background image

TEC2664Z-3 BACnet® MS/TP Rooftop Controller for Stand-Alone and Networked Zoning Systems 
Installation Instructions

6

Connecting the MS/TP Bus

To connect the MS/TP Bus:

1.

Set the device address of the TEC2664Z-3 Rooftop 
Controller per the engineering drawings, and test 
for bus voltage, polarity, and isolation prior to wiring 
the MS/TP Bus. (See the 

RTC MAC

 parameter in 

Table 2 to set the device address for the rooftop 
controller.)

Note:

Pressing and holding the 

YES

 and 

NO

 keys 

simultaneously displays the assigned device address.

Note:

The wiring rules for the MS/TP Bus differ from 

the wiring rules for the N2 Bus. For more details on 
wiring the MS/TP Communications Bus, refer to the 

MS/TP Communications Bus Technical Bulletin 
(LIT-12011034)

.

2.

Observe the polarity when connecting the bus 
wires to the rooftop controller.

3.

After the bus wires are connected to the first 
rooftop controller, continue in a daisy-chained 
fashion to the next device on the MS/TP Bus.

Note:

The bus wiring must be twisted-pair lines. Do 

not run the bus wiring in the same conduit as line 
voltage wiring (30 VAC or above) or other wiring that 
switches power to highly inductive loads (such as 
contactors, coils, motors, or generators).

The MS/TP Bus requires proper termination and 
biasing at each end of a segment (a segment is a 
physically continuous length of wire). Because the 
rooftop controller is not equipped with end-of-line 
termination, a Johnson Controls MS-BACEOL-0 
End-of-Line Terminator (see Table 6; ordered 
separately) or similar device is recommended to 
provide this end-of-line termination. An end-of-line 
terminator is required if a supervisory controller is not 
at the end of the segment. If a supervisory controller is 
at the end of the segment, then the end-of-line 
terminator switch on the supervisory controller must be 
set in the ON position.

Note:

See Table 6 for end-of-line terminator ordering 

information.

For applications with a supervisory controller on the 
MS/TP Bus, set the supervisory controller to establish 
the baud rate, and set the rooftop controller for 
automatic baud rate detection.

For stand-alone applications where a supervisory 
controller is not present, at least one device on the 
MS/TP Bus must be set to establish the baud rate. It is 
recommended that the baud rate be set at only one 
rooftop controller, and all other devices be set for 
automatic baud rate detection. Doing so prevents 
duplicate devices from having mismatched baud rates. 
After the baud rate is set, recycle the power to the 
device that was used to set the baud rate.

Do not exceed the maximum number of devices 
allowed on a Field Bus. Be sure that the wiring 
terminations are set correctly, and that all 
communication wiring is daisy-chained with no taps.

A small green light under the rooftop controller cover 
(on the left edge, when facing the rooftop controller) 
indicates the communications mode when the rooftop 
controller is operating. The following blink codes may 
occur:

Short-Short-Long: Indicates that the baud rate is 
known and communication is active.

Short-Short: Indicates that the rooftop controller is 
scanning for the correct baud rate and there is no 
communication.

Off: Indicates that there is no power to the rooftop 
controller or the MS/TP wiring polarity is reversed.

Long: Indicates that the MS/TP communication 
daughter board is the wrong type for the main 
board.

Содержание TEC2664Z-3 BACnet

Страница 1: ...IMPORTANT The TEC2664Z 3 Rooftop Controller is intended to provide an input to equipment under normal operating conditions Where failure or malfunction of the rooftop controller could lead to personal injury or property damage to the controlled equipment or other property additional precautions must be designed into the control system Incorporate and maintain other devices such as supervisory or a...

Страница 2: ...er condensation other liquids or corrosive or flammable vapors of any kind Mount the rooftop controller in an accessible location to allow for easy access to the user interface keys Do not mount the rooftop controller on surfaces that are prone to vibration or in areas where electromagnetic emissions inductive interference or radio frequency signals from other devices or wiring can interfere with ...

Страница 3: ...f you need to install the rooftop controller on an electrical junction box use 2 1 2 x 4 in 63 x 101 mm square boxes with mud ring covers and avoid smaller 1 1 2 x 4 in 38 x 101 mm square or 3 x 2 in 76 x 51 mm boxes This procedure ensures you have enough space for cabling and end of line devices if needed Note For surface mount applications use durable mounting hardware such as Molly bolt anchors...

Страница 4: ...e making electrical connections to avoid electric shock CAUTION Risk of Property Damage Do not apply power to the system before checking all wiring connections Short circuited or improperly connected wires may result in permanent damage to the equipment IMPORTANT Make all wiring connections in accordance with local national and regional regulations Do not exceed the electrical ratings of the TEC26...

