TEC2245-4 L
ON
W
ORKS
® Network Thermostat Controller with Single Proportional Output and One-Speed
Fan Control Installation Instructions
12
Set type
Provides the option of temporarily
changing the heating or cooling
setpoint by pressing the
UP/DOWN
arrow keys.
Default:
permnent
(temporar):
Local changes to the heating or cooling setpoints are
temporary, and remain effective for the specified TOccTime.
(permnent):
Local changes to the heating or cooling setpoints are
permanently stored in the thermostat controller memory.
Spt Func
Determines the operation and
usage of the local setpoint interface
by the user.
Default:
Dual Stp
(Attch Stp):
Single Occupied Setpoint Adjustment. The displayed
setpoint is the setpoint from the last action taken by the thermostat
controller, or the setpoint currently in use. Both the heating and cooling
setpoints are changed simultaneously, while respecting the minimum
configured deadband. If one setpoint is desired over the other, use the
MODE
key to toggle between the two setpoints.
(Dual Stp):
Dual Occupied Setpoint Adjustment. The displayed
setpoint is the setpoint from the last action taken by the thermostat
controller, or the setpoint currently in use. The heating and cooling
setpoints can be separated individually, allowing the minimum
configured deadband to expand. If one setpoint is desired over the
other, use the
MODE
key to toggle between the two setpoints.
TOccTime
Sets the duration of the Temporary
Occupancy Time when the heating
or cooling setpoints in the Occupied
mode are established by:
•
an Override Function enabled in
the Main User Menu (when the
thermostat controller is in the
Unoccupied mode)
•
a temporary heating or cooling
setpoint
Default:
2.0 hrs
Range:
0.0 to 24.0 hrs
in 1-hour increments
Deadband
Sets the minimum deadband
between the heating and cooling
setpoints.
Default:
2.0F°/1.0C°
Range:
2.0F°/1.0C° to 5.0F°/2.5C°
(adjustable in 1.0F°/0.5C°
increments)
Cal RS
Sets the desired room air sensor
calibration (offset). The offset can
be added to or subtracted from the
actual displayed room temperature.
Default:
0.0F°/0.0C°
Range:
-5.0F°/-2.5C° to 5.0F°/2.5C°
(adjustable in 1.0F°/0.5C°
increments)
Aux cont
Determines the auxiliary contact
function and configuration.
Default:
0
(0)
Not used,
or used for
reheat
If the Sequence of Operation is set to reheat
(2 or 3), ignore this parameter.
(1)
Auxiliary
N.O.
Occupied = contact closed
Unoccupied = contact open
The output
aligns with
occupancy.
(2)
Auxiliary
N.C.
Occupied = contact open
Unoccupied = contact
closed
(3)
Not used
(4)
(5)
Auxiliary On/Off control through the
auxiliary network command. The output
can be commanded through the network
for any required auxiliary functions via a
separate and dedicated network variable.
The output
aligns with
the
secondary
network
occupancy
command.
Table 4: Installer Configuration Menu (Part 4 of 5)
Parameter
Appearing
on Display
Description and Default
Selection Options