background image

TEC22x4-3 L

ON

W

ORKS

® Networked Multi-Stage Economizer Thermostats Installation Instructions

12

2.

Press the 

UP/DOWN

 arrow keys to locate the 

desired system mode. Press the 

YES

 key to select 

the desired system mode.

3.

Press the 

YES

 key to return to the Status Display 

Menu or press the 

NO

 key to return to the system 

mode selection menu.

Selecting the Fan Mode

The thermostat has three fan mode settings:

On Fan Mode (on):

 Energizes the fan all the time 

for both occupied and unoccupied states, even if 
the system mode is set to off.

Automatic Fan Mode (auto):

 Energizes the fan 

only on a call for heating or cooling, for both 
occupied and unoccupied states.

Smart Fan Mode (smart):

 Energizes the fan all 

the time for occupied states, and only on a call for 
heating or cooling in unoccupied states. This is the 
default setting.

To select the fan mode while in the Main User Menu:

1.

Press the 

NO

 key to all prompts until the fan mode 

prompt appears on the display. Press the 

YES

 key 

to set the fan mode.

2.

Press the 

UP/DOWN

 arrow keys to locate the 

desired fan mode. Press the 

YES

 key to select the 

desired fan mode.

3.

Press the 

YES

 key to return to the Status Display 

Menu or press the 

NO

 key to return to the fan 

mode selection menu.

Selecting Schedule (TEC2264-3 Only)

Programming the Daily Schedule – Two-Event

The schedule-setting menu is used to enter the 
occupied or unoccupied states for each day of the 
week. The schedule-setting menu reflects either a 
two- or a four-event schedule per day, based on what 
was selected in the 

2/4event 

parameter during the 

configuration process. If the schedule-setting menu 
does not reflect a two-event schedule, select two 
events in the 

2/4event

 parameter of the Installer 

Configuration Menu.

When changing the time, press the 

UP/DOWN

 arrow 

keys once to change the time in 1-minute increments; 
press and hold down the keys to change the time in 
30-minute increments.

Note:

Programming one of the digital inputs to remote 

NSB disables the menu.

To set the time schedule for a two-event schedule, 
follow the steps in Table 4. See Table 6, Events 1 
and 2, for an example of a two-event office schedule. 

Table 4:  Programming the Daily Schedule – 

Two-Event (Part 1 of 2)

Thermostat 
Display

Description

Press the 

MENU

 key while in the 

Status Display Menu to enter the 
Main User Menu.

Press the 

NO

 key to all prompts until 

the schedule set prompt appears on 
the display. Press the 

YES

 key to 

enter the scheduling menu.

Press the 

YES

 key to set the 

schedule for Monday or press the 

NO

 

key to advance to Tuesday.

Press the 

YES

 key to set the 

occupied start time for Monday or 
press the 

NO

 key to advance to 

Tuesday. Selecting 

NO

 will leave the 

thermostat in the unoccupied state 
for the entire day.

Press the 

UP/DOWN

 arrow keys to 

set the occupied start time. Press the 

YES

 key to enter the time.

Press the 

UP/DOWN

 arrow keys to 

set the unoccupied start time. Press 
the 

YES

 key to enter the time.

Press the 

YES

 key to set the 

schedule for Tuesday or press the 

NO

 key to advance to Wednesday.

Press the 

YES

 key to copy the 

schedule from the previous day. 
Press the 

NO

 key to set a different 

schedule.

RoomTemp
75.0

°

F

 

Schedule
set? Y/N 

Monday
set? Y/N 

Occupied
day? Y/N 

Occupied
12:00 AM 

Unoccup
12:00 AM 

Tuesday
set? Y/N 

Copy Y/N
previous 

Содержание TEC22 4-3 Series

Страница 1: ...nt Regulations Cet appareil num rique de la Classe A respecte toutes les exigences du R glement sur le mat riel brouilleur du Canada Installation Location Considerations Locate the TEC22x4 3 thermosta...

Страница 2: ...efully snap it into the locking tabs on the thermostat mounting base 9 Pull the pull tabs on each of the connectors and remove the screw terminal blocks as illustrated in Figure 4 Wiring When an exist...

Страница 3: ...7 8 9 10 11 12 13 14 15 16 Figure 6 Wiring the TEC22x4 3 Thermostats FIG TEC22x4_wrng 24 VAC Thermostat Power Y2 Y1 RC EC C If using the same power source for the thermostat and heating loads install...

Страница 4: ...of a segment a segment is a physically continuous length of wire The thermostat is not equipped with the ability to provide this termination therefore it cannot be located at the physical end of a LO...

Страница 5: ...Configuration Menu is used to set up the thermostat for application specific operation To access this menu press and hold the MENU key for approximately 8 seconds Configuring the TEC22x4 3 Thermostats...

Страница 6: ...thermostat RemNSB Remote Night Setback NSB via a time clock input an occupancy sensor or from a voltage free contact Contact open Occupied contact closed Unoccupied DI21 Configuration of Digital Inpu...

Страница 7: ...cycle timer Heat cph Sets the maximum number of Heating cycles per hour Default 4 0 Range 3 0 to 8 0 cycles per hour Cool cph Sets the maximum number of Cooling cycles per hour Default 4 0 Range 3 0 o...

Страница 8: ...H stage Reverts the operation of a two stage thermostat to a single stage thermostat when the second heating stage is not needed Default 2 0 1 0 One Stage 2 0 Two Stages C stage Reverts the operation...

Страница 9: ...fault 55 0 F 13 0 C Range 14 0 F 10 0 C to 70 0 F 21 0 C Min pos Sets the minimum position for the OA dampers on the economizer These dampers are energized to minimum position when the fan Terminal G...

Страница 10: ...e To resume the schedule while in the Main User Menu 1 Press the NO key to all prompts until the Cancel ovrd Y N prompt appears If the thermostat is in the unoccupied override state this is the first...

Страница 11: ...tus Display Menu to enter the Main User Menu Press the NO key to all prompts until the temperature setpoint prompt appears on the display it may be the first prompt Press the YES key to enter the temp...

Страница 12: ...event parameter during the configuration process If the schedule setting menu does not reflect a two event schedule select two events in the 2 4event parameter of the Installer Configuration Menu When...

Страница 13: ...prompt appears on the display Press the YES key to enter the scheduling menu Table 4 Programming the Daily Schedule Two Event Part 2 of 2 Thermostat Display Description Wednesda set Y N Exit Y N RoomT...

Страница 14: ...ayed press the YES key to store the day 6 Press the YES key to choose the time format or press the NO key to access the Main User Menu exit prompt 7 Press the UP DOWN arrow keys to select the desired...

Страница 15: ...ly voltage between RC and C is in the range of 19 to 30 VAC Check for tripped fuse or circuit breaker Overloaded power transformer Verify that the transformer used is powerful enough enough VAs to sup...

Страница 16: ...igital Inputs DI1 or DI2 Filter Indicates that the filter s is dirty in accordance with the programmable Digital Inputs DI1 or DI2 Frost ON Indicates that the heating is energized by the low limit fro...

Страница 17: ...g and Regulating Equipment FCC Compliant to CFR 47 Part 15 Subpart B Class A LONMARK Certification 3 4 pending Canada UL Listed File E27734 CCN XAPX7 Under CAN CSA C22 2 No 24 Temperature Indicating a...