Страница 5: ...s RC and RH RH W1 W2 AU Aux DI1 SP Auxiliary Contact for Lighting On Off Actuation Exhaust Fan BPD 0 to 5 VDC Heating Stage II G Fan Output Scom RS OS Outside Air Sensor Discharge Air Sensor Remote Inputs Return Air Sensor Cooling Stage II Cooling Stage I Heating Stage I REF MS TP Connector RH W1 W2 Three Pole Right Top Connector 6 7 8 SP DI1 RS Scom Eight Pole Bottom Connector OS DS AU BPD 9 10 1...

Страница 6: ...end of line terminator is required if a supervisory controller is not at the end of the segment If a supervisory controller is at the end of the segment then the end of line terminator switch on the supervisory controller must be set in the ON position Note See Table 6 for end of line terminator ordering information For applications with a supervisory controller on the MS TP Bus set the supervisor...

Страница 7: ... See Main User Menu on page 8 access the Installer Configuration Menu or to exit the menu See Configuring the TEC2664Z 3 Rooftop Controller on page 8 Use the UP DOWN arrow keys to change the configuration parameters and to activate a setpoint adjustment Light Emitting Diodes LEDs Three LEDs are included to indicate the fan status and to show a call for heating or a call for cooling The LED is on w...

Страница 8: ...parameter displays use the YES key to choose the desired selection option 4 Press the YES key and then the NO key to continue scrolling through the parameters When the rooftop controller is in the Installer Configuration Menu and left unattended for approximately 8 seconds the rooftop controller reverts to the Auto Scroll Display Refer to the TEC Zoning Control System for Stand Alone and BACnet MS...

Страница 9: ...e three highest PI Heating or Cooling demands controls the rooftop controller AV_H5 The average of the five highest PI Heating or Cooling demands controls the rooftop controller Dis HL4 Sets the Discharge Air High Limit temperature value at which the heating stages are locked Default 120 0 F 49 0 C Range 70 0 F 21 0 C to 150 0 F 65 5 C Dis LL4 Sets the Discharge Air Low Limit temperature value at ...

Страница 10: ...r Service A Service alarm is displayed on the rooftop controller when the input is energized This input can be tied into the air conditioning unit control card which provides an alarm should there be a malfunction TOccTime Sets the duration of the Temporary Occupancy Time when the heating or cooling setpoints in the Occupied mode are established by an Override Function enabled in the Main User Men...

Страница 11: ...ct open Occupied contact closed Unoccupied n o Contact closed Occupied contact open Unoccupied Note The contact toggles with the internal Occupied Unoccupied schedule or the remote NSB contact if DI1 is used Prog rec Enables Progressive recovery Default off Note Progressive recovery is automatically disabled if DI1 is configured for remote NSB on Progressive recovery enabled Note The programmed Oc...

Страница 12: ...500 Pa 1 RTC MAC is the unique device address of the rooftop controller from 004 to 127 on the MS TP network 2 Local Unocc Override appears only when in the Unoccupied mode 3 When adjusting the numeric value press the UP or DOWN arrow key to change the value by single increments press and hold the UP or DOWN arrow key to change the numeric value in increments of ten 4 When adjusting the temperatur...

Страница 13: ... the onboard sensor readings of the rooftop controller The user can choose between a single highest PI demand an average of the three highest PI demands or an average of the five highest PI demands Using the five highest PI demands as an example five buffers are required in the BACnet module of the rooftop controller for the PI heating demand and five additional buffers are required for the PI coo...

Страница 14: ... Cooling Setpoint Heating Setpoint AO1 FIG cntrl_crv_1 Figure 10 Zone Controller Set for No Reheat AO2 0 VDC and BO5 Off Rooftop Controller in Heating Mode Cooling Setpoint Heating Setpoint AO1 FIG cntrl_crv_2 Figure 11 Zone Controller Set for Analog Duct Reheat Only BO5 Off Rooftop Controller in Cooling Mode Cooling Setpoint If AO2 stage is locked then AO1 minimum position Heating Setpoint AO1 AO...

Страница 15: ...troller Set for Analog Duct Reheat Only BO5 Off Rooftop Controller in Heating Mode Cooling Setpoint Heating Setpoint AO1 AO2 FIG cntrl_crv_4 Figure 13 Zone Controller Set for On Off Duct Reheat Only AO2 0 and On Off Reheat Time Base 10 Seconds Rooftop Controller in Cooling Mode Cooling Setpoint Heating Setpoint A01 B05 FIG cntrl_crv_5 ...

Страница 16: ...troller Set for On Off Duct Reheat Only AO2 0 and On Off Reheat Time Base 15 Minutes Rooftop Controller in Cooling Mode Cooling Setpoint Heating Setpoint AO1 B05 FIG cntrl_crv_6 Cooling Setpoint Heating Setpoint AO1 B05 FIG cntrl_crv_7 Figure 15 Zone Controller Set for On Off Duct Reheat Only AO2 Off Rooftop Controller in Heating Mode ...

Страница 17: ...ontroller Set for On Off Peripheral Reheat Only AO2 0 Rooftop Controller in Cooling Mode Cooling Setpoint Heating Setpoint AO1 B05 AO1 FIG cntrl_crv_8 Figure 17 Zone Controller Set for Terminal Reheat on AO2 and Peripheral Heating on BO5 Rooftop Controller in Cooling Mode Cooling Setpoint Heating Setpoint AO1 AO2 B05 FIG cntrl_crv_9 ...

Страница 18: ...nd Alone and Networked Zoning Systems Installation Instructions 18 Figure 18 Zone Controller Set for Terminal Reheat on AO2 and Peripheral Heating on BO5 Rooftop Controller in Heating Mode Cooling Setpoint Heating Setpoint AO1 AO2 B05 FIG cntrl_crv_10 ...

Страница 19: ... 3 Rooftop Controller See Rooftop Controller User Interface Keys on page 7 for a description of the five user interface keys Figure 19 shows a flow chart of the Main User Menu The system mode can be set to either Off or Auto The Auto mode allows the rooftop controller to determine from the average PI demand if a network is detected or from the return air sensor PI demands if a network is not detec...

Страница 20: ...wer failure of more than 6 hours DAS Alrm This alarm indicates a high or low alarm at the discharge air sensor If no discharge air sensor is connected 40 0 F 40 0 C reading the associated functions such as lockouts and alarms are disabled If the discharge air sensor is shorted 122 0 F 50 0 C reading the associated functions such as lockouts and alarms are enabled Service This alarm indicates there...

Страница 21: ... F or C Pressure x x W C or Pa Zone Seq Cool Zone Seq Heat Effective PI Heat Demand at the Rooftop Unit Effective PI Cool Demand at the Rooftop Unit Highest PI Heat Demand Zone Address Highest PI Cool Demand Zone Address Heat Out xxx Cool Out xxx Heat MAC xxx Cool MAC xxx 1 The outdoor temperature displays only if an outside air temperature sensor is installed If an outside air temperature sensor ...

Страница 22: ...tion Figure 20 Heating Cooling Stages Handling FIG htng_clng Figure 21 Bypass Damper Sequence Start G Fan Output On Bypass Damper Output Based on Static Pressure Input No Yes Bypass Damper Loop Disabled Bypass Damper Position 100 Forced Open 10 VDC Exit Exit FIG byps_dmpr Figure 22 System Mode and Fan Operation FIG systm_mde_fn_oprtn ...

Страница 23: ...ions 23 Figure 23 Zone Sequence Selection System Mode Off Zone Sequence Cool Avg PI Heating Demand Avg PI Cooling Demand Zone Sequence Heat NO NO Avg PI Cooling Demand Avg PI Heating Demand Zone Sequence Cool NO Avg PI Cooling Demand Avg PI Heating Demand Zone Sequence Stays in Existing Mode FIG zn_sqnc_slctn ...

Страница 24: ...rol TEC2664Z 3 Rooftop Controller for Control of Up to Two Stages of Heating and Two Stages of Cooling in Rooftop Proportional Bypass Damper Fan and Zone Demand Strategies Table 6 Accessories Order Separately Code Number Description SEN 600 1 Remote Inside Air Temperature Sensor TE 6361M 11 Duct Mount Air Temperature Sensor Metal Enclosure TE 6363P 11 2 Outside Air Temperature Sensor Plastic Enclo...

Страница 25: ...lines 32 Devices Maximum 4 000 ft 1 219 m Maximum Cable Length Temperature Range Backlit Display 40 0 F 40 0 C to 122 0 F 50 0 C in 0 5 Increments Heating Control 40 0 F 4 5 C to 90 0 F 32 0 C Cooling Control 54 0 F 12 0 C to 100 0 F 37 5 C Accuracy 0 9F 0 5C at 70 0 F 21 0 C Typical Calibrated Minimum Deadband 2F 1C between Heating and Cooling Ambient Conditions Operating 32 to 122 F 0 to 50 C 95...

Отзывы: