 3 Default Values Available Values1 ...

Страница 35: ...g Unavailable due to Control Mode Supply Air Temperature 75 F 50 to 250 F 45 to 121 C Cooling OAT Lockout Inactive Active or Inactive Heating OAT Lockout Inactive Active or Inactive Comp Low OAT Lockout Inactive Active or Inactive Supp High Lockout Temp Inactive Active or Inactive Zone Temp Source Internal Sensor Unreliable Internal Sensor Remote Sensor Network Override Input Not Installed Control...

Страница 36: ...iring of the sensor 2 If intentionally disconnected reset sensors through the menu 3 If the problem persists order replacement units and return the affected devices to Johnson Controls under the RMA program Supply Temp Fail The External Supply Temperature sensor has been disconnected or has failed 1 Check the wiring of the sensor 2 If intentionally disconnected result fault by entering the menu en...

Страница 37: ... a Dirty Filter alarm is triggering the alarm Replace the filter in the equipment as explained in the manufacturer s instructions Calibration Corrupt Factory calibration data is lost or is not installed Order replacement units and return the affected devices to Johnson Controls under the RMA program Zone Temp Unreliable All sources of zone temperature are unreliable including the onboard sensor Or...

Страница 38: ... 1 Attempt to insert and use the USB drive again 2 Try a new USB drive 3 If problems persist order replacement units and return the affected devices to Johnson Controls under the RMA program Supply Fan Runtime Limit Extended The Supply Fan Runtime has exceeded the configured Supply Fan Runtime Limit 1 Service the Supply Fan 2 Reset the Supply Fan runtime Heating Ineffective The Supply Air Temperat...

Страница 39: ...ring configuration then set Heat Pump Supported to Yes The heat pump heats when it should be cooling and cools when it should heat Reversing Valve polarity is incorrectly set Consult the equipment documentation to verify reversing valve polarity then adjust the Reversing Valve Polarity menu option accordingly The staged equipment shuts off above the cooling setpoint or below the heating setpoint w...

Страница 40: ...r Order replacement units and return the affected devices to Johnson Controls under the RMA program The Bell icon is displayed on the TEC home page The fault has been detected on the TEC See Table 11 for TEC fault causes and resolution Partial Restore Complete is displayed when trying to restore settings from a backup file Not all of the items in the backup file have been restored This error can b...

Страница 41: ...ccuracy Temperature 0 9F 0 5C at 70 0 F 21 0 C typical calibrated Minimum Deadband 2F 1C between heating and cooling Occupancy Sensor Motion Detection Occupancy Sensing Models Minimum of 94 angular degrees up to a distance of 15 ft 4 6 m based on a clear line of sight Ambient Conditions Operating 32 to 122 F 0 to 50 C 95 RH maximum noncondensing Storage 22 to 122 F 30 to 50 C 95 RH maximum noncond...

Страница 42: ...e marks of their respective owners 2018 Johnson Controls Building Technologies Solutions 507 E Michigan Street Milwaukee WI 53202 42 European Single Point of Contact NA SA Single Point of Contact APAC Single Point of Contact JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA JOHNSON CONTROLS C O CONTROLS PRODUCT MANAGEMENT NO 22 BLOCK D NEW ...

Отзывы: